7.3.9 Breaker failure protection CCRBRF (50BF)................................................................................ 52
7.3.9.1 Checking the phase current operate value,
Pickup_PH
..................................................... 52
7.3.9.2 Checking the residual (ground fault) current operate value
Pickup_N
set below
Pickup_PH
................................................................................................................................... 52
7.3.9.3 Checking the re-trip and back-up times............................................................................... 53
7.3.9.4 Verifying the re-trip mode....................................................................................................... 53
7.3.9.5 Verifying the back-up trip mode............................................................................................ 54
7.3.9.6 Verifying the case
RetripMode
=
Contact
............................................................................ 54
7.3.9.7 Verifying the function mode
Current&Contact
...................................................................55
7.3.9.8 Completing the test..................................................................................................................55
7.3.10 Breaker failure protection CSPRBRF (50BF)..............................................................................56
7.3.10.1 Checking the phase current operate value, Pickup_PH.....................................................56
7.3.10.2 Checking the residual (GF) current operate value
IN>
set below IP>............................. 56
7.3.10.3 Checking the re-trip and back-up times...............................................................................56
7.3.10.4 Verifying the
RetripMode
.........................................................................................................57
7.3.10.5 Verifying the case
RetripMode
=
No CB Pos Check
............................................................ 57
7.3.10.6 Verifying the function mode
Current&Contact
...................................................................58
7.3.10.7 Checking the case with fault current below set value
Pickup_BlkCont
......................... 58
7.3.10.8 Checking the phase current operate value,
Pickup_PH
.....................................................58
7.3.10.9 Completing the test..................................................................................................................59
7.3.11 Stub protection STBPTOC (50STB).............................................................................................59
7.3.11.1 Measuring the operate limit of set values........................................................................... 59
7.3.11.2 Completing the test................................................................................................................. 60
7.3.12 Pole discrepancy protection CCRPLD (52PD)........................................................................... 60
7.3.12.1 Verifying the settings...............................................................................................................60
7.3.12.2 Completing the test................................................................................................................. 60
7.3.13 Broken conductor check BRCPTOC (46).....................................................................................61
7.3.13.1 Measuring the operate and time limit of set values...........................................................61
7.3.13.2 Completing the test..................................................................................................................61
7.3.14 Directional underpower protection GUPPDUP (37)..................................................................61
7.3.14.1 Verifying the settings............................................................................................................... 62
7.3.14.2 Completing the test..................................................................................................................63
7.3.15 Directional overpower protection GOPPDOP (32)................................................................... 63
7.3.15.1 Verifying the settings...............................................................................................................63
7.3.15.2 Completing the test................................................................................................................. 64
7.4 Testing voltage protection functions...........................................................................................64
7.4.1 Two step undervoltage protection UV2PTUV (27)................................................................... 64
7.4.1.1 Verifying the setting.................................................................................................................64
7.4.1.2 Completing the test..................................................................................................................65
7.4.2 Two step overvoltage protection OV2PTOV (59)..................................................................... 65
7.4.2.1 Verifying the settings...............................................................................................................65
7.4.2.2 Completing the test................................................................................................................. 66
7.4.3 Two step residual overvoltage protection ROV2PTOV (59N)................................................ 66
Table of contents
Breaker protection REQ650 3
Commissioning manual
© Copyright 2011 ABB. All rights reserved