Bradley S19-310FW Installation guide

Type
Installation guide

This manual is also suitable for

P.O. Box 309, Menomonee Falls, WI USA 53052-0309
PHONE 800.BRADLEY (800.272.3539) FAX 262.251.5817
bradleycorp.com
Installation
215-163FW Rev. P; ECN 08-538
© 2008 Bradley Corporation
Page 1 of 13 11/7/08
S19-310FW
Combination Drench Shower and
Eye/Face Wash
Combiné douche oculaire/faciale
Combinación de ducha de
aspersión y lavaojos/rostro
Table of Contents
Pre-Installation Information . . . . . . . . . . . . . . 2
Installation Instructions. . . . . . . . . . . . . . . . . . 3
Assembly of Components . . . . . . . . . . . . . . . 4
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table des matières
Avant l’installation. . . . . . . . . . . . . . . . . . . . . . 6
Instructions d’installation . . . . . . . . . . . . . . . . 7
Assemblage des composantes . . . . . . . . . . . 8
Liste des pièces . . . . . . . . . . . . . . . . . . . . . . . 9
Contenido
Información previa a la instalación. . . . . . . . 10
Instrucciones de instalación. . . . . . . . . . . . . 11
Armado de los componentes . . . . . . . . . . . . 12
Lista de piezas . . . . . . . . . . . . . . . . . . . . . . . 13
2
S19-310FW Installation
11/7/08 Bradley Corporation • 215-163FW Rev. P; ECN 08-538
IMPORTANT
Read this installation manual completely to ensure proper installation, then file it
with the owner or maintenance department. Compliance and conformity to drain
requirements and other local codes and ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before
discarding any packaging material. If any parts are missing, do not begin installation
until you obtain the missing parts.
Flush the water supply lines before beginning installation and after installation is
complete. Test the unit for leaks and adequate water flow. Main water supply to the
eyewash should be “ON” at all times. Provisions shall be made to prevent unauthorized
shutoff.
The ANSI Z358.1 standard requires an uninterruptible supply of flushing fluid at a
minimum 30 PSI (0.21 MPa) flowing pressure. Flushing fluid should be tepid per ANSI
Z358.1.
The inspection and testing results of this equipment should be recorded weekly to verify
proper operation. This equipment should be inspected annually to ensure compliance
with ANSI Z358.1.
Workers who may come in contact with potentially hazardous materials should be
trained regarding the placement and proper operation of emergency equipment per ANSI
Z358.1.
For questions regarding the operation or installation of this product, visit www.
bradleycorp.com or call 1-800-BRADLEY.
Product warranties and parts information may also be found under ”Products” on our
web site at www.bradleycorp.com.
Installation
THIS
SIDE
UP
Packing List
P
.
O
.
B
o
x
3
0
9
,
M
e
n
o
m
o
n
e
e
F
a
ll
s
,
W
I 5
3
0
5
1
R
T
E
S
T
T
H
I
S
U
N
I
T
E
A
C
H
W
E
E
K
Test-o
perate v
alv
e(s) ea
c
h w
eek an
d sign
belo
w
.
R
eport an
y m
alfunction
s immed
iat
el
y
.
Ventil(e) w
öc
hen
tlic
h im
Testbe
trie
b
prüfen,
b
est
ätigt
durch U
ntersc
hrift. J
eglic
he S
törun
g s
of
or
t m
elden.
Date
Datum
Date
Signed
Unterschrift
Signe
Date
Date
Date
Signed
Signed
Signed
D
I
E
S
E
S
G
E
R
Ä
T
1
S
T
W
Ö
C
H
E
N
T
L
IC
H
Z
U
P
R
Ü
F
E
N
.
E
S
S
A
I
H
E
B
D
O
M
A
D
A
I
R
E
Test le
fonctio
nnem
ent d
es v
alv
es
chaque sem
aine et
sign
e en b
as. S
'il y
à quelqu
e c
ho
se qui n
e v
a p
as fait
un
rappor
t im
m
édiatem
ent.
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
114-051
3
Installation S19-310FW
Bradley Corporation • 215-163FW Rev. P; ECN 08-538 11/7/08
Installation
Supplies Required:
(3) 3/8" floor anchors and bolts
Teflon tape and pipe sealant
Piping to 1-1/4" NPT water supply inlet and to 1-1/4"
NPT drain outlet on unit
• Adequate supply pipe supports
Min. 4" drain to accommodate 30 gallons per minute
discharge for shower waste
OPTIONAL: sign-mounting hardware
NOTE: Local codes may require the installation
of a backfl ow prevention valve to complete proper
installation. Compliance with local codes is the
responsibility of the installer. Valve must be tested
annually to verify that it is functioning properly. Backfl ow
prevention valves are not included with the fi xture and
may be supplied by the contractor or purchased from
Bradley Corporation.
Step 1: Secure base to floor
1. Install three suitable anchors (supplied by installer)
for 3/8" bolts in the floor.
2. Bolt the base to the floor anchors using 3/8" bolts
(supplied by installer).
Step 2: Assemble components
1. Assemble the remaining unit components as
shown on page 4.
Apply teflon tape or pipe sealant (supplied by
installer) as required to all male-threaded pipe
joints.
Use the rubber grip pad provided or a strap
wrench around pipes when tightening to prevent
marring. Place the grip pad on the pipe, then
put the wrench over the grip pad and turn the
pipe with the wrench.
The bottom edge of the showerhead should be
7'-2" (2180mm) from the floor.
Step 3: Connect water supply
IMPORTANT: Do not rely on Bradley’s
Combination Unit to support supply piping.
1. Connect water supply piping to 1-1/4" NPT inlet
on unit (piping by installer). Provide adequate
supports (by installer) for supply pipe using pipe
hangers or other means.
2. Connect drain piping to 1-1/4" NPT drain outlet on
unit (piping by installer).
3. Hang the safety sign from the unit with the curtain
hooks provided (or mount it to the wall using sign-
mounting hardware by installer).
NOTE: All dimensions assume standard thread
engagement. Variations in manufacturing allow for
+/- 1/8" (3mm) per threaded joint. To fi nd the tolerance
of a dimension, add the number of thread joints in
between a dimension and multiply it by 1/8" (3mm).
Ø 9" (229mm) Flange
with (3) Ø 3/8" (10mm)
Holes on Ø 8" (203mm)
Bolt Circle
Top View From Bowl
9"
(229mm)
25-3/8"
(645mm)
7'-2"
(2180mm)
to Floor
24"
(610mm)
Ø 10"
(254mm)
36-3/8"
(924mm)
6-1/2"
(165mm)
10-1/2"
(267mm)
9-1/2"
(241mm)
66"
(1676mm)
to Floor
6"
(152mm)
4-1/2"
(114mm)
Ø 3.1"
(78.7mm)
4
S19-310FW Installation
11/7/08 Bradley Corporation • 215-163FW Rev. P; ECN 08-538
Assembly of Components
15
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
114-052
P.O. Box 309, Menomonee Falls, WI 53051
R
TEST THIS UNIT EACH WEEK
Test-operate valve(s) each week and sign below.
Report any malfunctions immediately.
Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt
durch Unterschrift. Jegliche Störung sofort melden.
Date
Datum
Date
Signed
Unterschrift
Signe
Date
Date
Date Signed
Signed
Signed
DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.
ESSAI HEBDOMADAIRE
Test le fonctionnement des valves chaque semaine et
signe en bas. S'il y à quelque chose qui ne va pas fait
un rapport immédiatement.
28
29
13
1
2
3
4
2
5
6
2
7
8
9
3
11
12
17
19
17
20
24
19
25
26.1
26.2
26.3
26.4
26.5
23
21.1
21
22
18
10
10.1
10.31
10.2
10.4
10.3
10.5
26
27
27.1
27.2
27.3
14
14.1
Optional 1-1/4" NPT Supply
Inlet (best for rigid support)
1-1/4" NPT
Supply Inlet
1-1/4" NPT
Drain Outlet
NOTE: If tee (Item 7) is used as a supply
inlet, use plug (Item 8) on tee (Item 2).
NOTE: Items 10.1–10.5 come preassembled as Item 10.
Items 26.1–26.5 come preassembled as Item 26.
Items 27.1–27.3 come preassembled as Item 27.
NOTE: Use
teflon tape
only.
5
Installation S19-310FW
Bradley Corporation • 215-163FW Rev. P; ECN 08-538 11/7/08
Parts List
1 131-059 1 Base
2 169-727 3 Pipe Tee 1-1/4" NPT
3 113-006LW 2 Pipe 1-1/4" NPT x 22-1/2"
4 S06-136 1 Plugged Nipple 1-1/4" NPT x 3"
5 169-841 1 Reducing Tee
6 113-006LC 1 Pipe 1-1/4" NPT x 27-1/2"
7 169-722 1 Reducing Tee
8 169-724 1 Pipe Plug 1-1/4" NPT
9 113-006LL 1 Pipe 1" NPT x 9"
10 S30-059 1 Stay-Open Ball Valve Assy. 1" NPT
10.1 142-002DC 1 Lockwasher
10.2 128-129 1 Handle
10.3 S27-278 1 1" Ball Valve with Jam Nut
10.31 110-214 1 Jam Nut only
10.4 140-720 1 Stop Bracket
10.5 124-048 1 Washer, Friction
11 151-001 2 Curtain Hook
12 113-006LK 1 Pipe 1" NPT x 12"
13 169-847 1 90° Elbow 1" NPT
14 S24-188 1 Showerhead Assembly
14.1 S24-187 1 Flow Control Assembly, 23 GPM
15 128-156A 1 Pull Rod - 24" Long
16 269-915 1 Grip Pad (not shown)
17 169-025 2 Elbow 1/2" NPT
18 169-726 1 Union 1/2" Female NPT
19 113-006LQ 3 Pipe 1/2" NPT x 3-1/2"
20 113-006QX 1 Pipe 1-1/4" NPT x 7-3/32"
21 S27-282 1 1/2" Ball Valve with Jam Nut
21.1 110-215 1 Jam Nut only
22 128-135 1 Handle, Plastic
23 142-002DA 1 Lockwasher
24 169-764 1 90° Pipe Elbow 1-1/4" NPT
25 113-006LE 1 Pipe Nipple 1-1/4" NPT x 3"
26 S90-095 1 Plastic Bowl Assembly
26.1 111-039 1 Inlet Drain Fitting
26.2 124-028 1 Center Seal Gasket
26.3 154-058 1 Plastic Eyewash Bowl
26.4 173-025 1 Cup Strainer
26.5 113-1150 1 Supply Pipe
27 S05-064D 1 EFW Assembly
27.1 S05-091P 1 Eye/Face Wash Yoke
27.2 S05-135 2 Sprayhead
27.3 S53-063 2 Tethered Dust Cover
28 114-052 1 Safety Sign
29 204-421 1 Emergency Inspection Tag
Item Part No. Qty Description Item Part No. Qty Description
Prepack S45-122 includes items 21, 21.1, 22, 23
Prepack S45-123 includes items 21.1, 22, 23
6
S19-310FW Installation
11/7/08 Bradley Corporation • 215-163FW Rev. P; ECN 08-538
IMPORTANT
Lire ce manuel d’installation dans son intégralité pour garantir une installation
appropriée. Une fois celle-ci terminée, classer ce manuel auprès du service à la clientèle
ou d’entretien. L’installateur est responsable de la conformité de l’installation aux codes
pour des drain et codes et règlements en vigueur.
Assurez-vous que toutes les pièces sont incluses dans l’emballage et qu’il n’en manque
aucune avant de jeter l’emballage. Ne commencez pas l’assemblage avant de recevoir
les pièces manquantes.
Rincez la conduite d’alimentation avant et apres l’installation. Assurez-vous que le débit
d’eau est adéquat et qu’il n’y a pas de fuites. L’alimentation principale en eau doit être
toujours OUVERTE. On devra prévoir des dispositions pour empêcher tout arrêt non
autorisé.
La norme ANSI Z358.1 requiert une alimentation sans coupure du liquide de rinçage
à une pression minimum de 30 psi (0.21 MPa). Le liquide de rinçage doit être tiède
conformément à la norme ANSI Z358.1.
Inspectez et testez cet équipement une fois par semaine pour en assurer le bon
fonctionement. Notez les dates d’inspection. Ce matériel doit être inspecté une fois par
an pour assurer sa conformité à la norme ANSI Z358.1.
Les ouvriers susceptibles d’entrer en contact avec des matières potentiellement
dangereuses doivent recevoir une formation sur la mise en place et le bon
fonctionnement du matériel d’urgence conformément à la norme ANSI Z358.1.
Pour toute question concernant le fonctionnement ou l’installation de ce produit,
consulter le site www.bradleycorp.com ou appeler le 1-800-BRADLEY.
Les garanties de produits figurent sous la rubrique « Informations techniques » sur
notre site Internet à www.bradleycorp.com.
Installation
THIS
SIDE
UP
Packing List
P
.
O
.
Bo
x
3
0
9
, M
e
n
o
m
o
n
e
e
F
a
ll
s
,
W
I 5
3
0
5
1
R
T
E
S
T
T
H
IS
U
N
IT
E
A
C
H
W
E
E
K
Test-o
perate v
alv
e(s) eac
h week an
d sign
b
elo
w
.
R
eport an
y m
alfun
ctions im
me
d
iat
el
y.
Ventil(e) w
ö
c
hen
tlic
h im
Testbetrieb
prüfen,
b
estätigt
du
rc
h U
n
tersc
hrift. Jeglic
he S
törun
g sof
or
t melden
.
Date
Datum
Date
Signed
Unterschrift
Signe
Date
Date
Date
Signed
Signed
Signed
D
IE
S
E
S
G
E
R
Ä
T
1
S
T
W
Ö
C
H
E
N
T
L
IC
H
Z
U
P
R
Ü
F
E
N
.
E
S
S
A
I
H
E
B
D
O
M
A
D
A
I
R
E
Test le
fonctio
nnem
ent d
es v
alv
es
ch
aque
semaine et
sign
e en b
as. S
'il y
à quelqu
e c
ho
se qui ne v
a p
as fait
un
rappor
t im
m
édia
tem
ent.
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
114-051
12
S19-310FW Installation
11/7/08 Bradley Corporation • 215-163FW Rev. P; ECN 08-538
Armado de los componentes
15
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
114-052
P.O. Box 309, Menomonee Falls, WI 53051
R
TEST THIS UNIT EACH WEEK
Test-operate valve(s) each week and sign below.
Report any malfunctions immediately.
Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt
durch Unterschrift. Jegliche Störung sofort melden.
Date
Datum
Date
Signed
Unterschrift
Signe
Date
Date
Date Signed
Signed
Signed
DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.
ESSAI HEBDOMADAIRE
Test le fonctionnement des valves chaque semaine et
signe en bas. S'il y à quelque chose qui ne va pas fait
un rapport immédiatement.
28
29
13
1
2
3
4
2
5
6
2
7
8
9
3
11
12
17
19
17
20
24
19
25
26.1
26.2
26.3
26.4
26.5
23
21.1
21
22
18
10
10.1
10.31
10.2
10.4
10.3
10.5
26
27
27.1
27.2
27.3
14
14.1
Nota: Si el acoplamiento en T se usa como
entrada, utilizar el tapón artículo Nº 2.
NOTA: Los artículos del 10.1 al 10.5 vienen previamente montados como Artículo 10.
Los artículos del 26.1 al 26.5 vienen previamente montados como Artículo 26.
Los artículos del 27.1 al 27.3 vienen previamente montados como Artículo 27.
Entrada de
suministro
1-1/4" NPT
Salida de
drenado
1-1/4" NPT
Entrada de suministro
1-1/4" NPT
NOTA: Usar
cinta de teflon
solamente.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13

Bradley S19-310FW Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI