  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort, Card C47 User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Application sheet
ECL Card
C47
DH-SMT VA.7C.C2.02 © Danfoss 10/2005 1
The room temperature can be controlled by
ESMR, the remote control ECA 61, or the room
panel ECA 60.
The return temperature measured by S3 can be
limited during heating or during heating and
hot-water charging by S3 (optional).
Reduced flow or room temperatures can be set
for desired periods.
Hot water circuit
The tank temperature is measured by the upper
sensor S6 (cut-in) and by the lower sensor S5
(cut-out). A low S6 temperature causes the
charging pump P2/P4 to start. P2/P4 stops again
when the cut-out temperature is reached at S5.
The motorised valve M2 controls the charging
temperature during hot water heating. The
charging temperature is measured by S4.
The return temperature in the hot water circuit
can be limited by S5 (optional).
Function
Applications
Heating circuit
The motorised valve M1 controls the flow
temperature which is measured by S2.
The flow temperature (2) in the heating circuit is
controlled in relation to the outdoor temperature
measured by S1.
1. Indirectly connected heating system with mixing loop and
secondarily connected storage tank with built-in heating coil
2. Indirectly connected heating system and primarily connected heat
exchanger for hot-water charging system with circulation through the tank
2a. Indirectly connected heating system and primarily connected heat
exchanger for hot-water charging system with circulation through the
heat exchanger
3. Indirectly connected heating system and primarily connected,
direct storage tank with built-in heating coil
2 VA.7C.C2.02 © Danfoss 10/2005 DH-SMT
Application sheet ECL Card C47
5. Indirectly connected heating system and secondarily connected
hot-water charging system with mixing loop
4. Indirectly connected heating system with mixing loop and
secondarily connected hot-water charging system
6. Indirectly connected heating system and primarily connected
precontrolled heat exchanger for hot-water charging system with
circulation through the tank
6a.Indirectly connected heating system and primarily connected
precontrolled heat exchanger for hot-water charging system with
circulation through the heat exchanger
Applications with relay module ECA 80
Type Description Code no.
C47 ECL Comfort Card - English 087B4821
C47 ECL Comfort Card - German 087B4818
C47 ECL Comfort Card - Danish 087B4823
Ordering
DH-SMT VA.7C.C2.02 © Danfoss 10/2005 3
Application sheet ECL Card C47
Terminal Description Max. load
1 L Voltage supply 230 V a.c.
2 N Voltage supply 230 V a.c.
3 M1 Gear motor - open/circuit I 0.2 A 230 V a.c.
4 M1 Gear motor - close/circuit I
alt.: ABV thermo actuator
0.2 A 230 V a.c.
5 230 V a.c. voltage supply for
motor exit/circuit I
6 M2 Gear motor - open/circuit II 0.2 A 230 V a.c.
7 M2 Gear motor - close/circuit II
alt.: ABV thermo actuator
0.2 A 230 V a.c.
8 230 V a.c. voltage supply
for motor exit/circuit II
9 P1 Circulation pump for
heating circuit I
4(2)A 230 V a.c.
10 230 V a.c. voltage supply for
pump relay R1
11 P2 Hot-water charging pump
for hot-water circuit II
4(2)A 230 V a.c.
12 230 V a.c. voltage supply for
pump relay R2
13 P3 Circulation pump for
hot-water circuit II
4(2)A 230 V a.c.
14 230 V a.c. voltage supply for
pump relay R3
Outputs
Terminal Description Max. load
1 L Voltage supply 24 V a.c.
2 N Voltage supply 24 V a.c.
3 M1 Gear motor - open/circuit I 1.0 A 24 V a.c.
4 M1 Gear motor - open/circuit I
alt.: ABV thermo actuator
1.0 A 24 V a.c.
5 24 V a.c. voltage supply for
motor exit/circuit I
6 M2 Gear motor - open/circuit II 1.0 A 24 V a.c.
7 M2 Gear motor - close/circuit II
alt.: ABV thermo actuator
1.0 A 24 V a.c.
8 24 V a.c. voltage supply for
motor exit/circuit II
9 P1 Circulation pump for
heating circuit I
4(2) A 24 V a.c.
10 24 V a.c. voltage supply for
pump relay R1
11 P2 Hot-water charging pump
for hot-water circuit II
4(2) A 24 V a.c.
12 24 V a.c. voltage supply
for pump relay R2
13 P3 Circulation pump for
hot-water circuit II
4(2) A 24 V a.c.
14 24 V a.c. voltage supply for
pump relay R3
The ECA 80 relay module is optional (only
used for the applications 4-6a).
The ECA 80 relay module is optional (only
used for the applications 4-6a).
4 VA.7C.C2.02 © Danfoss 10/2005 DH-SMT
Application sheet ECL Card C47
Inputs
Safety thermostat
Terminal
Sensor
Description Type
(recommended)
15 and 16 System device bus/
room panel/remote control
ECA 60 / 61
17 and 16 S1 Outdoor temp. sensor ESM-10
18 and 16 S2 Flow temp. sensor
circuit I
ESMU/ESM-11/
ESMC
19 and 16 S3 Return temp. sensor
circuit I
ESMU/ESM-11/
ESMC
20 and 16 S4 Flow temp. sensor
circuit II
ESMU/ESM-11/
ESMC
21 and 16 S5 Return temp. sensor
circuit I
or
lower hot-water sensor
circuit II
ESMU/ESM-11/
ESMC
ESMB
22 and 16 S6 Upper hot-water sensor ESMU/ESMB
If a safety thermostat is applied, it must wired according to the
drawing.
/