Danfoss ECL Comfort 200 - P16 Operating instructions

Type
Operating instructions
Before you start
How to use this guide
This guide is divided into two parts:
• Daily Use (turn the guide over)
Yellow sections 01 - 09
• Installation and maintenance:
Grey sections 10 and onwards
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of hot water systems.
The ECL Comfort controller ensures you of the following;
• The hot water temperature will be adjusted to your
personal settings
.
Sketch an outline of your hot water system
The ECL Comfort controller is designed for a wide range of
hot water systems with different configurations and
capacities.
If your hot water system differs from the diagrams shown in
section 10, you may want to sketch an outline of the system
about to be installed. This makes it easier to use the
Installer’s Guide, which guides you step-by-step from
installation to the final adjustments before the end-user
takes over.
Note! The controller is pre-programmed with factory
settings that are shown in the relevant sections of this
guide.
Operating the ECL Controller and the ECL Card
The ECL Card has a yellow side for the daily use and a
grey side for the installation and maintenance.
Both sides of the card are divided into lines representing
the different options of control and programming.
Select the side of the ECL Card you want to
operate.
The light diode below the inserted ECL Card
indicates the chosen side, ie. left light for daily use
and right light for the installation and maintenance.
(See sections 15 and 16).
VI.7B.E2.02
Click here for cover P16
Installation
Identifying the system type
10
In this section you find the most frequently used
systems. If your system is not quite as shown below, find
the diagram which has the best resemblance to your
system and make your own combinations.
Hot water system type 1
Hot water system type 2
Installation
Hot water system type 3
Note!
System diagrams in this instruction are principal drawings and
do not necessarily contain all the components for hot water
systems.
Installation
Mounting the ECL Comfort
controller
11
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Installation
Installation
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 12
Jumper from 2 to common N-terminal.
Connecting the 230 V a.c. units
12
Electrical connections -
230 V a.c.
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted in each screw terminal.
1 L Voltage supply 230 V a.c.
2 N Voltage supply 230 V a.c.
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 Phase for motor exit
11 P2 Circulation pump 4(2)A 230 V a.c.
12 Phase for pump relay R2
Terminal Description Max. load
Connecting the sensors
Installation
Establish the jumper from 16 to common terminal.
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
15 and 16 System device bus
19 and 16 Hot water
temperature sensor (S3) ESMU
20 and 16 Return temperature ESMU/
sensor (S4) ESMA/ESMC
Terminal Description Type (recommended)
Installation
Connecting the 24 V a.c. and 230 V a.c. units
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 12
Jumper from 2 to common N-terminal.
13
Electrical connections -
24 V a.c.
1 L Voltage supply 24 V a.c.
2 N Voltage supply 24 V a.c.
3 M1 Gear motor - open 1 A 24 V a.c.
4 M1 Gear motor - close 1 A 24 V a.c.
5 24 V a.c. supply
for motor exit
11 K2* Relay for circulation pump 4(2)A 24 V a.c.
12 24 V a.c. supply for relay K2
Terminal Description Max. load
Cable cross section for voltage conductor: 0.75 ... 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted in each screw terminal.
* K2 auxiliary relay
Coil: 24 V a.c.
Connecting the sensors
Installation
Establish the jumper from 16 to common terminal.
15 and 16 System device bus
19 and 16 Hot water
temperature sensor (S3) ESMU
20 and 16 Return temperature ESMU/
sensor (S4) ESMA/ESMC
Terminal Description Type (recommended)
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Flow temperature sensor
(ESMU, ESMA or ESMC types)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends the
ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean at the area
where the sensor is mounted.
Do not move the sensor after it has been fastened in
order to avoid damage to the sensor element.
Hot water temperature sensor
(ESMU or ESMB types)
Place the hot water sensor according to the
manufacturers specification.
14
Placing the temperature
sensors
It is important that the sensors are mounted in the correct
position in your hot water system.
Special attention should be paid to the following
sensors:
Installation
15
Adapting the ECL Comfort
controller
Accept to set up the selection.
While the setup is in operation, the data transfer-display
will appear.
After initialising, the display will return to the standard
display line C of the yellow side of the ECL Card.
The controller is now ready to control the selected
hot water system. You can make your own
adjustments/settings in daily use and in the basic setup
and change the extended service settings.
Installation
Select the hot water system type printed on your
ECL Card.
Open the lid and switch on the controller. The display
shows the system type.
8
0 3 6 9 12 15 18 21 24
1
55
5
C
3
P 61
P
10
61
1
Insert the ECL Card with the grey side facing you.
See section 16 for general principles of operation and
section 17 for setting the time and date.
Select the grey side of the ECL Card for the
basic set-up and the extended service
parameters.
Basic set-up
16
Adjusting the ECL Card
settings
If several controllers are installed in the hot water system
you can write a title on the ECL Card with a permanent ink
pen.
Changing from one side of the ECL Card to the other
When changing from the grey side of the ECL Card to the
yellow side, you will always enter line C and the standard
display.
Changing from the yellow side to the grey side, you will
always enter line A - Time and date. See opposite page.
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the
grey side of the ECL Card. Select the grey side of the
ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 4:
Use the minus/plus buttons to adjust the
setting(s).
In some displays more than one setting or
value can be adjusted. Use the shift button to
switch between the options.
8
0 3 6 9 12 15 18 21 24
1
55
5
C
3
1
2
ON
4
80
Line
indicator
Settings to
be adjusted
Basic set-up
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12 hours,
the time and date have to be set again.
All other settings are stored as programmed.
Go to line A.
09
01
5609
5
A
3
1
Actual time
Month, day
Year
Use the shift button to switch between minutes,
hours, year, month and day
Set the correct time and date
Use the yellow side of the card to enter the day plan
settings.
See User’s Guide, section 4.
The grey side of the ECL Card.
Basic set-up
Monitoring temperatures and
system units - Line B
18
Go to line B.
If a sensor is not mounted or is disconnected, the
display will indicate it as
- -.
If the sensor is short -circuited, the display will indicate it as
- - - .
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, is indicated as ON below the pump symbol.
The grey side of the ECL Card.
2
1
ON
03
B
56
Controlled units
Return temperature
Flow
temperature
State indicator
Relationship between temperature and ohmic value
-10°C 961 Ohm
0°C 1000 Ohm
10°C 1039 Ohm
20°C 1078 Ohm
30°C 1117 Ohm
40°C 1156 Ohm
50°C 1195 Ohm
60°C 1234 Ohm
70°C 1273 Ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
Push the shift button to see:
- the calculated flow temperature
- the return temperature set point
19
Go to line B.
Manual control - Line B
Basic set-up
Shift to manual mode
Select the unit you want to control. The
selected unit symbol flashes.
Valves close or open while the
relevant button is pressed.
Pumps are switched off or on when the
relevant button is pressed.
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
The grey side of the ECL Card.
Controlled
units
6
2
1
ON
035
B
Controller
mode
Shift away from manual mode
2
ON
1 1
Setting the PI-regulation
Line 4 - 7
26
Basic set-up
Go to line 4.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A low integration time constant will make the
controller react fast but with less stability.
Setting range Factory setting
5 ... 999 sec. 20 sec.
5 Integration time constant
Setting range Factory setting
1 ... 250 K 80 K
4 Proportional band
Go to line 7.
Setting range Factory setting
0 ... 9 K 3 K
7 Neutral zone
Go to line 6.
Set the running time of the motorized valve
according to the example on opposite page. This
is the time it takes the valve to move from closed
to fully open position.
Setting range Factory setting
5 ... 250 sec. 15 sec.
6 Running time of the motorized valve
Set the proportional band
A higher value will result in a stable, but slow
regulation of the flow temperature.
Set the neutral zone to a high value if you can
accept a large variation in flow temperature.
When the actual flow temperature lies within the
neutral zone, the controller does not
activate the motorized valve.
Note! The valve is symmetrically around the
flow reference value.
The grey side of the ECL Card.
Setting to be adjusted
Line
indicator
1
2
ON
4
80
Basic set-up
If you want to tune the PI-regulation precisely, you can
use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (Line 4) until
the system starts hunting with a constant amplitude (it might
be necessary to force the system by setting an extreme
value).
Find the critical time period on the temperature recording or
use a stop watch.
This time period will be characteristic for the system, and you
can evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value in the
critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10 %.
Note! Make sure there is a consumption when you set the
parameters.
Time
Temp
Critical time period
How to calculate the running time of the motorized valve
The running time of the motorized valve is calculated using the
following methods:
Seated Valves
Running time = Valve stroke (mm) x actuator speed (sec/mm)
Example: 5.0 mm x 15 sec/mm = 75 sec.
Rotating Valves
Running time = Turning degrees x actuator speed (sec/degr.)
Example: 90 degrees x 2 = 180 sec.
VS2 15 3.0 AMV 100 90 270
VS2 15...25, VM2 15...25, AMV(E)
VB2 15...20 5.0 10, 20 15 75
VS2 15...25, VM2 15...25,
VB2 15...20 5.0 AMV(E) 30 3 15
VM2 32, VB2 25 7.0 AMV(E) 20 15 105
VM2 32, VB2 25 7.0 AMV(E) 30 3 21
Valve type Valve Actuator Actuator Running
stroke type speed time
(mm) (sec./mm) (sec.)
Control & overviews
29
Check list
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12 or 13.
Check that valves and pumps are connected
to the correct terminals.
See section 12 or 13.
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you and press
, if necessary.
Select manual operation in the controller
mode.
See section 2 in the User’s Guide.
Check that the temperatures shown in display
A and B match the actual sensors.
See section 1 in the User’s Guide.
Adapting the ECL Comfort controller to the
hot water system
29
Check list
Turn the ECL Card so that the grey side faces
you.
Select basic setup and extended service
settings. See section 16.
Set the time and date (Line A)
See section 17.
Check all settings referring to the grey side of the
ECL Card.
See section 26.
If your hot water system differs from the diagram
shown on the overleaf of the cover, you should
check and perhaps alter the service parameters.
Please pay special attention to line 35 and 36.
Control & overviews
ECL Card settings
30
A Time and date
B System information
Setting range Factory setting Your settings
See sections 16 & 17
See sections 18 & 19
4
Proportional band
1 ... 250 K 80 K
Set the PI-regulation, see section 26.
5
Integration time constant
5 ... 999 sec. 20 sec.
Set the PI-regulation, see section 26.
6
Running time of the motorized valve
5 ... 250 sec. 15 sec.
Set the PI-regulation, see section 26.
7
Neutral zone
0 ... 9 K 3 K
Set the PI-regulation, see section 26.
Control & overviews
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38