Protec 9100EN Installation and Maintenance Manual

Category
Fire protection
Type
Installation and Maintenance Manual
Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT.
Telephone: +44 (0) 1282 717171
Fax: +44 (0) 1282 717273
Web: www.protec.co.uk
Email: sales@protec.co.uk
9100EN
24V 1A POWER SUPPLY AND
BATTERY CHARGER
INSTALLATION, COMMISSIONING AND
MAINTENANCE MANUAL (N93-597-00)
N93-597-00 Issue 1 Page 2 of 17 © Protec Fire Detection PLC 2014
Document Revision Details
Issue
Modification Detail
Author
Date
1
Document Creation
RB
25/07/2014
2
Add ripple Voltage + Switching Frequency
RB
18/11/14
3
Add Document Reference Number
RB
21/11/14
N93-597-00 Issue 1 Page 3 of 17 © Protec Fire Detection PLC 2014
Table of Contents
1.0 INTRODUCTION .................................................................................................................................... 4
2.0 GENERAL INFORMATION - PLEASE READ ....................................................................................... 4
3.0 SYSTEM BLOCK DIAGRAM ................................................................................................................. 5
4.0 STANDBY BATTERY REQUIREMENTS .............................................................................................. 6
5.0 CABLING REQUIREMENTS ................................................................................................................. 6
6.0 INSTALLATION PROCEDURE ............................................................................................................. 7
6.1 UNPACKING ........................................................................................................................................... 7
6.2 REMOVAL OF THE DOOR ........................................................................................................................ 7
6.3 REMOVAL OF THE CONTROL PCB HOUSING ............................................................................................ 8
6.4 PREPARING THE MOUNTING POSITION AND CABLE ENTRIES .................................................................... 9
6.5 INSTALLING THE STANDBY BATTERIES .................................................................................................. 10
6.6 CONNECTING THE STANDBY BATTERIES................................................................................................ 11
6.7 REFITTING THE CONTROL PCB HOUSING ............................................................................................. 11
6.8 CONNECTING THE 24V OUTPUT WIRING ................................................................................................ 12
6.9 CONNECTING THE GLOBAL FAULT OUTPUT WIRING ................................................................................. 12
6.10 CONNECTING THE MAINS CABLING .................................................................................................... 13
6.11 RE-FITTING THE DOOR ..................................................................................................................... 14
6.12 SWITCHING THE MAINS POWER ON ................................................................................................... 15
7.0 MAINTENANCE ................................................................................................................................... 15
8.0 TECHNICAL SPECIFICATION ............................................................................................................ 16
N93-597-00 Issue 1 Page 4 of 17 © Protec Fire Detection PLC 2014
1.0 Introduction
This document describes the installation procedure required for the 9100EN charger and batteries. It also
incorporates the technical specification for the charger and associated batteries.
The 9100EN power supply is a self-contained supply designed to provide a 24V (nominal) output and charge
associated batteries simultaneously. The charger uses switch-mode technology to provide a lightweight,
efficient and reliable unit.
2.0 General Information - Please Read
This manual should be thoroughly read and understood before installation and commissioning is
undertaken.
The power supply and its associated connections must be installed, commissioned and maintained by a
suitably trained, skilled and competent person.
This equipment must be earthed and earth continuity must be preserved on broken segments of
screened cable used anywhere in the system installation.
This equipment is not guaranteed unless installed and commissioned in accordance with current national
standards.
This equipment is not suitable as part of an I.T type power distribution system as defined in
IEC 60364-3.
This equipment is suitable for fixed, internal installation only.
It is perfectly normal for sealed lead acid batteries to vent small amounts of hydrogen when being
charged. The enclosure is vented to dissipate any build up of hydrogen. The enclosure must not be not
sealed in any way.
Protec Fire Detection plc, Nelson, Lancashire, England BB9 6RT
BS EN 54-4:1997 + A1:2002 + A2:2006
Control / Indicating and Power Supply equipment for fire detection
and fire alarm systems for buildings
9100EN Power Supply and Battery Charger Unit
Power supply:
Performance of power supply: Pass
Durability of operational reliability, Temperature resistance: Pass
Durability of operational reliability, Vibration resistance: Pass
Durability of operational reliability, Electrical stability: Pass
Durability of operational reliability, Humidity resistance: Pass
14
N93-597-00 Issue 1 Page 5 of 17 © Protec Fire Detection PLC 2014
This equipment has been manufactured in conformance with the requirements of all
applicable EU council directives and regulations.
Electrical or electronic devices that are no longer serviceable must be collected separately and
sent for environmentally compatible recycling (in accordance with the European Waste
Electrical and Electronic Equipment Directive). To dispose of old electrical or electronic
devices, you should use the return and collection systems put in place in the country
concerned.
The policy of Protec Fire Detection plc is one of continuous improvement. As such we reserve the right to
make changes to product specifications at any time and without prior notice. Errors and omissions excepted.
3.0 System Block Diagram
Figure 3.0 shows a simplified block diagram of the system topology.
230V to 24V
Offline switching
converter
24V load
output circuit
EN54-4 battery
charger circuit
Supervisory
Microcontroller
Output protection
Standby
Battery
Mains / battery
switchover
EMC filtering
N93-597-00 Issue 1 Page 6 of 17 © Protec Fire Detection PLC 2014
4.0 Standby Battery Requirements
Only use batteries recommend by Protec (see technical specification section). The charger has been
specifically designed to maintain the charge voltage at an optimum level for these batteries over the entire
operating temperature range in order to maximise the life of the batteries.
The charger is designed to charge batteries up to a maximum capacity of 24Ah to 80% of their capacity in 24
hours and 100% in 72 hours.
5.0 Cabling Requirements
Wiring should be installed in accordance with BS7671 or local wiring regulations and also with
BS5839 Part 1. The ECA recommended cable separation for Electromagnetic Compatibility in Buildings
must be followed.
A readily accessible double pole disconnection device is required to be installed external to the equipment,
and should be used only for the fire alarm system. Wiring from the disconnection device to the charger
should be in 1.5mm² fire rated cable with circuit protection rated at 5 Amps.
Mains and field wiring must be segregated by keeping the mains wiring as short as is feasible and by routing
it through one of the knockouts in the enclosure in the vicinity of the mains terminal block. The mains
terminal cable restraint provided must be used to retain the cable.
Field wiring must be wired in suitably sized, screened, fire rated cable. The cable should use the knockouts
to the left side of the enclosure and should not be routed anywhere near the mains wiring.
Although no connections are to be made to the power supply until the commissioning stage it is important
that cables are left long enough to connect directly to the relevant terminals. To ensure that cable tails are
left with sufficient length all cable tails must be a minimum of 500mm.
N93-597-00 Issue 1 Page 7 of 17 © Protec Fire Detection PLC 2014
6.0 Installation Procedure
The 9100EN power supply may be surface or flush mounted (no extra bezel is required when flush
mounting).
The 9100EN circuit board is fully enclosed within a sealed control PCB housing. The control PCB housing
must never be opened. If the 9100EN requires repair it must be sent back to the Protec factory.
The batteries are fully accessible with the control PCB housing removed from the back box.
The 9100EN must be located internally in an area that is not subject to dampness, extremes of temperature
or physical abuse. The environmental limits are given in the technical specification section
6.1 Unpacking
Carefully open the cardboard carton (do not use a sharp object) and remove the packing fitments,
manuals and spares pack.
6.2 Removal of the Door
Stage 1: Remove the 9100EN from the packaging then, using a T15 Torx® type security tool,
unscrew but do not withdraw the fixing screw from the bottom of the panel housing front as shown in
Fig. 6.0.
Stage 2 and 3 : Slide the door upward from the bottom and pull away as shown in Fig. 6.0
Put all removed parts in a safe, dry place.
The 9100EN power supply is only suitable for install on permanent internal equipment.
Note: Further insulation tests MUST NOT be carried out after this point and the mains or standby supply
MUST NOT be connected.
Figure 6.0 Removing the 9100EN door
N93-597-00 Issue 1 Page 8 of 17 © Protec Fire Detection PLC 2014
6.3 Removal of the Control PCB Housing
Before handling the 9100EN power supply PCB housing it is important that any
operatives discharge themselves of any static charge that may have built up. This can
be done by momentarily touching a solid earth point (a non-painted part of a radiator,
for example).
The Power supply PCB housing is a sealed unit and must not be opened. Tampering
with this unit will invalidate the warranty. If the unit becomes faulty it must be
returned for repair.
Unscrew and remove the four mounting screws on the control PCB housing. Carefully lift away the
control PCB housing from the plastic enclosure. See Fig 6.1.
The 9100EN power supply PCB housing and all screws should be stored in the cardboard carton
away from the place of work where they will not get damaged.
Figure 6.1 Removal of the 9100EN Control PCB Housing
N93-597-00 Issue 1 Page 9 of 17 © Protec Fire Detection PLC 2014
6.4 Preparing the Mounting Position and Cable Entries
Use the dimensions shown on the interior rear face of the 9100EN back-box in conjunction with a
spirit level to mark out the fixing locations for the panel. Drill and plug the mounting holes just
marked.
Using a suitable tool carefully remove the rear panel knockouts at the required cable entry positions
and mount the enclosure in position whilst feeding the cables into the enclosure via suitable glands.
The mains cable entry position must be segregated from all other system cabling, a
reserved knock-out is provided specifically for this purpose.
A four way brass earth block is supplied with the 9100EN. Three locations are provided for this in the
9100EN back box. This allows the best location to be selected depending on wiring entry
requirements. Choose the location then clip the earth block into the back box, ensuring it is securely
fitted.
N93-597-00 Issue 1 Page 10 of 17 © Protec Fire Detection PLC 2014
6.5 Installing the Standby Batteries
The 9100EN power supply is designed to house two 12V 3.3Ah Valve Regulated Lead Acid (VRLA)
batteries. These fit into the back-box and must be secured with the two plastic tie-wraps provided
as shown in figure 6.2.
Only use batteries supplied or recommended by Protec. The internal charger has been specifically
designed to maintain the charge voltage at an optimum level for these batteries over the entire
operating temperature range in order to maximise the life of the batteries.
Figure 6.2 Installation of 9100EN standby batteries
(Shown with the lid and control PCB housing removed)
Tie-Wraps
must be used
to secure the
batteries
N93-597-00 Issue 1 Page 11 of 17 © Protec Fire Detection PLC 2014
6.6 Connecting the Standby Batteries
The two standby batteries must be connected in series with the battery link provided. Then,
observing correct polarity ( red lead to the positive of one battery and black lead to the negative of
the other battery ), carefully push the spade connectors of the 9100EN battery leads onto the
relevant battery terminals as illustrated in figure 6.3 .
Please note that at this point the 9100EN will not power up until the mains supply is connected.
Figure 6.3 Standby battery connections
6.7 Refitting the Control PCB Housing
Ensure that all cable earth connections are sleeved to insulate them and then securely connect them
to the brass earth terminals in the back-box.
Carefully route the battery leads from the rear of the control PCB housing down between the two
batteries.
Replace the Control PCB housing (a reversal of removal), ensuring it is pushed flush to the back box
and that the battery leads do not get trapped. Secure with the four screws removed previously,
taking care not to over tighten the screws.
Black Battery cable
N93-597-00 Issue 1 Page 12 of 17 © Protec Fire Detection PLC 2014
6.8 Connecting the 24V output wiring
When connecting wiring from the fire alarm equipment to any other equipment, care must be taken
to avoid subjecting the fire alarm equipment to any hazardous voltages. This is normally achieved
by only connecting SELV circuits to the equipment, or by using optical or galvanic isolation.
The 24V output from the power supply are fed from the terminals marked '+24’ and ‘0V' on the main PCB
(TB2).
6.9 Connecting the global fault output wiring
Volt free global fault contacts are provided to allow optional connection to ancillary systems.
These connections are found on the PCB and are marked N/O, N/C and COM (TB4).
Under 'no fault' conditions the COM and N/C contacts are short circuit, and change to open circuit when the
PSU has detected a fault (including being completely depowered).
N93-597-00 Issue 1 Page 13 of 17 © Protec Fire Detection PLC 2014
6.10 Connecting the Mains Cabling
Isolate the incoming mains supply by ensuring the fused double pole isolator is in the
‘OFF’ position.
Pay particular attention that the incoming mains cable is segregated from all other
cables within the 9100EN enclosure.
Ensure the incoming earth cable is firmly connected to the Main PCB (see figure
6.4), and that the earth cable from the Main PCB is securely connected to the brass
earth terminals within the back-box.
The mains wiring must now be restrained using the clamp provided to secure the
mains cables to the control PCB housing (see figure 6.5). The restraining clamp must
be supported at the rear when the two screws are being tightened.
Figure 6.4 Power Supply Terminal Details
Figure 6.5 Mains wiring connections
Mains wiring
clamp
Main PCB to
earth block cable
N93-597-00 Issue 1 Page 14 of 17 © Protec Fire Detection PLC 2014
6.11 Re-fitting the Door
Before replacing the door, it is recommended these checks are made:
Ensure the mains cable conductors are short and there is no bare conductor showing.
Ensure the incoming mains earth is secure in the PCB terminal block.
Ensure the mains cable is restrained by use of the cable clamp provided.
Ensure all 24 Volt output supply, Global Fault contacts wiring has been completed and will not foul
the door when it is refitted.
Replace the plastic door by raising the door and placing flush to the back-box of the panel (figure 6.6
step 1). Slide the door down and ensure it pushes fully home into the back box (figure 6.6 step 2).
Finally screw in the fixing screw, taking care not to over tighten it (figure 6.6 step 3)
Figure 6.6 Refitting the 9100EN door
N93-597-00 Issue 1 Page 15 of 17 © Protec Fire Detection PLC 2014
6.12 Switching the Mains Power On
Switch the fused isolator to the ‘ON’ position. The green ‘Power’ indicator will illuminate and,
assuming all other connections are correct, the 9100EN should show no fault on the display
7.0 Maintenance
No regular maintenance of the PSU is required. The internal microcontroller of the PSU performs regular
checks to ensure the battery and outputs are healthy.
However, the standby batteries should be checked periodically and, in any case, be replaced after 5 years
from the date of installation.
N93-597-00 Issue 1 Page 16 of 17 © Protec Fire Detection PLC 2014
8.0 Technical Specification
Rated Voltage
100V -240 AC RMS ( +10% -15%)
Rated Frequency
50 to 60 Hz
Rated Current
600mA rms
Maximum Inrush Current
20A at 240V from cold
Maximum Quiescent Load, Imax_a
350mA ( batteries charging )
Maximum Alarm Load, Imax_b
770mA ( batteries not charging )
Minimum Load, Imin, panel only
5 mA
Current taken from the standby
batteries during mains fail
Less than 150μA ( 9100EN is turned off )
Environmental
Designed to meet IP30
Ambient Temperature Limits
-5 to 50 Degrees C
Humidity Limits
90% ( no condensation or icing )
Current Consumption from Batteries
( low battery cut-off condition)
900uA
Mains Input Fuse (FS1)
1.6A time delay ( not user or engineer replaceable )
Battery Type
2 x 12V 3.3Ah Sealed Lead Acid ( connected in series )
Manufacture: Online, Model: OL3.3-12, Dimensions: 66x134x67mm (+/- 1mm)
Battery Fuse (FS2)
4A Quick Blow 20mm x 5mm glass
Output Voltage Range
24 29V dc with mains present , 17 29V dc on batteries
Output Ripple Voltage
400mV maximum ( peak to peak ) at full output load
Battery Charge Voltage
27.3V at 20 degrees C. Temperature compensated at
40mV / deg C. Protected by 1.6A self-resetting thermal fuse.
Battery Charge Current
250mA ( ± 25mA )
Battery Over Voltage Fault Level
28.5V dc ( nominal )
Battery Under Voltage Fault Level
22 V dc ( nominal )
Battery Low Voltage Cut-off Level
21.0V dc Battery Voltage ( outputs turn off )
Battery Monitoring
Charger dip, battery load and internal impedance
Maximum Battery Resistance ( Ri )
2Ω ( battery internal resistance + lead and connection resistances )
Fault Relay Contact
Maximum rating of 1A at 24V DC ( resistive load )
Switching Frequency
65 kHz ± 10%
N93-597-00 Issue 1 Page 17 of 17 © Protec Fire Detection PLC 2014
Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT.
Telephone: +44 (0) 1282 717171
Fax: +44 (0) 1282 717273
Web: www.protec.co.uk
Email: sales@protec.co.uk
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17

Protec 9100EN Installation and Maintenance Manual

Category
Fire protection
Type
Installation and Maintenance Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI