  • Hello! I'm your chat assistant, and I've reviewed the instruction sheet for the Schneider Electric Resi9 R9TDBpppp Arc fault detection RCBO. This document provides crucial information on installation, safety, diagnosis and features like arc fault, earth leakage, overvoltage, short-circuit, and overload protection. It also explains the use of the multi-function button, VISI-SAFE indicator and the LED fault diagnosis. I'm here to help you with any questions you might have regarding this device.
  • Who should install this device?
    Can this device be repaired?
    What standards does this device comply with?
    What should you do before working on the device?
    What is the function of the multi-function button?
    What is VISI-SAFE?
    How often should I test the device?
1Description
Instruction sheet
Resi9 AFDD - R9TDBpppp
Arc fault detection RCBO (AFDD)
Compliant with AS/NZS 61009.1 & IEC 62606
BAClip for DIN rail mounting
BConnection terminals
CQR code for more information
DMulti-function button: Regular test / Diagnosis / Diagnosis reset
EVISI-TRIP: Earth leakage, arc and overvoltage fault tripping
FVISI-TRIP: Short-circuit and overload fault tripping
GVISI-SAFE: Positive contact indication
TM
HLED tripping fault diagonsis
GEX26747
PLEASE NOTE
b The installation, maintenance and eventual replacement of this device must only be carried
out by a qualified electrician.
b This device must not be repaired.
b All applicable local, regional and national regulations must be complied with during the
installation, use, maintenance and replacement of this device.
b This device should not be installed if, when unpacking it, you observe that it is damaged.
b Schneider Electric cannot be held responsible in the event of noncompliance with the
instructions in this document and in the documents to which it refers.
b The service instruction must be observed throughout the life time of this device.
b
b
b
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Turn off all power supplying this product before working on it.
Use a voltage tester with a suitable rated voltage in order to check
that all active conductors aren’t energized.
Carefully inspect the work area to check that no tools or objects could
have been left inside the equipment.
Failure to follow these instructions will result in death or serious injury.
DANGER
06/2023 1/4
GEX2674701-00
N
AB
D
H
C
Resi9
G
F
E
3
NOTICE
HAZARD OF WRONG INSULATION RESISTANCE TEST RESULT
In case of bottom feeding, disconnect the power supply wires from the bottom terminals before performing the insulation resistance test as per AS/NZS standards.
Failure to follow these instructions can result in wrong insulation resistance test result.
4Regular test
2Installation
Load terminals
Top Feeding
O OFF
Regular test
Load terminals
Bottom Feeding
Note:
1. Test the device at regular intervals by pressing the Test button (marked T), following the intervals defined in your local regulations or monthly.
2. After turning the device on, wait 2 seconds before pressing the test button.
Regular test
I ON
≤ 1 s
2 s
Regular test
I ON
O OFF
Regular test
O OFF
Regular test
Clack!
GEX2674701-00 2/4
Resi9
O OFF
Regular test
Resi9
Resi9Resi9
Resi9
Resi9
When supply is connected to the
bottom terminals, both Line & N
bottom terminals will remain live
even when toggle is switched off.
14 mm
1...16 mm²
1...10 mm²
C
2 N.m
5.5 mm
PZ2
5Diagnosis
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all output wires prior to the diagnostic steps.
Failure to follow these instructions will result in death or serious injury.
After 60 seconds, the blinking sequence stops and the LED is continuously switched OFF.
Regular test
I ON
Regular test
I ON
5 s
4
5 s
5 s
6
< 50 s
O OFF
Regular test
O OFF
Regular test
O OFF
Regular test
O OFF
Regular test
2
1
Top Feeding
Load terminals
x2x2 2 s
Load*
L
N
x3x3 2 s
Load*
L
N
x4x4 2 s
Load*
L
N
2 s x5x5
Load*
L
N
U > 275 V
2 s x6x6
Internal fault
5 s
Reset diagnosis mode
Note: Diagnosis operations are similar whether in top feed or bottom feed.
Load terminals
Bottom Feeding
(Example: Top Feeding)
GEX2674701-00 3/4
O OFF
Regular test
Resi9Resi9
Resi9Resi9
3
Resi9
5
Resi9
6More information
O OFF
Regular test
R9TDB
pppp
© 2023 Schneider Electric - All rights reserved.