A1001

Axis A1001 User manual

  • Hello! I am an AI chatbot trained to assist you with the Axis A1001 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
USERMANUAL
AXISA1001NetworkDoorController&AXISEntryManager
AboutthisDocument
Thismanualisintendedforadministratorsandusersof
AXISA1001NetworkDoorControllerandisapplicableto
AXISEntryManagerandrmware1.15andlater.Itincludes
instructionsforusingandmanagingtheproductonyournetwork.
Previousexperienceofnetworkingwillbeofusewhenusingthis
product.SomeknowledgeofUNIXorLinux-basedsystemsmayalsobe
benecial,fordevelopingshellscriptsandapplications.Laterversions
ofthisdocumentwillbepostedtotheAxiswebsite,asrequired.See
alsotheproduct’sonlinehelp,availableviatheweb-basedinterface.
Inthismanual,AXISA1001NetworkDoorControllerisreferredtoas:
theAxisproduct,product,networkdoorcontroller,anddoorcontroller.
Liability
Everycarehasbeentakeninthepreparationofthisdocument.Please
informyourlocalAxisofceofanyinaccuraciesoromissions.Axis
CommunicationsABcannotbeheldresponsibleforanytechnicalor
typographicalerrorsandreservestherighttomakechangestothe
productandmanualswithoutpriornotice.AxisCommunicationsAB
makesnowarrantyofanykindwithregardtothematerialcontained
withinthisdocument,including,butnotlimitedto,theimplied
warrantiesofmerchantabilityandtnessforaparticularpurpose.Axis
CommunicationsABshallnotbeliablenorresponsibleforincidentalor
consequentialdamagesinconnectionwiththefurnishing,performance
oruseofthismaterial.Thisproductisonlytobeusedforitsintended
purpose.
IntellectualPropertyRights
AxisABhasintellectualpropertyrightsrelatingtotechnologyembodied
intheproductdescribedinthisdocument.Inparticular,andwithout
limitation,theseintellectualpropertyrightsmayincludeoneormore
ofthepatentslistedatwww.axis.com/patent.htmandoneormore
additionalpatentsorpendingpatentapplicationsintheUSandother
countries.
ThisproductcontainssourcecodecopyrightAppleComputer,
Inc.,underthetermsofApplePublicSourceLicense2.0(see
www.opensource.apple.com/apsl).Thesourcecodeisavailablefrom
https://developer.apple.com/bonjour/
EquipmentModications
Thisequipmentmustbeinstalledandusedinstrictaccordancewiththe
instructionsgivenintheuserdocumentation.Thisequipmentcontains
nouser-serviceablecomponents.Unauthorizedequipmentchangesor
modicationswillinvalidateallapplicableregulatorycertications
andapprovals.
TrademarkAcknowledgments
AXISCOMMUNICATIONS,AXIS,ETRAX,ARTPECandVAPIXare
registeredtrademarksortrademarkapplicationsofAxisABinvarious
jurisdictions.Allothercompanynamesandproductsaretrademarksor
registeredtrademarksoftheirrespectivecompanies.
RegulatoryInformation
Europe
ThisproductcomplieswiththeapplicableCEmarkingdirectives
andharmonizedstandards:
ElectromagneticCompatibility(EMC)Directive2004/108/EC.See
ElectromagneticCompatibility(EMC),onpage2.
LowVoltage(LVD)Directive2006/95/EC.SeeSafety,onpage2.
RestrictionsofHazardousSubstances(RoHS)Directive2011/65/EU.
SeeDisposalandRecycling,onpage2.
Acopyoftheoriginaldeclarationofconformitymaybeobtainedfrom
AxisCommunicationsAB.SeeContactInformation,onpage3.
ElectromagneticCompatibility(EMC)
Thisequipmenthasbeendesignedandtestedtofulllapplicable
standardsfor:
Radiofrequencyemissionwheninstalledaccordingtothe
instructionsandusedinitsintendedenvironment.
Immunitytoelectricalandelectromagneticphenomenawhen
installedaccordingtotheinstructionsandusedinitsintended
environment.
USA
Thisequipmenthasbeentestedusingashieldednetworkcable(STP)
andfoundtocomplywiththelimitsforaClassBdigitaldevice,
pursuanttopart15oftheFCCRules.Theselimitsaredesigned
toprovidereasonableprotectionagainstharmfulinterferenceina
residentialinstallation.Thisequipmentgenerates,usesandcanradiate
radiofrequencyenergyand,ifnotinstalledandusedinaccordance
withtheinstructions,maycauseharmfulinterferencetoradio
communications.However,thereisnoguaranteethatinterference
willnotoccurinaparticularinstallation.Ifthisequipmentdoes
causeharmfulinterferencetoradioortelevisionreception,which
canbedeterminedbyturningtheequipmentoffandon,theuseris
encouragedtotrytocorrecttheinterferencebyoneormoreofthe
followingmeasures:
Reorientorrelocatethereceivingantenna.
Increasetheseparationbetweentheequipmentandreceiver.
Connecttheequipmentintoanoutletonacircuitdifferentfrom
thattowhichthereceiverisconnected.
Consultthedealeroranexperiencedradio/TVtechnicianforhelp.
Theproductshallbeconnectedusingashieldednetworkcable(STP)
thatisproperlygrounded.
Canada
ThisClassBdigitalapparatuscomplieswithCanadianICES-003.The
productshallbeconnectedusingashieldednetworkcable(STP)thatis
properlygrounded.
CetappareilnumériquedelaclasseBestconfomeàlanorme
NMB-003duCanada.Leproduitdoitêtreconnectéàl'aided'uncâble
réseaublindé(STP)quiestcorrectementmisàlaterre.
Europe
ThisdigitalequipmentfulllstherequirementsforRFemission
accordingtotheClassBlimitofEN55022.Theproductshallbe
connectedusingashieldednetworkcable(STP)thatisproperly
grounded.
Thisproductfulllstherequirementsforimmunityaccording
toEN61000-6-1residential,commercialandlight-industrial
environments.
Thisproductfulllstherequirementsforimmunityaccordingto
EN61000-6-2industrialenvironments.
Thisproductfulllstherequirementsforimmunityaccordingto
EN55024ofceandcommercialenvironments
Thisproductfulllstherequirementsforimmunityaccordingto
EN50130-4residential,commercial,light-industrialandindustrial
environments.
Australia/NewZealand
ThisdigitalequipmentfulllstherequirementsforRFemission
accordingtotheClassBlimitofAS/NZSCISPR22.Theproductshall
beconnectedusingashieldednetworkcable(STP)thatisproperly
grounded.
Japan
B
で使てい
やテ使用
を引取扱
取りルド
(STP)を使してしてさい
切に地しださ
Safety
ThisproductcomplieswithIEC/EN/UL60950-1,SafetyofInformation
TechnologyEquipment.Ifitsconnectingcablesareroutedoutdoors,
theproductshallbegroundedeitherthroughashieldednetworkcable
(STP)orotherappropriatemethod.
Thepowersupplyusedwiththisproductshallfullltherequirements
forSafetyExtraLowVoltage(SELV)andLimitedPowerSource(LPS)
accordingtoIEC/EN/UL60950-1.
DisposalandRecycling
Whenthisproducthasreachedtheendofitsusefullife,disposeof
itaccordingtolocallawsandregulations.Forinformationabout
yournearestdesignatedcollectionpoint,contactyourlocalauthority
responsibleforwastedisposal.Inaccordancewithlocallegislation,
penaltiesmaybeapplicableforincorrectdisposalofthiswaste.
Europe
Thissymbolmeansthattheproductshallnotbedisposedof
togetherwithhouseholdorcommercialwaste.Directive2012/19/EU
onwasteelectricalandelectronicequipment(WEEE)isapplicablein
theEuropeanUnionmemberstates.Topreventpotentialharmto
humanhealthandtheenvironment,theproductmustbedisposed
ofinanapprovedandenvironmentallysaferecyclingprocess.For
informationaboutyournearestdesignatedcollectionpoint,contact
yourlocalauthorityresponsibleforwastedisposal.Businessesshould
contacttheproductsupplierforinformationabouthowtodispose
ofthisproductcorrectly.
ThisproductcomplieswiththerequirementsofDirective2011/65/EU
ontherestrictionoftheuseofcertainhazardoussubstancesin
electricalandelectronicequipment(RoHS).
China
Thisproductcomplieswiththerequirementsofthelegislative
actAdministrationontheControlofPollutionCausedbyElectronic
InformationProducts(ACPEIP).
ContactInformation
AxisCommunicationsAB
Emdalavägen14
22369Lund
Sweden
Tel:+46462721800
Fax:+4646136130
www.axis.com
SupportedReaders
Thislistofsupportedreadersissubjecttochangewithoutnotice.
ContactyourAxisresellerforinformationaboutsupportedreaders.
ThisproductiscompatiblewithUL-listedWiegandaccesscontrol
readers
ThisproductisapprovedforuseinsystemsthatrequireULcertication
whenconnectedtothefollowingcompatibleRS485accesscontrol
readers:
HIDiCLASS®RW100:6101CG40000,6101CGM0000,
6101CK40000,6101CK40002,6101CK40100,6101CK403C0,
6101CKM0000,6101CKM0002,6101CKM0203;RW300:
6111CG40000,6111CG400C0,6111CGM0000,6111CK40000,
6111CK4000Z,6111CKM0000;RW400:6121CG40000,
6121CGM0000,6121CK40000,6121CK40003,6121CK40007-G3.0,
6121CK4000D-G3.0,6121CKM0000;RK40:6122CKP00P0,
6122CKP05P0,6122CKP06P0;RWK400:6131CG4020000,
6131CK4000000,6131CK4000014,6131CK4000300,6131CK4020000,
6131CKM000000,6131CKM000214;RK40:6132BKP00Q709-G3.0,
6132CKP000009,6132CKP000011,6132CKP000700-G3.0,
6132CKP000709-G3.0,6132CKP001009,6132CKP001011,
6132CKP00P000,6132CKP00P009,6132CKP00P709-G3.0,
6132CKP00Q709-G3.0,6132CKP030014,6132CKP060514,
6132CKP06P009,6132CKP06P609,6132CKP070209;RW150:
6141CG40000,6141CGM0000,6141CK40000,6141CKM0000;
R15:6142CKP000Z,6142CKP00P0,6142CKP0100;RWKL550:
6171BK4000000,6171BK4000009,6171BK4000014,6171BK4000214,
6171BK4000500,6171BK4040Z14,6171BK4060000,6171BK4060209,
6171BK4060Z09,6171BK4061000,6171BKM000000,
6171BKM000200,6171BKM000300,6171BKM040400;RWKLB575:
6181BK4000000,6181BK4000009,6181BK4000014,6181BK4000022,
6181BK406C009;
HIDSmartid®:8031DSAP
HIDpivClass®R10-H:900LHRNAK00000,900LHRTAK00000,
900NHRNAK00000,900NHRTAK00000,900PHRNAK00000,
900PHRTAK00000,910LHRNAK00000,910LHRTAK00000,
910NHRNAK00000,910NHRTAK00000,910PHRNAK00000,
910PHRTAK00000,920LHRNAK00000,920LHRTAK00000,
920NHRNAK00000,920NHRTAK00000,920PHRNAK00000,
920PHRTAK00000,921LHRNAK00000,921LHRTAK00000,
921NHRNAK00000,921NHRTAK00000,921PHRNAK00000,
921PHRTAK00000;RPKCL40-P:923LPRNAK00000,923LPRTAK00000,
923NPRTAK00000,923PPRNAK00000,923PPRTAK00000
Aptiq
TM
:M11,MTK15,MTMSK15,MT15,MTMS15
Support
Shouldyourequireanytechnicalassistance,pleasecontactyourAxis
reseller.Ifyourquestionscannotbeansweredimmediately,your
resellerwillforwardyourqueriesthroughtheappropriatechannelsto
ensurearapidresponse.IfyouareconnectedtotheInternet,youcan:
downloaduserdocumentationandsoftwareupdates
ndanswerstoresolvedproblemsintheFAQdatabase.Search
byproduct,category,orphrase
reportproblemstoAxissupportstaffbyloggingintoyourprivate
supportarea
chatwithAxissupportstaff(selectedcountriesonly)
visitAxisSupportatwww.axis.com/techsup/
LearnMore!
VisitAxislearningcenterwww.axis.com/academy/forusefultrainings,
webinars,tutorialsandguides.
AXISA1001NetworkDoorController&AXISEntryManager
TableofContents
HardwareOverview..........................................5
LEDIndicators..................................................7
ConnectorsandButtons..........................................8
AccessingtheProduct.......................................10
AccessfromaBrowser...........................................10
AccessfromtheInternet..........................................10
SettheRootPassword...........................................10
SystemConguration........................................11
ConguretheHardware..........................................11
ManageNetworkDoorControllers..................................14
MaintenanceInstructions.........................................16
AccessManagement.........................................17
AccessSchedules................................................17
Groups........................................................19
Doors.........................................................20
Users.........................................................22
ExampleAccessScheduleCombinations.............................24
AlarmandEventConguration................................26
CongureEventandAlarmLogs....................................26
Events........................................................27
ReaderFeedback................................................30
SystemOptions.............................................32
Security.......................................................32
Date&Time....................................................34
Network.......................................................34
Ports&Devices.................................................39
Maintenance...................................................39
Support.......................................................40
Advanced......................................................41
ResettoFactoryDefaultSettings...................................41
Troubleshooting............................................42
CheckingtheFirmware...........................................42
UpgradingtheFirmware..........................................42
EmergencyRecoveryProcedure....................................42
Symptoms,PossibleCausesandRemedialActions.....................43
TechnicalSpecications......................................45
AXISA1001NetworkDoorController...............................45
AXISEntryManager.............................................47
Connectors....................................................48
ConnectionDiagrams............................................52
4
AXISA1001NetworkDoorController&AXISEntryManager
HardwareOverview
HardwareOverview
1
2
5
4
8
6
7
3
Frontandback:
1
Cover
2
Coverscrew
3
Coverremovalslot
4
Base
5
DINclipupper
6
Tamperingalarmswitchback
7
DINcliplower
8
Partnumber(P/N)&Serialnumber(S/N)
5
AXISA1001NetworkDoorController&AXISEntryManager
HardwareOverview
1
2
3
4
5
6
7
8
9
10
11
12
I/Ointerface:
1
Readerdataconnector(READERDATA1)
10
Readerdataconnector(READERDATA2)
3
ReaderI/Oconnector(READERI/O1)
8
ReaderI/Oconnector(READERI/O2)
4
Doorconnector(DOORIN1)
7
Doorconnector(DOORIN2)
6
Auxiliaryconnector(AUX)
5
Audioconnector(AUDIO)(notused)
Externalpowerinputs:
2
Powerconnector(DCIN)
12
Networkconnector(PoE)
Poweroutputs:
9
Powerlockconnector(LOCK)
11
Power&Relayconnector(PWR,RELAY)
6
AXISA1001NetworkDoorController&AXISEntryManager
HardwareOverview
1
2
3
4
5
6
7
8
9
1011
12
13
LEDindicators,buttonsandotherhardware:
1
PowerLEDindicator
2
StatusLEDindicator
3
NetworkLEDindicator
4
Reader2LEDindicator(notused)
5
Reader1LEDindicator(notused)
6
Tamperingalarmpinheaderfront(TF)
7
Tamperingalarmpinheaderback(TB)
8
LockLEDindicator
9
LockLEDindicator
10
Tamperingalarmsensorfront
11
SDcardslot(microSDHC)(notused)
12
Controlbutton
13
Partnumber(P/N)&Serialnumber(S/N)
LEDIndicators
LED
Color
Indication
Green
Steadyforconnectiontoa100MBit/snetwork.Flashesfornetworkactivity.
Amber
Steadyforconnectiontoa10MBit/snetwork.Flashesfornetworkactivity.
Network
UnlitNonetworkconnection.
GreenSteadygreenfornormaloperation.
Amber
Steadyduringstartupandwhenrestoringsettings.
Status
Red
Slowashforfailedupgrade.
Green
Normaloperation. Power
Amber
Flashesgreen/amberduringrmwareupgrade.
7
AXISA1001NetworkDoorController&AXISEntryManager
HardwareOverview
GreenSteadywhennotenergized.
Red
Steadywhenenergized.
Lock
UnlitFloating.
Note
TheStatusLEDcanbeconguredtoashwhileaneventisactive.
TheStatusLEDcanbeconguredtoashforidentifyingtheunit.GotoSetup>AdditionalControllerConguration>
SystemOptions>Maintenance.
ConnectorsandButtons
Fortechnicalspecications,seepage45.
I/OInterface
ReaderDataConnector
Two6-pinterminalblockssupportingRS485andWiegandprotocolsforcommunicationwiththereader.
ReaderI/OConnector
Two6-pinterminalblocksforreaderinputandoutput.Inadditiontothe0VDCreferencepointandpower(DCoutput),the
readerI/Oconnectorprovidestheinterfaceto:
DigitalinputForconnecting,forexample,readertamperingalarms.
DigitaloutputForconnecting,forexample,readerbeepersandreaderLEDs.
DoorConnector
Two4-pinterminalblocksforconnectingdoormonitoringdevicesandrequesttoexit(REX)devices
AuxiliaryConnector
4-pincongurableI/Oterminalblock.Usewithexternaldevices,incombinationwith,forexampletamperingalarms,eventtriggering
andalarmnotications.Inadditiontothe0VDCreferencepointandpower(DCoutput),theauxiliaryconnectorprovidesthe
interfaceto:
DigitalinputAnalarminputforconnectingdevicesthatcantogglebetweenanopenandclosedcircuit,forexamplePIR
sensorsorglassbreakdetectors.
DigitaloutputForconnectingexternaldevicessuchasburglaralarms,sirensorlights.Connecteddevicescanbe
activatedbytheVAPIX®applicationprogramminginterfaceorbyanactionrule.
ExternalPowerInputs
NOTICE NOTICE
NOTICE
Theproductshallbeconnectedusingashieldednetworkcable(STP).Allcablesconnectingtheproducttothenetworkshall
beintendedfortheirspecicuse.Makesurethatthenetworkdevicesareinstalledinaccordancewiththemanufacturer’s
instructions.Forinformationaboutregulatoryrequirements,seeElectromagneticCompatibility(EMC),onpage2.
PowerConnector
2-pinterminalblockforDCpowerinput.UseaSafetyExtraLowVoltage(SELV)compliantlimitedpowersource(LPS)witheither
aratedoutputpowerlimitedto100Woraratedoutputcurrentlimitedto5A.
NetworkConnector
RJ45Ethernetconnector.SupportsPoweroverEthernet(PoE).
PowerOutputs
PowerLockConnector
4-pinterminalblockforconnectingoneortwolocks.Thelockconnectorcanalsobeusedtopowerexternaldevices.
8
AXISA1001NetworkDoorController&AXISEntryManager
HardwareOverview
Power&RelayConnector
6-pinterminalblockforconnectingpowerandthedoorcontroller’srelaytoexternaldevicessuchaslocksandsensors.
ButtonsandOtherHardware
TamperingAlarmPinHeader
Two2-pinheadersfordisconnectingthefrontandbacktamperingalarms.
ControlButton
Thecontrolbuttonisusedfor:
Resettingtheproducttofactorydefaultsettings.Seepage41.
ConnectingtoanAXISVideoHostingSystemservice.Seepage35.Toconnect,pressandholdthebuttonforabout1
seconduntiltheStatusLEDashesgreen.
ConnectingtoAXISInternetDynamicDNSService.Seepage36.Toconnect,pressandholdthebuttonforabout3seconds.
9
AXISA1001NetworkDoorController&AXISEntryManager
AccessingtheProduct
AccessingtheProduct
ToinstalltheAxisproduct,refertotheInstallationGuidesuppliedwiththeproduct.
Theproductcanbeusedwithmostoperatingsystemsandbrowsers.TherecommendedbrowsersareInternetExplorerwithWindows,
SafariwithMacintoshandFirefoxwithotheroperatingsystems.SeeTechnicalSpecications,onpage45
AccessfromaBrowser
1.Startabrowser(InternetExplorer,Firefox,Safari).
2.EntertheIPaddressorhostnameoftheAxisproductinthebrowser’sLocation/Addresseld.Toaccesstheproductfroma
Macintoshcomputer(MacOSX),clickontheBonjourtabandselecttheproductfromthedrop-downlist.
IfyoudonotknowtheIPaddress,useAXISIPUtilitytolocatetheproductonthenetwork.Forinformationabouthowto
discoverandassignanIPaddress,seetheInstallationGuide,availableonaxis.com.Thisinformationisalsoavailablefrom
thesupportpagesonwww.axis.com/techsup
3.Enteryourusernameandpassword.Ifthisisthersttimetheproductisaccessed,therootpasswordmustrstbe
congured.Forinstructions,seeSettheRootPassword,onpage10.
4.AXISEntryManageropensinyourbrowser.ThestartpageiscalledtheOverviewpage.
AccessfromtheInternet
Onceconnected,theAxisproductisaccessibleonyourlocalnetwork(LAN).ToaccesstheproductfromtheInternetyoumust
congureyournetworkroutertoallowincomingdatatrafctotheproduct.Todothis,enabletheNAT-traversalfeature,whichwill
attempttoautomaticallyconguretheroutertoallowaccesstotheproduct.ThisisenabledfromSetup>AdditionalController
Conguration>SystemOptions>Network>TCP/IP>Advanced.
Formoreinformation,seeNATtraversal(portmapping)forIPv4,onpage37.SeealsoAXISInternetDynamicDNSService
atwww.axiscam.net
ForTechnicalnotesonthisandothertopics,visittheAxisSupportwebatwww.axis.com/techsup
SettheRootPassword
ToaccesstheAxisproduct,youmustsetthepasswordforthedefaultadministratoruserroot.ThisisdoneintheCongureRoot
Passworddialog,whichopenswhentheproductisaccessedforthersttime.
Topreventnetworkeavesdropping,therootpasswordcanbesetviaanencryptedHTTPSconnection,whichrequiresanHTTPS
certicate.HTTPS(HypertextTransferProtocoloverSSL)isaprotocolusedtoencrypttrafcbetweenwebbrowsersandservers.The
HTTPScerticateensuresencryptedexchangeofinformation.SeeHTTPS,onpage32.
Thedefaultadministratorusernamerootispermanentandcannotbedeleted.Ifthepasswordforrootislost,theproductmustbe
resettothefactorydefaultsettings.SeeResettoFactoryDefaultSettings,onpage41.
TosetthepasswordviaastandardHTTPconnection,enteritdirectlyinthedialog.
TosetthepasswordviaanencryptedHTTPSconnection,followthesesteps:
1.ClickUseHTTPS.
Atemporarycerticate(validforoneyear)iscreated,enablingencryptionofalltrafctoandfromtheproduct,andthe
passwordcannowbesetsecurely.
2.Enterapasswordandthenre-enterittoconrmthespelling.
3.ClickOK.Thepasswordhasnowbeencongured.
10
AXISA1001NetworkDoorController&AXISEntryManager
SystemConguration
SystemConguration
TheOverviewpageshowsinformationaboutthedoorcontroller’sname,MACaddress,IPaddress,andrmwareversion.Italso
enablesyoutoidentifythedoorcontrolleronthenetworkorinthesystem.
ThersttimeyouaccesstheAxisproduct,theOverviewpagewillpromptyoutocongurethehardware,tosetdateandtime,to
congurethenetworksettings,andtocongurethedoorcontrolleraspartofasystemorasastandaloneunit.
Tocongurethedoorcontroller:
1.Congurethedoorcontrollerandconnecteddevicessuchasreaders,locksandrequesttoexit(REX)devices.SeeCongure
theHardware,onpage11.
2.Setthedateandtime.SeeDate&Time,onpage34.
3.Congurethenetworksettings.SeeNetwork,onpage34.
4.Congurethedoorcontrollersystem.SeeManageNetworkDoorControllers,onpage14.
Forinformationabouthowtocongureandmanagethesystem'sdoors,schedules,usersandgroups,seeAccessManagement,on
page17.
ToreturntotheOverviewpagefromtheproduct’sotherwebpages,clickOverviewinthemenubar.
Note
Toaddorremovedoorcontrollers,toadd,remove,oreditusers,ortocongurethehardware,morethanhalfofthedoor
controllersinthesystemmustbeonline.Tocheckthedoorcontrollerstatus,gotoSetup>ManageNetworkDoor
ControllersinSystem.
ConguretheHardware
Beforeyoucanmanagethedoors,thehardwaremustbeconguredintheHardwareCongurationpages.
Doors,locksandotherdevicescanbeconnectedtotheAxisproductbeforecompletingthehardwareconguration.However,the
connectionofdeviceswillbeeasierifyoucompletethehardwarecongurationrst.Thisisbecausethehardwarepinchartwillbe
availablewhenthecongurationiscomplete.Thehardwarepinchartisaguideonhowtoconnectthepinsandcanbeusedas
areferencesheetformaintenance.
Tocongurethehardware:
1.GotoSetup>HardwareCongurationandclickStartnewhardwareconguration.Iftheproduct’shardwarehasnot
beencongured,HardwareCongurationwillbeavailableinthenoticationpanelintheOverviewpage.
2.Selectadooroptiondependingonthenumberofdoors,one(1)ortwo(2),thatwillbeconnectedtotheAxisproduct
3.EnteradescriptivenameforeachdoorandclickNext.Itisrecommendedtoprovidethedoorswithuniquedescriptive
namessothattheyeasilycanbeidentifedbyanyonewhowilladministratethesystem.
4.SelectthelockoptionsthatmatchtherequirementsandthetypeoflockconnectionsthatwillbeusedandclickNext.For
moreinformationaboutavailableoptions,seeLocks,onpage12.
5.SelectthetypesofreadersthatwillbeusedandclickFinish.Formoreinformationaboutavailableoptions,seeReaders,
onpage13.
Tocancelthehardwareconguration,clickCancel.Thiscanbedoneinanyofthehardwarecongurationpages.
Toviewthehardwarepinchart,gotoSetup>HardwarePinChart.
Toprintthehardwarepinchart,clickPrintHardwarePinChart.
Todeletethehardwareconguration,clickResethardwarecongurationforthiscontroller.
11
AXISA1001NetworkDoorController&AXISEntryManager
SystemConguration
Todeleteandrecongurethehardwareconguration,clickResetandstartnewhardwareconguration.
Locks
1.Ifadoormonitorwillbeused,selectDoormonitorandthenselecttheoptionthatmatcheshowthedoormonitor
circuitswillbeconnected.
2.Ifthedoorlockshalllockimmediatelyafterthedoorhasbeenopened,selectLockwhendooropens.
3.Specifythedoormonitortimeoptions,orifnodoormonitorwillbeused,thelocktimeoptions.
Thefollowingoptionsfordoormonitors,doormonitortimeandlocktimeareavailable:
Doormonitor
-Opencircuit=OpendoorThedoormonitorgivesthedooropensignalwhenthecircuitisopen.Selectifthe
doormonitorcircuitisnormallyclosed.
-Opencircuit=CloseddoorThedoormonitorgivesthedoorclosedsignalwhenthecircuitisopen.Selectif
thedoormonitorcircuitisnormallyopen.
LockwhendooropensSelectifthedoorshalllockimmediatelyafterthedoorhasbeenopened.Whenthedoor
closes,thedoorlockswithoutdelay.
AccesstimeSetthenumberofsecondsthedoorshallremainunlockedafteraccesshasbeengranted.Thedoorremains
unlockeduntilthedoorhasbeenopenedandwilllockwhenitclosesregardlessofwhethertheaccesstimehasexpiredor
not.Ifthedoorremainsunopened,itlockswhenthesetaccesstimehasbeenreached.
OpentoolongtimeSetthenumberofsecondsthedoorisallowedtostayopen.Ifthedoorisstillopenwhenthe
opentoolongtimehasbeenreached,thedooropentoolongalarmistriggered.Setupanactionruletocongurewhich
actiontheopentoolongeventshalltrigger.
Pre-alarmtimeApre-alarmisawarningsignalthatistriggeredbeforetheopentoolongtimehasbeenreached.It
tellstheadministratorand,dependingonhowtheactionrulehasbeensetup,itcanalsowarntheuser(theperson
enteringthedoor)thatthedoorneedstobeclosedortherealalarm,thedooropentoolongalarm,willgooff.Setthe
numberofsecondsbeforethedooropentoolongalarmistriggeredthesystemshallgivethepre-alarmwarningsignal.
Todisablethepre-alarm,setthepre-alarmtimeto0.
DoorunlockedtimeDeselectDoormonitortomakethisoptionavailable.Setthenumberofsecondsthedoorshall
remainunlockedafteraccesshasbeengranted.Thedoorremainsunlockeduntilthedoorhasbeenopenedandwill
lockwhenitclosesregardlessofwhetherthedoorunlockedtimehasexpiredornot.Ifthedoorremainsunopened,it
lockswhenthesetdoorunlocktimehasbeenreached.
Pre-locksignaltimeDeselectDoormonitortomakethisoptionavailable.Apre-locksignalisawarningsignalthatis
triggeredbeforethedoorlocks.Ittellstheadministratorand,dependingonhowtheactionrulehasbeensetup,itcanalso
warntheuser(thepersonenteringthedoor)thatthedoorwilllocksoon.Setthenumberofsecondsbeforethedoor
locksthesystemshallgivethepre-lockwarningsignal.Thepre-locksignaltimemustbeshorterthanthedoorunlocked
time.Todisablethepre-lockwarningsignal,setthepre-locksignaltimeto0.
Forinformationabouthowtosetupanactionrule,seeSettingUpanActionRule,onpage29.
Thefollowingoptionsforlocksareavailable:
12V
-Locked=GND(-)Selectforlocksthatremainlockedduringpoweroutages(failclose/secure).
-Locked=12VSelectforlocksthatunlockduringpoweroutages(failopen/safe).
RelayCanonlybeusedononelockperdoorcontroller.Iftwodoorsareconnectedtothedoorcontroller,arelaycan
onlybeusedonthelockoftheseconddoor.
-Locked=RelayopenSelectforlocksthatremainlockedwhentherelayisopen(failclose/secure).
12
AXISA1001NetworkDoorController&AXISEntryManager
SystemConguration
-Locked=RelayclosedSelectforlocksthatunlockduringpoweroutages(failopen/safe).
NoneSelectifonlyonelockwillbeused.
Note
Mostlock,doormonitor,andreaderoptionscanbechangedwithoutresettingandstartinganewhardwareconguration.
GotoSetup>HardwareReconguration.
Motorizedlocksmustbeconguredassecondarylocks.
Readers
1.Ifareaderwillbeused,selectReaderandthenselecttheoptionsthatmatchthereader’scommunicationprotocol.
2.Ifarequesttoexit(REX)devicesuchasabutton,sensor,orpushbarwillbeused,selectREXandthenselecttheoption
thatmatcheshowtheREXdevice’scircuitswillbeconnected.
Ifthedoorshallremainlockeduntiltheusermanuallyunlocksandopensthedoor,selectRequiremanualunlock.
3.IfconnectingmorethanonereaderorREXdevicetothedoorcontroller,dotheprevioustwostepsagainuntileach
readerorREXdevicehasthecorrectsettings.
Thefollowingoptionsforreadersareavailable:
WiegandSelectforreadersthatuseWiegandprotocols.
RS485halfduplexSelectforRS485readerswithhalfduplexsupportandthenselecttheRS485protocolthatis
supportedbythereader.Seethemanufacturer’sinformationaboutwhichprotocolthereadersupports.
RS485fullduplexSelectforRS485readerswithfullduplexsupportandthenselecttheRS485protocolthatissupported
bythereader.Seethemanufacturer’sinformationaboutwhichprotocolthereadersupports.
ThefollowingoptionsforREXdevicesareavailable:
ActivelowSelectifactivatingtheREXdeviceclosesthecircuit.
ActivehighSelectifactivatingtheREXdeviceopensthecircuit.
RequiremanualunlockSelectifthedoorshallremainlockeduntiltheusermanuallyunlocksandopensthedoor.The
doorforcedopenalarmwillnotbetriggeredaslongastheuseropensthedoorwithintheaccesstime.Deselectifthedoor
shallunlockautomaticallywhentheuseractivatestheREXdevice.
Important
Ifthedoorcontrollerhasonlybeenconguredwithonedoorbeforeitisupgradedtormware1.15orlaterfromrmware
1.10,Requiremanualunlockwillbenon-selectableatrst.TomakeRequiremanualunlockselectable,gotoSetup>
HardwareCongurationandclickResetandstartanewhardwareconguration.Thensetuptherulesforthedoors
connectedtothedoorcontrollerandaddthemtogroups,seeDoors.
Note
Mostlock,doormonitor,andreaderoptionscanbechangedwithoutresettingandstartinganewhardwareconguration.
GotoSetup>HardwareReconguration.
VerifytheHardwareConnections
Whenthehardwareinstallationandcongurationiscomplete,andanytimeduringthedoorcontroller’slifetime,youcanverifythe
functionoftheconnecteddoormonitors,locksandreaders.
Toverifythecongurationandaccessthevericationcontrols,gotoSetup>HardwareConnectionVerication.
VericationControls
Doorstate–Verifythecurrentstateofthedoormonitor,dooralarmsandlocks.ClickGetcurrentstate.
13
AXISA1001NetworkDoorController&AXISEntryManager
SystemConguration
LockManuallytriggerthelock.Bothprimarylocksandsecondarylocksifthereareanywillbeaffected.ClickLockor
Unlock.
Lock(access)Manuallytriggerthelocktograntaccess.Onlyprimarylockswillbeaffected.ClickAccess.
Reader:FeedbackVerifythereaderfeedback,forexamplesoundsandLEDsignals,fordifferentcommands.Selectthe
commandandclickTest.Whichtypesoffeedbackthatareavailabledependsonthereader.Formoreinformation,see
ReaderFeedback.Seealsothemanufacturer’sinstructions.
Reader:TamperingGetinformationaboutthelasttamperingattempt.Thersttamperingattemptwillberegistered
whenthereaderisinstalled.ClickGetlasttampering.
Reader:CardswipeGetinformationaboutthelastswipedcardorothertypeofusertokenacceptedbythereader.
ClickGetlastcredential.
REXGetinformationaboutthelasttimetherequesttoexit(REX)devicewaspressed.ClickGetlastREX.
ManageNetworkDoorControllers
TheManageNetworkDoorControllersinSystempageshowsinformationaboutthedoorcontroller,itssystemstatusandwhich
otherdoorcontrollersarepartofthesystem.Italsoenablestheadministratortochangethesystemsetupbyaddingandremoving
doorcontrollers.
Tomanagedoorcontrollers,gotoSetup>ManageNetworkDoorControllersinSystem.
Systemstatusforthiscontroller-Showsthedoorcontroller'ssystemstatusandenablesswitchingbetweensystemandstandalone
modes.Formoreinformation,seeSystemStatus,onpage14.
Networkdoorcontrollersinsystem-Showsalistwhichcontainsthefollowinginformationaboutthedoorcontrollersinthesystem:
NameTheuser-denednameofthedoorcontroller.Iftheadministratorhasnotsetanamewhenconguring
thehardware,thedefaultnamewillbeshown.
IPaddress
MACaddress
StatusThedoorcontrollerfromwhichyouaccessthesystemwillshowstatusThiscontroller.Theotherdoor
controllersinthesystemwillshowstatusOnline.
Forinformationabouthowto
changethedoorcontrollersystemstatus,seeSystemStatus,onpage14.
addadoorcontrollertoasystem,seeAddDoorControllerstotheSystem,onpage15.
removeadoorcontrollerfromasystem,seeRemoveDoorControllersfromtheSystem,onpage15.
SystemStatus
Ifthedoorcontrollercanbepartofasystemofdoorcontrollersdependsonitssystemstatus.Thedoorcontroller’ssystemstatus
isdisplayedunderSystemstatusforthiscontroller.Availablesystemstatusesare:
Thiscontrollerisnotpartofasystemandnotinstandalonemode-Thedoorcontrollerhasnotbeenconguredaspartofa
systemanditisnotinstandalonemode.Thismeansthatthedoorcontrollerisopenandcanbeaddedtoasystembyanyotherdoor
controllerwithinthesamenetwork.Toprotectthedoorcontrollerfrombeingaddedtoasystem,activatethestandalonemode.To
setthedoorcontrollertostandalonemode,clickActivatestandalonemode.
Thiscontrollerissettostandalonemode-Thedoorcontrollerisnotpartofasystem.Itcannotbeaddedtoasystembyotherdoor
controllersinthenetworkoraddotherdoorcontrollersitself.Standalonemodeistypicallyusedinasmallsetupwithoneortwo
doors.Ifyouareplanningonaddingthedoorcontrollertoasystem,clickDeactivatestandalonemode.
Thiscontrollerispartofasystem-Thedoorcontrollerispartofadistributedsystemsharingusers,groups,doorsandschedules.
14
AXISA1001NetworkDoorController&AXISEntryManager
SystemConguration
AddDoorControllerstotheSystem
Important
Whenpairingdoorcontrollers,allaccessmanagementsettingsontheaddeddoorcontrollerwillbedeletedandoverwritten
bythesystem’saccessmanagementsettings.
Toaddadoorcontrollertothesystemfromthelistofdoorcontrollers:
1.GotoSetup>ManageNetworkDoorControllersinSystem.
2.ClickAddcontrollerstosystemfromlist.
3.Selectthedoorcontrollerthatyouwishtoadd.
4.ClickAdd.
5.Toaddmoredoorcontrollers,repeatthestepsabove.
ToaddadoorcontrollertothesystembyitsknownIPaddressorMACaddress:
1.GotoManageDevices.
2.ClickAddcontrollertosystembyIPorMACaddress.
3.EntertheIPaddressorMACaddress.
4.ClickAdd.
5.Toaddmoredoorcontrollers,repeatthestepsabove.
Whenthepairingiscompleted,allusers,doors,schedules,andgroupsaresharedbyalldoorcontrollersinthesystem.
Toupdatethelist,clickRefreshlistofcontrollers.
RemoveDoorControllersfromtheSystem
Important
Beforeremovingadoorcontrollerfromthesystem,resetitshardwareconguration.Ifyouskipthisstep,alldoorsrelatedto
theremoveddoorcontrollerwillremaininthesystemandcannotbedeleted.
Whenremovingadoorcontrollerfromatwo-controllersystem,bothdoorcontrollersautomaticallyswitchtostandalone
mode.
Toremoveadoorcontrollerfromthesystem:
1.AccessthesystemthroughthedoorcontrollerthatyouwanttoremoveandgotoSetup>HardwareConguration.
2.ClickResethardwareconguration.
3.Afterthehardwarecongurationhasbeenreset,gotoSetup>ManageNetworkDoorControllersinSystem.
4.IntheNetworkdoorcontrollersinsystemlist,identifythedoorcontrollerthatyouwanttoremoveandclickRemove
fromsystem.
5.Adialogopensremindingyoutoresetthedoorcontroller’shardwareconguration.ClickRemovecontrollertoconrm.
6.Adialogopenspromptingyoutoconrmthatyouwanttoremovethedoorcontroller.ClickOKtoconrm.Theremoved
doorcontrollerisnowinstandalonemode.
Note
Whenadoorcontrollerisremovedfromthesystem,allitsaccessmanagementsettingsaredeleted.
Onlydoorcontrollersthatareonlinecanberemoved.
15
AXISA1001NetworkDoorController&AXISEntryManager
SystemConguration
MaintenanceInstructions
Tokeeptheaccesscontrolsystemrunningsmoothly,Axisrecommendsregularmaintenanceoftheaccesscontrolsystem,including
doorcontrollersandconnecteddevices.
Domaintenanceatleastonceayear.Thesuggestedmaintenanceprocedureincludes,butisnotlimitedto,thefollowingsteps:
Makesurealltheconnectionsbetweenthedoorcontrollerandtheexternaldevicesaresecure.
Verifyallthehardwareconnections.SeeVericationControls,onpage13.
Verifythatthesystem,includingtheconnectedexternaldevices,functionscorrectly.
-Swipeacardandtestthereaders,doors,andlocks.
-IfthesystemincludesREXdevices,sensorsorotherdevices,testthemaswell.
-Ifactivated,testthetamperingalarms.
Iftheresultsfromanyofthestepsaboveindicatefaultsorunexpectedbehavior:
-Testthesignalsofthewiresusingappropriateequipmentandcheckifthewiresorcablesaredamaged
inanyway.
-Replacealldamagedorfaultycablesandwires.
-Oncethecablesandwireshavebeenreplaced,verifyallthehardwareconnectionsagain.SeeVerication
Controls,onpage13.
Makesureallaccessschedules,doors,groups,andusersareuptodate.
Ifthedoorcontrollerisnotbehavingasexpected,seeTroubleshooting,onpage42andMaintenance,onpage39for
moreinformation.
16
AXISA1001NetworkDoorController&AXISEntryManager
AccessManagement
AccessManagement
TheAccessManagementpageallowsyoutocongureandmanagethesystem’susers,groups,doors,andschedules.Toopenthe
AccessManagementpage,clickAccessManagement.
Theaccessmanagementstructureisexible,allowingyoutodevelopaworkowthatsuitsyourneeds.Thefollowingisaworkow
example:
Jane Doe
10010
1
2
3
4
5
6
7
8
1.Createaccessschedules.Seepage17.
2.Creategroups.Seepage19.
3.Applyaccessschedulestogroups.
4.Addidenticationtypestodoors.Seepage20andpage21.
5.Applyaccessschedulestoeachidenticationtype.
6.Applydoorstogroups.
7.Createusers.Seepage22.
8.Adduserstogroups.
Forappliedexamplesofthisworkow,seeExampleAccessScheduleCombinations,onpage24.
Toadduserstogroupsandapplyaccessschedulesanddoors,dragtheitemstotheirrespectivedestinationintheGroupsand
Doorslists.
Note
Messagesthatrequireactionareshowninredtext.
AccessSchedules
Accessschedulesareusedtodenegeneralrulesforwhendoorscanandcannotbeaccessed.Theyarealsousedtodenerulesfor
whengroupscanandcannotaccessthedoorsinthesystem.Formoreinformation,seeAccessScheduleTypes,onpage18.
Tocreateanewaccessschedule:
1.IntheAccessSchedulestab,clickAddnewschedule.
2.IntheAddaccessscheduledialog,entertheschedulename.
17
AXISA1001NetworkDoorController&AXISEntryManager
AccessManagement
3.Tocreatearegularaccessschedule,selectAdditionSchedule,ortocreateasubtractionschedule,selectSubtraction
Schedule.
4.ClickSave.
ToexpandanitemintheAccessScheduleslist,click
.Additionschedulesareshowningreentextandsubtractionschedules
areshownindarkredtext.
Toviewanaccessschedule’scalendar,click.
Toeditanaccessschedule’snameorascheduleitem,clickandmakethechanges.ThenclickSave.
Todeleteanaccessschedule,click.
Note
Thedoorcontrollerhasafewpredenedcommonlyusedaccessschedulesthatcanbeusedasexamplesormodiedas
required.However,thepredenedaccessscheduleAlwayscannotbemodiedordeleted.
AccessScheduleTypes
Therearetwotypesofaccessschedules:
Additionschedule-Regularaccessschedulesthatdenewhendoorscanbeaccessed.Typicaladditionschedulesareofcehours,
businesshours,afterhours,ornighttimehours.
Subtractionschedule-Exceptionstoregularaccessschedules.Theyaregenerallyusedtorestrictaccessduringaspecictime
periodthatoccurswithinthetimeperiodofaregularschedule(additionschedule).Forexample,subtractionschedulescanbeused
todenyusersaccesstothebuildingduringpublicholidaysthatoccuronweekdays.
Bothtypesofaccessschedulescanbeusedattwolevels:
Identicationtypeschedules-Determinewhenandhowreadersgrantusersaccesstoadoor.Eachidenticationtypemustbe
connectedtoanaccessschedulethattellsthesystemwhentograntusersaccesswiththatparticularidenticationtype.Multiple
additionschedulesandsubtractionschedulescanbeaddedtoeachidenticationtype.Forinformationaboutidenticationtypes,
seepage21.
Groupschedules-Determinewhen,butnothow,membersofagrouparegrantedaccesstoadoor.Eachgroupmustbeconnected
tooneormoreaccessschedulesthattellthesystemwhentograntitsmembersaccess.Multipleadditionschedulesandsubtraction
schedulescanbeaddedtoeachgroup.Forinformationaboutgroups,seepage19.
Groupschedulescanrestrictentryaccessrightsbutnotextendentryorexitaccessrightsbeyondwhattheidenticationtype
schedulesallow.Inotherwords,ifanidenticationtypeschedulerestrictsentryorexitaccessatcertaintimes,agroupschedule
cannotoverridethatidenticationtypeschedule.However,ifagroupscheduleismorerestrictiveaboutaccessthantheidentication
typeschedule,thegroupscheduleoverridestheidenticationtypeschedule.
Identicationtypeschedulesandgroupschedulescanbecombinedinseveralwaystoachievedifferentresults.Forexampleaccess
schedulecombinations,seepage24.
ScheduleItems
Bothadditionschedulesandsubtractionschedulescanbeone-time(single)eventsorrecurringevents.
Toaddascheduleitemtoanaccessschedule:
1.ExpandtheaccessscheduleintheAccessScheduleslist.
2.ClickAddscheduleitem.
3.Enterthenameofthescheduleditem.
4.SelectOnetimeorRecurrence.
18
AXISA1001NetworkDoorController&AXISEntryManager
AccessManagement
5.Setthedurationinthetimeelds.SeeTime.
6.Forrecurringscheduleevents,selecttheRecurrencepatternandRangeofrecurrenceparameters.SeeRecurrence
PatternandRangeofRecurrence.
7.ClickSave.
Time
Theavailabletimeoptionsare:
AlldaySelectforeventsthatlastforall24hoursoftheday.ThenenterthedesiredStartdate.
StartClickthetimeeldandselectthedesiredtime.TheallowedtimeformatisHH:MM.Ifrequired,clickthedateeld
andselectthedesiredmonth,day,andyear.Youcanalsotypethedatedirectlyintheeld(MM/DD/YYYY).
EndClickthetimeeldandselectthedesiredtime.TheallowedtimeformatisHH:MM.Ifrequired,clickthedateeld
andselectthedesiredmonth,day,andyear.Youcanalsotypethedatedirectlyintheeld(MM/DD/YYYY).
RecurrencePattern
Theavailablerecurrencepatternsare:
YearlySelecttorepeateveryyear.
WeeklySelecttorepeateveryweek.
RecurseveryweekonMonday,Tuesday,Wednesday,Thursday,Friday,Saturday,andSundaySelectwhichdaystorepeat.
RangeofRecurrence
Theavailablerangesofrecurrenceare:
FirstoccurrenceClickthedateeldandselectthedesiredmonth,day,andyear.Youcanalsotypethedatedirectlyin
theeld(MM/DD/YYYY).
NoenddateSelecttorepeattheoccurrenceindenitely.
EndbyClickthedateeldandselectthedesiredmonth,day,andyear.Youcanalsotypethedatedirectlyinthe
eld(MM/DD/YYYY).
Groups
Groupsallowyoutomanageusersandtheiraccessrightscollectivelyandefciently.Agroupconsistsofcredentialsthattellthe
systemwhichusersthegroupconsistsofandwhenandhowthegroupmembersaregrantedaccesstothedoors.
Eachusermustbelongtooneormoregroups.Toaddausertoagroup,draganddroptheusertothedesiredgroupintheGroups
list.Formoreinformationaboutusers,seepage22.
Tocreateanewgroup:
1.IntheGroupstab,clickAddnewgroup.
2.IntheAddGroupdialog,enterthegroup’scredentials.
3.ClickSave.
ToexpandanitemintheGroupslistandviewitsmembers,dooraccessrightsandschedules,click.
Toeditagroup’snameorvaliditydate,click
andmakethechanges.ThenclickSave.
19
AXISA1001NetworkDoorController&AXISEntryManager
AccessManagement
Toverifywhenandhowagroupcanaccesscertaindoors,click.
Todeleteagrouporgroupmembers,doorsorschedulesfromagroup,click.
Thefollowingcredentialsareavailable:
Name(required)
ValidfromandValidtoEnterthedatesbetweenwhichthegroup’scredentialsshallbevalid.Clickthedateeldand
selectthedesiredmonth,day,andyear.Youcanalsotypethedatedirectlyintheeld(MM/DD/YYYY).
Note
Tobeabletosavetheprole,youmustenterthegroup’sName.
Doors
ThegeneralrulesforeachdooraremanagedintheDoorstab.Therulesincludeaddingidenticationtypesthatdeterminehowusers
willbegrantedaccesstothedoorandaccessschedulesthatdeterminewheneachidenticationtypeisvalid.Formoreinformation,
seeIdenticationTypes,onpage21andAccessSchedules,onpage17.
Beforeyoucanmanageadoor,youmustaddittotheaccesscontrolsystembycompletingthehardwareconguration,see
ConguretheHardware,onpage11.
Tomanageadoor:
1.GotoAccessManagementandselecttheDoorstab.
2.IntheDoorslist,click
nexttothedooryouwanttoedit.
3.Dragthedoortoatleastonegroup.IftheGroupslistisempty,createanewgroup.Seepage19.
4.ClickAddidenticationtypeandselectwhichcredentialsusersneedtopresenttothereadertobegrantedaccess
tothedoor.
Addatleastoneidenticationtypetoeachdoor.
5.Toaddmultipleidenticationtypes,repeatthepreviousstep.
IfbothidenticationtypesCardnumberonlyandPINonlyareadded,userscanchoosetoeitherswipetheircardorenter
theirpintoaccessthedoor.Butif,instead,onlytheidenticationtypeCardnumberandPINisadded,usersmustboth
swipetheircardandentertheirPINtoaccessthedoor.
6.Todenewhenthecredentialsarevalid,dragascheduletoeachidenticationtype.
Tomanuallyunlockdoors,lockdoors,orgranttemporaryaccess,clickoneofthemanualdooractionsasrequired.SeeManualDoor
Actions,onpage21.
ToexpandanitemintheDoorslist,click
.
Toeditadoororreadername,click
andmakethechanges.ThenclickSave.
Toverifythereader,identicationtype,andaccessschedulecombinations,click.
Toverifythefunctionofthelocksconnectedtothedoors,clickthevericationcontrols.SeeVericationControls,onpage13.
Todeleteidenticationtypesoraccessschedules,click.
20
/