ICM Controls ICM292 Installation guide

Category
Motorcycle Accessories
Type
Installation guide
7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com LIAF107-1
FEATURES SPECIFICATIONS
ICM292
Gas Ignition Control Board
• Control voltage:24VAC(18-30VAC),60Hz
• Line voltage:115VAC,60Hz
• Power consumption:0.3Aplusgasvalvecurrentat24VAC
• Operating temperature:-40°C(-40°F)to75°C(176°F)
Timing
• Pre-purge:30seconds
• Trial for ignition:7seconds
• Retries:Twogroupsoftwo,30secondsdelaywithinthe
groupand3minutesdelaybetweengroups
• Lockout:1hour
• Post-purge:90,120,160and180seconds
Inputs
• Power:24VACandCOM
• Thermostat interface:R,W,YandG
• System switches:VentPressureandLimitswitches
(MainandOver-temperatureswitchesinseries)
• Flame Sensing
• Heat blower OFF delay: SW1toggleswitch
Install New Control
1. Groundyourself.Whenhandlingcircuitboard,holditbytheedges.
2. Fastencircuitboardwithretainingscrews.
3. Connectalllinevoltage,lowvoltage,andaccessorywires.
4. Verifythesequenceofoperation.
Safety Considerations
Onlytrainedpersonnelshouldinstallorserviceheatingequipment.Whenworkingwithheatingequip-
ment,besuretoreadandunderstandallprecautionsinthedocumentation,onlabels,andontags
thataccompanytheequipment.Failuretofollowallsafetyguidelinesmayresultindamagetoequip-
ment,severepersonalinjuryordeath.
Introduction
TheICM292DSIgasignitioncontrolreplacesthefollowingRheemmodel:62-24140-04.TheICM292
hasincorporatedLEDdiagnosticstoassistintroubleshooting.Faultcodeinformationcanbefound
inthisapplicationguide.Pleasekeepthisapplicationguidewiththefurnaceinstallationmanualfor
futurereference.
Electrostatic Discharge (ESD) Precautions
CAUTION!
Use caution when installing and servicing the furnace to avoid and control electrostatic discharge;
ESD can impact electronic components. These precautions must be followed to prevent
electrostatic discharge from hand tools and personnel. Following the precautions will protect the
control from ESD by discharging static electricity buildup to ground.
1. Disconnectallpowertothefurnace.Donottouchthecontrolorthewiringpriortodischargingyour
body’selectrostaticchargetoground.
2. Togroundyourself,touchyourhandandtoolstoaclean,metal(unpainted)furnacesurfacenear
thecontrolboard.
3. Servicethefurnaceaftertouchingthechassis.Yourbodywillrechargewithstaticelectricityasyou
shufeyourfeetormovearound,andyoumustregroundyourself.
4. Regroundyourselfifyoutouchungroundeditems.
5. Beforehandlinganewcontrol,regroundyourself;thiswillprotectthecontrol.Storeusedandnew
controlsinseparatecontainersbeforetouchingungroundedobjects.
6. ESDdamagecanalsobepreventedbyusinganESDservicekit.
AWcallfromthethermostatwillengagetheInducerDraftmotor.TheVentPressureswitchcloses.
Ignitionsequencebegins,gasvalveandsparkareengaged,providingthatsystemsafetyswitches
(MainandOver-temperatureswitchesinseries)areclosed.TheBlowermotorwillengageatHEAT
speed20secondsafterameisestablishedandsensed.OnWcallsatisfaction,theInducermotor
turnsoffafter10secondsandBlowermotorturnsoffaccordingtoHeatBlowerOffdelaysetting.
AGcallfromthethermostatwillengageBlowermotorwithoutdelayatFANspeed.Itdisengages
withoutdelaywhenGcallisremoved.
AYcallfromthethermostatwillengageBlowermotorwithoutdelayatCOOLspeed.Itdisengages
45secondsafterYcallissatised.
Sequence of Operation
Flame not established
1. Ifameisnotestablishedduringthe7secondinitialsequencethenthecontrolwillstartthenext
trialforignitionin30seconds.
2. Therewillbetwomoreattemptstoigniteafter3minutedelay,30secondsapartbeforethe
respectivefaultcodeistriggeredandignitiontrialsarestopped.
3.Thegasvalveisenergizedonlyduringtheignitionsequenceof7seconds.
4. Blowermotorisoffuntil20secondsafterameisestablished.
Flame out
1. Flameoutisconsideredwhenameislostduringheating.
2. WhenWsignalispresentandameisnotsensed,thengasvalvewilldisengageuntilthenexttrial
forignition
3. Ifameisnotestablishedontheimmediatesequence(2above)thenthecontrolwillcontinuewith
additionaltrialsforignition
4. InducerandBlowermotorswillcontinuerunningduringameoutscenario
Flame out of sequence
1. FlameoutofsequencerepresentsascenariowhenameissensedwhileWsignalisnotpresent.
2. InducerandBlowermotorswillbeengaged(ifnotalreadyrunning)andkeeprunningforaslongas
thefaultconditionispresent.
3.Thereis1hourlockoutbeforeaWcallcanbeexecutedoronpowerreset
Troubleshooting Tips
LED Fault Codes
Outputs
• Spark:SE
• Gas Valve:GV
• Inducer draft motor:IDM
• Blower motor:FAN,COOLand
HEATspeeds
• Electric Air Cleaner:EAC
• Humidier relay:HUM
• Heat/Cool relay:H/C
LED indicators
• Power, green LED:PWR
• Status, green LED:OK
• Flame status, yellow LED:FLAME
 
Direct Spark Ignition (DSI) control board
Microprocessor-based
Controls inducer motors, air cleaner (if equipped), humidier (if
equipped), spark ignitor and the gas valve
Monitors timing, trial for ignition, system switches, ame sensing
and lockout
100% lockout safety feature
Compatible with LP or Natural Gas
LED indication for status and fault codes to aid in troubleshooting
Replaces: Rheem 62-24140-04
LEDS Flashes Fault condition
GREEN ON Normaloperation
1Flash Ignitionfailure(4trials)
2Flashes Pressureswitchstuckopen
3Flashes Limitswitchesopen
4Flashes Pressureswitchstuckclosed
5Flashes Twinfault
6Flashes Brownoutvoltage
7Flashes Hotandneutralreversedornoground
Continuous Gasvalverelayshort
YELLOW RapidBlink Flameoutofsequence
SlowBlink Lowameornoame
ON Flamepresent
CAUTION!
To service control, and prior to disconnection, label all wires. Failure to do so may result in wiring
errors that can cause dangerous operation.
Remove Existing Control
1. TurnthermostattoOFFpositionorsetittothelowestpossiblesetting.
2. TurnOFFelectricalsupplytofurnace.
3. TurnOFFgassupplytofurnace.
CAUTION:Failure to turn off gas and electric supplies can result in explosion, re, death, or
personal injury.
4. Removefurnaceblowerandcontrolaccessdoors.
5. Disconnectthermostatwiresandhumidierwires(ifequippedwithahumidier).
6. Disconnectlinevoltage,blower,electronicaircleanerwires(ifequipped),andtransformerwires.
7. Removescrewsandanyotherfasteners,andtheoldcircuitboard.
8. Examinecontrolandcontrolboxtocheckforwaterstains.
9. Makerepairsifanysourcesofwaterleakagearefound.Besuretocheckhumidiers,evaporator
coils,andventsystemsintheareaofthecontrol.
Typical Wiring Diagram
7
1
4
2
5
6
3
8
9
7
1
4
2
5
6
3
8
0
BL
Y
BR
PR
R
R9
7
1
4
2
5
6
3
8
9G
R/W
PR
BR
R
R/W
G
MRLCLC MRLC
MRLC
R
R
Overtemperature Switches
(3-Maximum)
Main Limit
Control
NPC
GPR
Vent System
Pressure Switch
Drain System
Pressure Switch
NPC
BLMV BL
Y
G
MV
GND
GND
M
P
C
1
2
3
BL
Y
Honeywell
Gas Valve
White
Rogers
C RY WG
G Y W R
G Y W R
TH
LT OK
LT FLAME
LT PWR
24 VAC
24 VAC
Y
CT
X
2.0 AMP
Slowblow
Fuse
FU
P1
Integrated
Furnace Control
M2
M1
Heat/Cool
Fan
Cool
Heat
EACEAC L1Neutrals
R
BL
Y
BK BR
BR
M-HI
M-LO
LO
HI
IBM
COM
RC
IBM
BK
W
XFWR-PR1
W
W
W
32 41
32 41 4-Pin Connector P-8
G
G
FU
B K
PBS (Blower Door Switch)
Junction Box
N
H
DISC
To 115/1/60
Power Supply
G
W
BK
G
GND
3
2
43
4
1
6
53
2
4
1
6
5
3
4
6
53
4
6
5BK
W
BR/W
BK
W
BR/W
BR/W
BR/W
RCIDM
6-Pin
Connector
P-4 2-Pin
Connector
P-2
IDM
4-Pin
Connector
P-9
P-2
9-Pin
Connector
P-1
Flame Sensor
9-Pin
Connector
P-5
GND
SE
To CC
Unused Motor
Lead(s) 3
2.0 AMP
Slowblow Fuse CT
FU
GND
LC
MRLC MRLC
MRLC
P5-8 P1-8
P5-3 P1-3
P5-6 P1-6
P5-5
P1-4
P1-5
GVR
NPC
NPC
CR YW G
GND
MGV
P5-4
BR
FR
HCR
IDR
HUM
GVR
FLMS
GND
SE
P5-7
P1-7
IFC
24 VAC
L1
24 VAC
115 VAC NEU
COM
P9-4 P2-2P4-4
P8-1
P8-2
NEU
P9-3P4-3P2-1
IDR
GND
NEU
IBM
IDM
GND
GND
P4-5
P9-2
P4-6
P9-1
RC
RC
GND
PBS
M2
HCR
Heat
Fan
FR
HUM
BR
EAC
Heat/Cool
Cool
P8-3
FU
H N
To 115/1/60
Power Supply
DISC or CB
L1
P1-9
Notes:
1. Iffactorywiringofheatingand
coolingspeedsisnotdesirable,
refertospecicationssection
forappropriatespeeds.
2. Connectunusedmotorleadsto
M1and/orM2.
3. Modelswith3speedmotors;
 •Blueleadisformediumspeed
 •Noyellowleadonmotor
Legend:
ALC Aux.LimitControl(Temp)
BR BlowerRelay
CC CompressorContactor
CT ControlTransformer
DISC DisconnectSwitch
EAC ElectricAirCleaner
FR FanRelay
FLMS FlameSensor
FU Fuse
GND Ground
GVR GasValveRelay
HCR Heat/CoolRelay
HUM HumidierRelay
IBM IndoorBlowerMotor
IDM IndoorDraftMotor
IDR IndoorDraftRelay
IFC IntegratedFurnaceControl
IR IgnitionRelay
LC LimitControl
MGV MainGasValve
MRLC MainResetLimitControl
MV MainValve
NPC NegativePressureControl
PBS PushButtonSwitch
PL Plug
RC RunCapacitor
SE SparkIngitionElectrode
TH Thermostat(H/C)
 WireNut
Wiring Information:
LINEVOLTAGE
•Factorystandard
•FactoryOption
•FieldInstalled
LOWVOLTAGE
•Factorystandard
•FactoryOption
•FieldInstalled
REPLACEMENTWIRE
•Mustbethesamesizeandtypeof
insulationasoriginal(105C*Min.)
WARNING
•Cabinetmustbepremanently
groundedandconformtoI.E.C.,
N.E.C,C.E.C,andlocalcodes
Wire Color Codes:
BK Black
BR Brown
BL Blue
G Green
GY Gray
Electrical Wiring Diagram:
•UpowBlowerInducedDraft
•GasFiredForcedAirFurnace
•SingleStageHeat
•SingleStageCool
•DirectSparkIgnition
O Orange
PR Purple
R Red
W White
Y Yellow
  • Page 1 1
  • Page 2 2

ICM Controls ICM292 Installation guide

Category
Motorcycle Accessories
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI