DH-SMT VA.7B.C2.02 © Danfoss 10/2005 3
Application sheet ECL Card P30
Outputs
Inputs
Safety
thermostat
If a safety thermostat is applied, it must wired
according to the drawing.
Terminal Description Max. load
1 L Voltage supply 230 V a.c.
(Phase)
2 N Voltage supply 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close
alt.: ABV thermo actuator
0.2 A 230 V a.c.
5 Phase for M1
9 P1 Circulation pump 4(2)A 230 V a.c.
10 Phase for pump relay
Terminal Description Max. load
1 L Voltage supply 24 V a.c.
2 N Voltage supply 24 V a.c.
3 M1 Gear motor - open 1 A 24 V a.c.
4 M1 Gear motor - close
alt.: ABV thermo actuator
1 A 24 V a.c.
5 24 V a.c. supply fo M1
9 K1 Relay for circulation pump
P1
10 24 V a.c. supply for relay
Terminal Description Type (recommended)
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2) ESM-10
19 and 16 Flow sensor (S3) ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC