(*) Spain only (**) Rest of World
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA · SPAIN · FAX +34 93 848 11 51
REF. JM629B01 CODE 401AB000403 ED. JANUARY 2011 UNINTERRUPTIBLE POWER SUPPLY (UPS)
ASK FOR LOCAL
CONDITIONS
YEARS
WARRANTY
MODEL
SLC TWIN 700 VA - 10kVA SLC TWIN/3 8 kVA - 20kVA
FORMAT
Tower or rack
(2)
Tower
TECHNOLOGY
On-line, double conversion, PFC, double DC bus
INPUT
Nominal voltage 220 / 230 / 240 V
(3)
3 x 380 / 400 / 415 V
Voltage range 176 ÷276 V 3 x 304 ÷ 478 V
Frequency 50 / 60 Hz
Frequency range ± 4 Hz
Power factor ≥ 0.98
(2)
≥ 0.95
Rectifier structure PFC with Soft Start
OUTPUT
Nominal voltage 220 / 230 / 240 V
Voltage accuracy
±1% steady state; ±2% transient state
Maximum slew rate
1 Hz / s
Synchronisation
Mains present ± 4 Hz; free running ± 0.05 Hz
(2)
Efficiency > 88% at full load
Total harmonic distortion (THDv)
≤
2% (linear load) ; ≤ 6% with non-linear load
(in accordance with EN 62040-3)
Permissible overloads
Up to 130% for 10 minutes; >130% for 1 second
Crest factor
3 to 1
BYPASS
Nominal voltage 220 / 230 / 240 V
Permissible voltage range
± 15%
Permissible frequency range
50 / 60 Hz ± 4 Hz
Overload
Up to 130% permanently; >130% for 1 second
BATTERIES
Battery type
Sealed, maintenance free
Protection Against overvoltages, under voltages and alternating current component
CHARGER
Technology
PWM
Charge type
P/U (Constant power - Constant voltage)
Recharging time
7 hours up to 90% 8 hours up to 90%
COMMUNICA-
TION
Ports RS-232
Monitoring software For platforms Windows, Linux and Mac
GENERALS
Operating temperature 0º C ÷ +40º C
Relative humidity Up to 95%, non-condensing
Operating altitude 2400 m.a.s.l.
Acoustic noise level at 1metre <45 dB
(2)
<60 dB
STANDARDS
Safety EN 62040-1; EN 60950-1; EN 60529
Electromagnetic compatibility (EMC) EN 62040-2
Operating VFI in accordance with EN 62040-3
Marking CE
Quality and environmental management ISO 9001 and ISO 14001 TÜV
Extended autonomies.
(1)
Galvanic isolation.
(1)
Other input / output voltages.
(1)
Tower or 19” rack format.
Single or three-phase input.
Redundant parallel system ≥ 4 kVA.
RS-232 interface.
Monitoring software.
SNMP adapter / Web.
(1)
AS-400 card.
USB port card.
(1)
MODBUS protocol.
(1)
Temperature-humidity sensor.
(1)
AC input.
AC output.
Maintenance bypass.
RS-232 interface.
Intelligent slot (SNMP, USB, AS-400).
Data line protection RJ-11/RJ-45.
Battery module connection.
Input protection.
Parallel port.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Pre-sale and after sale advisory service.
Multiple formulae for maintenance and telemain-
tenance (SICRES).
TECHNICAL SPECIFICATIONS
SLC TWIN
ON-LINE DOUBLE CONVERSION UPS
700 VA - 20 kVA
DESCRIPTION
ADAPTABILITY
COMMUNICATIONS
SERVICES
TOWER MODEL
POWER
(VA / W)
DIMENSIONS
(D x W x H mm)
WEIGHT
(Kg)
INPUT/OUTPUT
SLC - 700 - TWIN 700 / 490 410 x 145 x 220 13 II / II
SLC - 1000 - TWIN 1000 / 700 410 x 145 x 220 14 II / II
SLC - 1500 - TWIN 1500 / 1050 470 x 195 x 347 30 II / II
SLC - 2000 - TWIN 2000 / 1400 470 x 195 x 347 31 II / II
SLC - 3000 - TWIN 3000 / 2100 470 x 195 x 347 32 II / II
SLC - 4000 - TWIN 4000 / 2800 575 x 260 x 717 84 II / II
SLC - 5000 - TWIN 5000 / 3500 575 x 260 x 717 87 II / II
SLC - 6000 - TWIN 6000 / 4200 575 x 260 x 717 90 II / II
SLC - 8000 - TWIN 8000 / 5600 575 x 260 x 717 92 II ó III / II
SLC - 10000 - TWIN 10000 / 7000 575 x 260 x 717 93 II ó III / II
SLC - 12000 - TWIN 12000 / 8400 575 x 260 x 717 (x 2) 48 + 131 III / II
SLC - 15000 - TWIN 15000 / 10500 575 x 260 x 717 (x 2) 49 + 131 III / II
SLC - 20000 - TWIN 20000 / 14000 575 x 260 x 717 (x 2) 50 + 131 III / II
RACK 19” MODEL
POWER
(VA / W)
DIMENSIONS
(D x W x H mm)
WEIGHT
(Kg)
INPUT/OUTPUT
SLC - 700 - TWIN R 700 / 490 450 x 483 x 87 (2U) 16 II / II
SLC - 1000 - TWIN R 1000 / 700 450 x 483 x 87 (2U) 17 II / II
SLC - 1500 - TWIN R 1500 / 1050 450 x 483 x 87 (2U) (x 2) 10 + 28 II / II
SLC - 2000 - TWIN R 2000 / 1400 450 x 483 x 87 (2U) (x 2) 11 + 28 II / II
SLC - 3000 - TWIN R 3000 / 2100 450 x 483 x 87 (2U) (x 2) 12 + 28 II / II
SLC - 4000 - TWIN R 4000 / 2800 600 x 483 x 132 (3U) (x 2) 14 + 64 II / II
SLC - 5000 - TWIN R 5000 / 3500 600 x 483 x 132 (3U) (x 2) 14.5 + 64 II / II
SLC - 6000 - TWIN R 6000 / 4200 600 x 483 x 132 (3U) (x 2) 15 + 64 II / II
RANGE
(2) Depending on the model (3) Voltage availability of 110 / 115 / 120 / 127 V (4) On line mode
Values for standard autonomies. For other configurations, consult dimensions and weights.
Data may change without previous notice.
(1) Optional
1 kVA rack model
2 kVA tower model
6 kVA tower model