Danfoss VLT HVAC Drive FC 102 Operating instructions

Category
Measuring, testing & control
Type
Operating instructions

This manual is also suitable for

Contents
1 Safety
1-1
Safety instructions 1-1
Before Commencing Repair Work 1-2
Special conditions 1-2
Avoid unintended Start. 1-3
Safe Stop of the Adjustable Frequency Drive 1-3
IT Line Power 1-5
2 Introduction
2-1
3 Mechanical installation
3-1
Before starting 3-1
Mechanical Dimensions 3-3
4 Electrical installation
4-1
How to connect 4-1
Line power wiring overview 4-6
Motor wiring overview 4-13
DC bus connection 4-17
Brake Connection Option 4-18
Relay Connection 4-20
How to Test Motor and Direction of Rotation. 4-24
Electrical Installation and Control Cables 4-27
5 How to operate the adjustable frequency drive
5-1
Three ways of operating 5-1
How to operate the numeric LCP (NLCP) 5-1
Tips and tricks 5-5
6 How to program the adjustable frequency drive
6-1
How to program 6-1
Quick Menu Mode 6-1
Function Set-ups 6-10
Parameter list 6-55
Main Menu Structure 6-55
0-** Operation and Display 6-56
1-** Load / Motor 6-58
2-** Brakes 6-59
VLT
®
HVAC Drive Instruction Manual Contents
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3-** Reference / Ramps 6-60
4-** Limits / Warnings 6-61
5-** Digital In / Out 6-62
6-** Analog In / Out 6-64
8-** Communication and Options 6-66
9-** Profibus 6-67
10-** CAN Fieldbus 6-68
11-** LonWorks 6-69
13-** Smart Logic Controller 6-70
14-** Special Functions 6-71
15-** FC Information 6-72
16-** Data Readouts 6-74
18-** Info & Readouts 6-76
20-** FC Closed-loop 6-77
21-** Ext. Closed-loop 6-78
22-** Application Functions 6-80
23-** Time-based Funtions 6-82
24-** Application Functions 2 6-83
25-** Cascade Controller 6-84
26-** Analog I / O Option MCB 109 6-86
7 Troubleshooting
7-1
Alarms and warnings 7-1
Fault messages 7-4
Acoustic noise or vibration 7-6
8 Specifications
8-1
General Specifications 8-1
Special Conditions
8-20
9 Index
9-1
Contents VLT
®
HVAC Drive Instruction Manual
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1Safety
1.1.1 Symbols
Symbols used in this manual:
NOTE!
Indicates something to be noted by the reader.
Indicates a general warning.
Indicates a high-voltage warning.
✮ Indicates a default setting
1.1.2 High voltage warning
The voltage of the adjustable frequency drive and the MCO 101 option card is dangerous whenever it is connected to line power.
Incorrect installation of the motor or adjustable frequency drive may cause damage to the equipment, serious injury or death. Con-
sequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations.
1.1.3 Safety instructions
Prior to using functions directly or indirectly influencing personal safety (e.g., Safe Stop, Fire Mode or other functions either forcing
the motor to stop or attempting to keep it functioning), a thorough risk analysis and system test must be carried out. The system
tests must include testing failure modes regarding the control signaling (analog and digital signals and serial communication.
NOTE!
Before using fire mode, contact Danfoss
VLT
®
HVAC Drive Instruction Manual 1 Safety
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1-1
1
• Make sure the adjustable frequency drive is properly grounded.
• Do not remove AC line input connections, motor connections or other power connections while the adjustable frequency drive is connected to
line power.
• Protect users against supply voltage.
• Protect the motor against overloading in accordance with national and local regulations.
• The ground leakage current exceeds 3.5 mA.
• The [OFF] key is not a safety switch. It does not disconnect the adjustable frequency drive from line power.
1.1.4 Before Commencing Repair Work
1. Disconnect the adjustable frequency drive from line power.
2. Disconnect DC bus terminals 88 and 89.
3. Wait at least the time mentioned above in the section General Warning.
4. Remove motor cable
1.1.5 Special conditions
Electrical ratings:
The rating indicated on the nameplate of the adjustable frequency drive is based on a typical 3-phase line power supply within the specified voltage,
current and temperature ranges, which are expected to be used in most applications.
The adjustable frequency drives also support other special applications, which affect the electrical ratings of the adjustable frequency drive.
Special conditions that affect the electrical ratings might be:
• Single phase applications.
• High temperature applications that require derating of the electrical ratings.
• Marine applications with more severe environmental conditions.
Other applications might also affect the electrical ratings.
Consult the relevant sections in this manual and in the
VLT HVAC Drive Design Guide, MG.11.BX.YY
for information about the electrical ratings.
Installation requirements:
The overall electrical safety of the adjustable frequency drive requires special installation considerations regarding:
• Fuses and circuit breakers for overcurrent and short-circuit protection
• Selection of power cables (line power, motor, brake, load sharing and relay)
• Grid configuration (IT,TN, grounded leg, etc.)
• Safety of low-voltage ports (PELV conditions).
Consult the relevant clauses in these instructions and in the
VLT HVAC Drive Design Guide
for information about the installation requirements.
1 Safety VLT
®
HVAC Drive Instruction Manual
1-2
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1
1.1.6 Caution
Caution
The adjustable frequency drive DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard, disconnect
the adjustable frequency drive from line power before carrying out maintenance. Wait at least as follows before doing service on the adjustable
frequency drive:
Voltage
Minimum Waiting Time
4 min. 15 min. 20 min. 30 min. 40 min.
200–240 V 1.1 - 3.7 kW 7.5–60 hp [5.5–45 kW]
380–480 V 1.1 - 7.5 kW 15–125 hp [11–90 kW]
150–300 hp [110–200
kW]
350–600 hp [250–450
kW]
525–600 V
1.5–10 hp [1.1–7.5
kW]
150–350 hp [110–250
kW]
450–750 hp [315–560
kW]
525–690 V 60–125 hp [45–90 kW]
150–350 hp [110– 250
kW]
450–750 hp [315– 560
kW]
850–1600 hp [630–
1200 kW]
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
1.1.7 Installation at high altitudes (PELV)
At altitudes above 6,600 feet [2 km], please contact Danfoss regarding PELV.
1.1.8 Avoid unintended Start.
While the adjustable frequency drive is connected to line power, the motor can be started/stopped using digital commands, bus
commands, references or via the Local Control Panel.
• Disconnect the adjustable frequency drive from line power whenever personal safety considerations make it necessary to avoid an unintended
start.
• To avoid an unintended start, always activate the [OFF] key before changing parameters.
• Unless terminal 37 is turned off, an electronic fault, temporary overload, a fault in the line power supply or lost motor connection may cause a
stopped motor to start.
1.1.9 Safe Stop of the Adjustable Frequency Drive
For versions equipped with a Safe Stop terminal 37 input, the adjustable frequency drive can perform the safety function
Safe Torque Off
(as defined by
draft CD IEC 61800-5-2) or
Stop Category 0
(as defined in EN 60204-1).
It is designed and deemed suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe Stop. Prior to integrating and
using safe stop in an installation, a thorough risk analysis must be carried out on the installation in order to determine whether the safe stop functionality
and safety category are appropriate and sufficient. In order to install and use the safe stop function in accordance with the requirements of Safety Category
3 in EN 954-1, the related information and instructions of the
VLT HVAC Drive Design Guide
must be followed! The information and instructions contained
in the Instruction Manual are not sufficient for a correct and safe use of the safe stop functionality!
VLT
®
HVAC Drive Instruction Manual 1 Safety
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1-3
1
130BA491
This certificate also covers FC 102 and FC 202!
1 Safety VLT
®
HVAC Drive Instruction Manual
1-4
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1
1.1.10 IT Line Power
IT Line Power
Do not connect 400 V adjustable frequency drives with RFI filters to line supplies with a voltage between phase and ground of more
than 440 V.
For IT line power and delta ground (grounded leg), AC line voltage may exceed 440 V between phase and ground.
par. 14-50
RFI 1
can be used to disconnect the internal RFI capacitors from the RFI filter to ground. If this is done, it will reduce the RFI performance
to A2 level.
1.1.11 Software version and approvals: VLT HVAC Drive
VLT HVAC Drive
Software version: 3.1.x
This manual can be used with all VLT HVAC Drive adjustable frequency drives with software version 3.1.x.
The software version number can be seen from par. 15-43
Software Version
.
1.1.12 Disposal Instructions
Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid leg-
islation.
VLT
®
HVAC Drive Instruction Manual 1 Safety
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1-5
1
1 Safety VLT
®
HVAC Drive Instruction Manual
1-6
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
1
2Introduction
2.1 Introduction
2.1.1 Available literature
- Instruction Manual MG.11.Ax.yy provides the necessary information for getting the adjustable frequency drive up and running.
- Design Guide MG.11.Bx.yy contains all the technical information about the adjustable frequency drive and customer design and applications.
- Programming Guide MG.11.Cx.yy provides information on how to program and includes complete parameter descriptions.
- Mounting Instruction, Analog I/O Option MCB109, MI.38.Bx.yy
-
PC-based Configuration Tool MCT 10, MG.10.Ax.yy enables the user to configure the adjustable frequency drive from a Windows
â„¢
based PC
environment.
-
Danfoss VLT
®
Energy Box software at
www.danfoss.com/BusinessAreas/DrivesSolutions
, then choose PC Software Download
-
VLT
®
VLT HVAC Drive Drive Applications, MG.11.Tx.yy
- Instruction Manual VLT HVAC Drive BACnet, MG.11.Dx.yy
- Instruction ManualVLT HVAC Drive Profibus, MG.33.Cx.yy.
- Instruction ManualVLT HVAC Drive Device Net, MG.33.Dx.yy
- Instruction ManualVLT HVAC Drive LonWorks, MG.11.Ex.yy
- Instruction Manual VLT HVAC Drive High Power, MG.11.Fx.yy
- Instruction ManualVLT HVAC Drive Metasys, MG.11.Gx.yy
- Instruction Manual VLT HVAC Drive FLN, MG.11.Zx.yy
x = Revision number
yy = Language code
Danfoss technical literature is available in print from your local Danfoss Sales Office or online at:
www.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/Technical+Documentation.htm
VLT
®
HVAC Drive Instruction Manual 2 Introduction
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
2-1
2
2.1.2 Adjustable Frequency Drive Identification
Below is an example of an identification label. This label is situated on the adjustable frequency drive and shows the type and the options with which the
unit is equipped. See below for details of how to read the Type code string (T/C).
Figure 2.1: This example shows an identification label.
NOTE!
Please have T/C (type code) number and serial number ready before contacting Danfoss.
2 Introduction VLT
®
HVAC Drive Instruction Manual
2-2
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
2
2.1.3 Type Code String
Description Pos Possible choice
Product group & FC Series 1-6 FC 102
Power rating 8-10 1.1–560 kW (P1K1 - P560)
Number of phases 11 Three phases (T)
AC line voltage 11-12
T 2: 200–240 V AC
T 4: 380–480 V AC
T 6: 525–600 V AC
Enclosure 13-15
E20: IP20
E21: IP 21/NEMA Type 1
E55: IP 55/NEMA Type 12
E2M: IP21/NEMA Type 1 w/ line power shield
E5M: IP 55/NEMA Type 12 w/ line power shield
E66: IP66
P21: IP21/NEMA Type 1 w/ backplate
P55: IP55/NEMA Type 12 w/ backplate
RFI filter 16-17
H1: RFI filter class A1/B
H2: RFI filter class A2
H3: RFI filter class A1/B (reduced cable length)
H4: RFI filter class A2/A1
Brake 18
X: No brake chopper included
B: Brake chopper included
T: Safe Stop
U: Safe + brake
Display 19
G: Graphical Local Control Panel (GLCP)
N: Numeric Local Control Panel (NLCP)
X: No Local Control Panel
Coating PCB 20
X. No coated PCB
C: Coated PCB
Line power option 21
X: No line power disconnect switch
1: With line power disconnect switch (IP55 only).
See Chapter 8 for max. cable sizes.
Adaptation 22 Reserved
Adaptation 23 Reserved
Software release 24-27 Current software
Software language 28
A options 29-30
AX: No options
A0: MCA 101 Profibus DP V1
A4: MCA 104 DeviceNet
AG: MCA 108 Lonworks
AJ: MCA 109 BACnet gateway
B options 31-32
BX: No option
BK: MCB 101 General purpose I/O option
BP: MCB 105 Relay option
BO: MCB 109 Analog I/O option
C0 options MCO 33-34 CX: No options
C1 options 35 X: No options
C option software 36-37 XX: Standard software
D options 38-39
DX: No option
D0: DC backup
Table 2.1: Type code description.
The various options and accessories are described further in the
VLT HVAC Drive Design Guide, MG.11.BX.YY
.
VLT
®
HVAC Drive Instruction Manual 2 Introduction
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
2-3
2
2.1.4 Abbreviations and Standards
Abbreviations: Terms: SI units: I-P units:
a Acceleration
m/s
2
ft/s
2
AWG American wire gauge
Auto Tune Automatic Motor Tuning
°C
Celsius
I Current A Amp
I
LIM
Current limit
Joule Energy J = N∙m ft-lb, Btu
°F
Fahrenheit
FC Adjustable Frequency Drive
f Frequency Hz Hz
kHz Kilohertz kHz kHz
LCP Local Control Panel
mA Milliampere
ms Millisecond
min Minute
MCT Motion Control Tool
M-TYPE Motor Type Dependent
Nm Newton meters in-lbs
I
M,N
Nominal motor current
f
M,N
Nominal motor frequency
P
M,N
Nominal motor power
U
M,N
Nominal motor voltage
par. Parameter
PELV Protective Extra Low Voltage
Watt Power W Btu/hr, hp
Pascal Pressure Pa = N/m² psi, psf, ft of water
I
INV
Rated Inverter Output Current
RPM Revolutions Per Minute
SR Size Related
T Temperature C F
t Time s s, hr
T
LIM
Torque limit
U Voltage V V
Table 2.2: Abbreviation and Standards table
2 Introduction VLT
®
HVAC Drive Instruction Manual
2-4
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
2
3 Mechanical installation
3.1 Before starting
3.1.1 Checklist
When unpacking the adjustable frequency drive, make sure that the unit is undamaged and complete. Use the following table to identify the packaging:
Enclosure
type:
A2
(IP 20-21)
A3
(IP 20-21)
A5
(IP 55-66)
B1/B3
(IP 20-21-55-66)
B2/B4
(IP 20-21-55-66)
C1/C3
(IP 20-21-55-66)
C2*/C4
(IP 20-21-55-66)
Unit size (kW):
200–240 V
1.1–3.0 3.7 1.1–3.7
5.5–11/
5.5–11
15/
15–18.5
18.5–30/
22–30
37-45/
37-45
380–480 V 1.1–4.0 5.5–7.5 1.1–7.5
11–18.5/
11–18.5
22-30/
22-37
37-55/
45-55
75-90/
75-90
525–600 V 1.1–7.5
11–18.5/
11–18.5
22-37/
22-37
45-55/
45-55
75-90/
75-90
Table 3.1: Unpacking table
Please note that it is recommended to have a selection of screwdrivers (phillips or cross-thread screwdriver and torx), a side-cutter, drill and knife handy
for unpacking and mounting the adjustable frequency drive. The packaging for these enclosures contains, as shown: accessory bag(s), documentation
and the unit. Depending on options fitted, there may be one or two bags and one or more booklets.
VLT
®
HVAC Drive Instruction Manual 3 Mechanical installation
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3-1
3
A2 A3 A5 B1 B2 B3 B4 C1 C2 C3 C4
IP20/21 IP20/21 IP55/66 IP21/55/66 IP21/55/66 IP20 IP20 IP21/55/66 IP21/55/66 IP20 IP20
Figure 3.1: Top and bottom mounting holes.
Figure 3.2: Top and bottom mounting holes. (B4+C3+C4 only)
Accessory bags containing necessary brackets, screws and connectors are included with the drives upon delivery.
All measurements in mm.
3.2.1 Mechanical Front Views
3 Mechanical installation VLT
®
HVAC Drive Instruction Manual
3-2
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3
Mechanical dimensions
Frame size (kW): A2 A3 A5 B1 B2 B3 B4 C1 C2 C3 C4
200–240 V
380–480 V
525–600 V
1.1–3.0
1.1–4.0
-
3.7
5.5–7.5
1.1–7.5
1.1–3.7
1.1–7.5
1.1–7.5
5.5–11
11–18.5
11–18.5
15
22-30
22-30
5.5–11
11–18.5
11–18.5
15–18.5
22–37
22–37
18.5–30
37–55
37–55
37-45
75-90
75-90
22-30
45-55
45-55
37-45
75-90
75-90
IP
NEMA
20
Chassis
21
Type 1
20
Chassis
21
Type 1
55/66
Type 12
21/ 55/66
Type 1/12
21/ 55/66
Type 1/12
20
Chassis
20
Chassis
21/ 55/66
Type 1/12
21/ 55/66
Type 1/12
20
Chassis
20
Chassis
Height (mm)
Enclosure A** 246 372 246 372 420 480 650 350 460 680 770 490 600
..with de-coupling plate A2 374 - 374 - - - - 419 595 - - 630 800
Backplate A1 268 375 268 375 420 480 650 399 520 680 770 550 660
Distance between mount. holes a 257 350 257 350 402 454 624 380 495 648 739 521 631
Width (mm)
Enclosure B 90 90 130 130 242 242 242 165 231 308 370 308 370
With one C option B 130 130 170 170 242 242 242 205 231 308 370 308 370
Backplate B 90 90 130 130 242 242 242 165 231 308 370 308 370
Distance between mount. holes b 70 70 110 110 215 210 210 140 200 272 334 270 330
Depth (mm)
Without option A/B C 205 205 205 205 200 260 260 248 242 310 335 333 333
With option A/B C* 220 220 220 220 200 260 260 262 242 310 335 333 333
Screw holes (mm)
c 8.0 8.0 8.0 8.0 8.2 12 12 8 - 12 12 - -
Diameter ø d 11 11 11 11 12 19 19 12 - 19 19 - -
Diameter ø e 5.5 5.5 5.5 5.5 6.5 9 9 6.8 8.5 9.0 9.0 8.5 8.5
f 9 9 9 9 9 9 9 7.9 15 9.8 9.8 17 17
Max weight
(kg)
4.9 5.3 6.6 7.0 14 23 27 12 23.5 45 65 35 50
* Depth of enclosure will vary with different options installed.
** The free space requirements are above and below the bare enclosure height measurement A. See section 3.2.3 for further information.
3.2.2 Mechanical Dimensions
VLT
®
HVAC Drive Instruction Manual 3 Mechanical installation
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3-3
3
Accessory Bags: Find the following parts included in the adjustable frequency drive accessory bags
Frame sizes A1, A2 and A3 Frame size A5 Frame sizes B1 and B2 Frame sizes C1 and C2
Frame size B3 Frame size B4 Frame size C3 Frame size C4
1 + 2 only available in units with brake chopper. For DC link connection (load sharing) the connector 1 can be ordered separately (Code no. 130B1064)
An eight-pole connector is included in accessory bag for FC 102 without Safe Stop.
3.2.3 Accessory Bags
3 Mechanical installation VLT
®
HVAC Drive Instruction Manual
3-4
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3
3.2.4 Mechanical mounting
All IP20 enclosure sizes as well as IP21/ IP55 enclosure sizes except A2 and A3 allow side-by-side installation.
If the IP 21 Enclosure kit (130B1122 or 130B1123) is used on enclosure A2 or A3,, there must be a minimum of 2 in [50 mm] of clearance between
drives.
For optimal cooling conditions, allow a free air passage above and below the adjustable frequency drive. See table below.
Air passage for different enclosures
Enclo-
sure:
A2 A3 A5 B1 B2 B3 B4 C1 C2 C3 C4
a (mm): 100 100 100 200 200 200 200 200 225 200 225
b (mm): 100 100 100 200 200 200 200 200 225 200 225
1. Drill holes in accordance with the measurements given.
2. You must provide screws suitable for the surface on which you want to mount the adjustable frequency drive. Re-tighten all four screws.
Table 3.2: Mounting frame sizes A5, B1, B2, B3, B4, C1, C2, C3 and C4 on a non-solid back wall, the drive must be provided with a backplate A due to
insufficient cooling air over the heatsink.
For heavier drives (B4, C3, C4), use a lift. First wall-mount the 2 lower bolts, then lift the drive onto the lower bolts. Finally, fasten the drive against the
wall with the 2 top bolts.
VLT
®
HVAC Drive Instruction Manual 3 Mechanical installation
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3-5
3
3.2.5 Safety Requirements for Mechanical Installation
Pay attention to the requirements that apply to integration and the field mounting kit. Follow the information in the list to avoid serious
damage or injury, especially when installing large units.
The adjustable frequency drive is cooled by air circulation.
To protect the unit from overheating, it must be ensured that the ambient temperature
does not exceed the maximum temperature stated for the
adjustable frequency drive
, and that the 24-hour average temperature
is not exceeded
. Locate the maximum temperature and 24-hour average in the
paragraph
Derating for Ambient Temperature
.
If the ambient temperature is in the range of 113°–131°F [45°–55°C], derating of the adjustable frequency drive will become relevant, see
Derating for
Ambient Temperature
.
The service life of the adjustable frequency drive is reduced if derating for ambient temperature is not taken into account.
3.2.6 Field Mounting
For field mounting the IP 21/IP 4X top/,TYPE 1 kits or IP 54/55 units are recommended.
3.2.7 Panel Through Mounting
A Panel Through mount kit is available for adjustable frequency drive series VLT HVAC Drive, VLT Aqua Drive and .
In order to increase heatsink cooling and reduce panel depth, the adjustable frequency drive may be mounted in a through panel. Furthermore, the built-
in fan can then be removed.
The kit is available for enclosures A5 through C2.
NOTE!
This kit cannot be used with cast front covers. No cover or imminent plastic cover must be used instead.
Information on ordering numbers is found in the
Design Guide
, section
Ordering Numbers.
More detailed information is available in the
Panel Through Mount Kit instruction, MI.33.H1.YY,
where yy=language code.
3 Mechanical installation VLT
®
HVAC Drive Instruction Manual
3-6
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
3
4 Electrical installation
4.1 How to connect
4.1.1 Cables General
NOTE!
For the VLT HVAC Drive High Power series line power and motor connections, please see the VLT HVAC Drive
High Power Instruction
ManualMG.11.FX.YY
.
NOTE!
Cables General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper (140°–167°F
[60°–75°C]) conductors are recommended.
Details of terminal tightening torques.
Power (kW) Torque (Nm)
Enclo-
sure
200–240
V
380–480
V
525–600
V
Line pow-
er
Motor
DC connec-
tion
Brake Ground Relay
A2 1.1–3.0 1.1–4.0 1.8 1.8 1.8 1.8 3 0.6
A3 3.7 5.5–7.5 1.1–7.5 1.8 1.8 1.8 1.8 3 0.6
A5 1.1–3.7 1.1–7.5 1.1–7.5 1.8 1.8 1.8 1.8 3 0.6
B1 5.5–11 11–18.5 - 1.8 1.8 1.5 1.5 3 0.6
B2
-
15
22
30
-
-
4.5
4.5
2)
4.5
4.5
2)
3.7
3.7
3.7
3.7
3
3
0.6
0.6
B3 5.5–11 11–18.5 11–18.5 1.8 1.8 1.8 1.8 3 0.6
B4 11–18.5 18.5–37 18.5–37 4.5 4.5 4.5 4.5 3 0.6
C1 18.5–30 37 - 55 - 10 10 10 10 3 0.6
C2 37 - 45 75 - 90
-
-
14/24
1)
14/24
1)
14 14 3 0.6
C3 18.5–30 37 - 55 37 - 55 10 10 10 10 3 0.6
C4 30 - 45 55 - 90 55 - 90
14/24
1)
14/24
1)
14 14 3 0.6
D1/D3 - 110 - 132 110 - 132 19 19 9.6 9.6 19 0.6
D2/D4 - 160-250 160-315 19 19 9.6 9.6 19 0.6
E1/E2 - 315-450 355-560 19 19 19 9.6 19 0.6
F1–F4
3)
-
Table 4.1: Tightening of terminals
1) For different cable dimensions x/y, where x ≤0.147 in² [95 mm²] and y≥0.147 in² [95 mm²]
2) Cable dimensions above 25 hp [18.5 kW] ≥ 0.0542 in
2
[35 mm
2
] and below 30 hp [22 kW] ≤ 0.0155 in
2
[10 mm
2
]
3) For data on the F-series, please consult VLT
®
HVAC Drive High Power Instruction Manual, MG.11.F1.02
4.1.2 Fuses
Branch circuit protection
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines, etc., must be short-circuit
and overcurrent protected according to the national/international regulations.
Short circuit protection
The adjustable frequency drive must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned
below to protect service personnel or other equipment in case of an internal failure in the unit. The adjustable frequency drive provides full short circuit
protection in case of a short circuit in the motor output.
VLT
®
HVAC Drive Instruction Manual 4 Electrical installation
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
4-1
4
Overcurrent protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Overcurrent protection must always be provided in
accordance with national regulations. The adjustable frequency drive is equipped with internal overcurrent protection that can be used for upstream
overload protection (UL applications excluded). See par. 4-18
Current Limit
in the
VLT HVAC Drive Programming Guide
. Fuses must be designed for
protection in a circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 500 V/600 V maximum.
Non-UL compliance
If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in the table below, which will ensure compliance with EN50178.
In case of malfunction, not following the recommendation may result in unnecessary damage to the adjustable frequency drive.
Non-UL compliance
Adjustable frequency
drive
Max. fuse size
Voltage Type
200–240 V
1K1-1K5
16A
1
200–240 V type gG
2K2
25A
1
200–240 V type gG
3K0
25A
1
200–240 V type gG
3K7
35A
1
200–240 V type gG
5K5
50A
1
200–240 V type gG
7K5
63A
1
200–240 V type gG
11K
63A
1
200–240 V type gG
15K
80A
1
200–240 V type gG
18K5
125A
1
200–240 V type gG
22K
125A
1
200–240 V type gG
30K
160A
1
200–240 V type gG
37K
200A
1
200–240 V type aR
45K
250A
1
200–240 V type aR
380–480 V
1K1
10A
1
380–500 V type gG
2K2-3K0
16A
1
380–500 V type gG
4K0-5K5
25A
1
380–500 V type gG
7K5
35A
1
380–500 V type gG
11K–15K
63A
1
380–500 V type gG
18K
63A
1
380–500 V type gG
22K
63A
1
380–500 V type gG
30K
80A
1
380–500 V type gG
37K
100A
1
380–500 V type gG
45K
125A
1
380–500 V type gG
55K
160A
1
380–500 V type gG
75K
250A
1
380–500 V type aR
90K
250A
1
380–500 V type aR
1) Max. fuses - see national/international regulations to select an appropriate fuse size.
Table 4.2: Non-UL fuses 200 V to 480 V
Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, 600 V AC maximum, with the rating plugs listed below can be used to meet
UL requirements.
Size/Type
Rating plug catalog # Amps
P110 SRPK800A300 300
P132 SRPK800A350 350
P160 SRPK800A400 400
P200 SRPK800A500 500
P250 SRPK800A600 600
Table 4.3: Circuit Breaker Tables - D enclosures, 380–480 V
Size/Type
Bussmann PN* Rating Ferraz Siba
P250 170M4017 700 A, 700 V 6.9URD31D08A0700 20 610 32.700
P315 170M6013 900 A, 700 V 6.9URD33D08A0900 20 630 32.900
P355 170M6013 900 A, 700 V 6.9URD33D08A0900 20 630 32.900
P400 170M6013 900 A, 700 V 6.9URD33D08A0900 20 630 32.900
Table 4.4: E enclosures, 380–480 V
4 Electrical installation VLT
®
HVAC Drive Instruction Manual
4-2
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
4
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178