Sanyo SAP–CM1821A Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual

This manual is also suitable for

TECHNICAL & SERVICE MANUAL
SAPK91A (2) + SAPCM1821A
FILE NO.
REFERENCE NO. SM700428
Indoor Unit
Outdoor Unit
MULTI-SPLIT SYSTEM AIR CONDITIONER
SAP–CM1821A
SAP–K91A (2)
Indoor Model No Product Code No.
SAPK91A–S 1 852 063 35
Outdoor Model No. Product Code No.
SAPCM1821A–S 1 852 068 10
Destination : Australia
i
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operat-
ing standards. As the installer or service person, it is an
important part of your job to install or service the system
so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as
shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tub-
ing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause
accidental
injury or death.
Ground the unit
following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your
knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can cut
your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the outdoor unit. This pre-
vents water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-
free connection.
Check carefully for leaks before starting the test run.
When Servicing
Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have been
left inside the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously
toxic gas.
Confirm upon completing installation that no refriger-
ant gas is leaking. If escaped gas comes in contact
with a stove, gas water heater, electric room heater or
other heat source, it can produce dangerously toxic
gas.
WARNING
WARNING
CAUTION
CAUTION
Table of Contents
Page
Unit Combination.................................................................................................................................... iii
1. OPERATING RANGE .............................................................................................................................. 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 3
2-3. Other Component Specifications.................................................................................................... 5
3. DIMENSIONAL DATA.............................................................................................................................. 6
4. COOLING CAPACITY ............................................................................................................................. 8
5. AIR THROW DISTANCE CHART ........................................................................................................... 10
6. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 11
7. ELECTRICAL DATA
7-1. Electrical Characteristics................................................................................................................ 12
7-2. Electric Wiring Diagrams................................................................................................................ 13
8. INSTALLATION INSTRUCTIONS
8-1. Installation Site Selection ............................................................................................................... 15
8-2. Remote Control Unit Installation Position....................................................................................... 17
8-3. Recommended Wire Length and Diameter ................................................................................... 18
9. FUNCTION
9-1. Room Temperature Control ........................................................................................................... 19
9-2. Dry Operation ................................................................................................................................ 20
9-3. Freeze Prevention ......................................................................................................................... 20
10. TROUBLESHOOTING
10-1. Check before and after troubleshooting ........................................................................................ 21
10-2. Air conditioner does not operate .................................................................................................... 22
10-3. Some part of air conditioner does not operate .............................................................................. 27
10-4. Air conditioner operates, but abnormalities are observed ............................................................. 29
10-5. If a sensor is defective ................................................................................................................... 30
11. ARRANGEMENT OF ELECTRICAL COMPONENT .............................................................................. 31
12. CHECKING ELECTRICAL COMPONENTS
12-1. Measurement of Insulation Resistance .......................................................................................... 32
12-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 33
12-3. Checking Motor Capacitor ............................................................................................................. 33
INSTRUCTION MANUAL ........................................................................................................ 34
APPENDIX
ii
iii
Unit Combination
Combine indoor and outdoor units only as listed below.
Indoor Unit
Outdoor Unit
A
B
Fig.1
Refer toOutdoor Unit
Symbol of
Indoor Unit
Indoor Unit
SAPCM1821A
K91A A
Fig.1
K91A B
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
No. of indoor units. 1-unit 2-units
Power Source 240V Single phase 50 Hz
Cooling
Capacity kW 2.50 5.00
BTU/h 8,500 17,100
Air circulation (High) m
3
/h 430 430
2
Moisture removal (High) Liters/h 0.85 0.85
2
Voltage rating V 240
Available voltage range V 216 to 264
Running amperes A 5.0 9.3
Power input W 1,110 2,120
Power factor % 93 95
C.O.P. W/W 2.30 2.41
Compressor locked rotor amperes A 24 48
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer 1-hour OFF / 12-hour ON or OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, AntiMold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 1,260 (630
2)
Refrigerant control Capillary tube
Operation sound Indoor – Hi / Me / Lo dB-A 39 / 37 / 33
Outdoor – Hi dB-A 53
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4)
diameter
Wide tube mm (in.) 9.52 (3/8)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 250 630
Width mm 790 810
Depth mm 174 275
Package dimensions Height mm 242 704
Width mm 850 953
Depth mm 312 369
Weight Net kg 7.0 48.0
Shipping kg 10.0 52.5
Shipping volume m
3
0.06 0.25
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit SAPK91A
Outdoor Unit SAPCM1821A
2
2-2. Major Component Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POWK91G
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS7S3E
Type Crossflow
Number ... Dia. and length mm 1 ... ø95 / L578
Fan motor model ... Number UF4Q21H5P–S ... 1
No. of poles ... rpm (240 V, High) 4 ... 1,290
Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT – BRN : 449.4
WHT – VLT : 126.4
VLT – ORG : 92.4
ORG – YEL : 136.1
YEL – PNK : 92.5
Safety
Type Internal fuse
devices Operating temp. Open °C 145 ± 2
Close
Run capacitor µF 1.0
VAC 440
Type Stepping motor
Model MP24S2–12V
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) A pair of each terminal : 380 ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.4
Face area m
2
0.110
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
3
Indoor Unit SAPK91A
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Type Rotary (Hermetic)
Compressor model ... Number C1R80H5K ... 2 / 80603345–S ... 2
Nominal output W 800
Compressor oil ... Amount cc SUNISO 4GSDT ... 320
2
Coil resistance (Ambient temp. 25°C) C – R : 3.65
C – S : 5.38
Type External protector (OLR 1, 3) External protector (OLR 2, 4)
Safety
Overload relay ... Number MRA99109-9201 ... 2 CS-7C115 ... 2
devices Operating temp. Open °C 150 ± 5 115 ± 3
Close °C 69 ± 11 95 ± 5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 16A
Run capacitor ... Number µF 30.0 ... 2
VAC 400 ... 2
Type Propeller
Number ... Dia. mm 1 ... ø420
Fan motor model ... Number KFG651C5PS ... 1
No. of poles ... rpm (240 V) 6 ... 870
Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 67.1
WHT – PNK : 83.8
Safety
Type Internal protector
devices Operating temp. Open °C 130 ± 5
Close Automatic reclosing
Run capacitor µF 4.0
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 1
Fin pitch mm 1.3
Face area m
2
0.506
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
Outdoor Unit SAPCM1821A
4
5
2-3. Other Component Specifications
Power Relay (PR) G7L-2A-TUB-55
Coil rating AC 200240V, 50/60Hz
Coil resistance (at 23°C) 21 ± 15%
Contact rating AC 220V, 25A
Outdoor Unit SAPCM1821A
Thermistor (Room sensor) DTN-TKS128B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance (at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAPK91A
6
3. DIMENSIONAL DATA
Indoor Unit SAPK91A
790
250
174 (3)
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8")
Drain hose ø18
58.5
132
41.0
41.0
Center of tubing
hole (2 places)
18.5
57
161
Remote control unit
Unit : mm
7
Outdoor Unit SAPCM1821A
810 15
538
AIR INTAKE
AIR DISCHARGE
136
140
302
630
22
5
275
98 45 45 45
325
Narrow tube service valve
ø6.35 (1/4")
Wide tube service valve
ø9.52 (3/8")
2
1
1
2
Unit : mm
4. COOLING CAPACITY
1 - indoor unit in operation
Indoor Unit SAPK91A (
1)
Outdoor Unit SAPCM1821A
8
2 - indoor units in operation
240V Single phase 50Hz
RATING CAPACITY 5.00 kW
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 20 25 30 35 40 43
TC 5.04 4.82 4.60 4.38 4.11 3.79
CM 1.46 1.58 1.69 1.81 1.91 2.02
21 SHC 3.41 3.30 3.19 3.08 2.95 2.79
15 23 SHC 3.83 3.72 3.61 3.50 3.37 3.21
25 SHC 4.25 4.14 4.03 3.92 3.79 3.63
27 SHC 4.67 4.56 4.45 4.34 4.11 3.79
29 SHC 5.04 4.82 4.60 4.38 4.11 3.79
31 SHC 5.04 4.82 4.60 4.38 4.11 3.79
TC 5.41 5.17 4.94 4.70 4.42 4.07
CM 1.50 1.62 1.74 1.86 1.97 2.08
21 SHC 2.98 2.87 2.76 2.65 2.52 2.36
17 23 SHC 3.40 3.29 3.18 3.07 2.94 2.78
25 SHC 3.82 3.71 3.60 3.49 3.36 3.20
27 SHC 4.24 4.13 4.02 3.91 3.78 3.62
29 SHC 4.66 4.55 4.44 4.33 4.20 4.04
31 SHC 5.08 4.97 4.85 4.70 4.42 4.07
TC 5.75 5.50 5.25 # 5.00 4.70 4.33
CM 1.55 1.67 1.79 1.92 2.03 2.14
21 SHC 2.53 2.42 2.31 2.20 2.07 1.91
19 23 SHC 2.95 2.84 2.73 2.62 2.49 2.33
25 SHC 3.37 3.26 3.14 3.04 2.91 2.75
27 SHC 3.79 3.67 3.56 3.46 3.33 3.17
29 SHC 4.21 4.09 3.98 3.88 3.75 3.59
31 SHC 4.63 4.51 4.40 4.29 4.17 4.01
TC 6.10 5.83 5.57 5.30 4.98 4.58
CM 1.59 1.72 1.84 1.97 2.09 2.20
23 SHC 2.49 2.38 2.27 2.16 2.04 1.88
21 25 SHC 2.91 2.80 2.69 2.58 2.46 2.30
27 SHC 3.33 3.22 3.11 3.00 2.88 2.72
29 SHC 3.75 3.64 3.53 3.42 3.29 3.14
31 SHC 4.17 4.06 3.95 3.84 3.71 3.56
TC 6.47 6.19 5.90 5.57 5.21 4.85
CM 1.62 1.76 1.89 2.03 2.14 2.26
23 25 SHC 2.42 2.31 2.20 2.08 1.95 1.82
27 SHC 2.84 2.73 2.62 2.50 2.37 2.24
29 SHC 3.26 3.15 3.04 2.92 2.79 2.66
31 SHC 3.68 3.57 3.46 3.34 3.21 3.08
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
Indoor Unit SAPK91A (
2)
Outdoor Unit SAPCM1821A
9
5. AIR THROW DISTANCE CHART
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C
Fan speed : High
0
1
2
3
4
0 1 2 3 4 5 6 7 8 9
: Flap angle 0° , : Axis air velocity 0°
: Flap angle 30°, : Axis air velocity 30°
10
Indoor Unit SAPK91A
6. REFRIGERANT FLOW DIAGRAM
11
Indoor Unit SAPK91A
Outdoor Unit SAPCM1821A
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of condensa-
tion, both tubes must be well insulated with a proper insula-
tion material. The thickness of the insulation should be a min.
8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
IMPORTANT
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
CAUTION
Outdoor Unit
Wide tube
O.D.
ø9.52mm
(3/8 ")
Narrow tube
O.D.
ø6.35 mm
(1/4")
Condenser
Wide tube
service
valve
Compressor A
Accumulator
Compressor B
B
A
A
Narrow tube
service
valve
Capillary tube
B
Accumulator
Evaporator
Indoor Unit A
Evaporator
Indoor Unit B
7. ELECTRICAL DATA
7-1. Electrical Characteristics
1 - indoor unit in operation
2 - indoor units in operation
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.36 0.50 8.44 9.3
Power Input kW 0.080 0.119 1.921 2.12
Full Load Conditions Running Amps. A 0.36 0.50 10.04 10.9
Power Input kW 0.080 0.119 2.261 2.46
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAPK91A (
2)
Outdoor Unit SAPCM1821A
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 240V Single phase 50Hz
Rating Conditions Running Amps. A 0.18 0.50 4.32 5.0
Power Input kW 0.040 0.119 0.951 1.11
Full Load Conditions Running Amps. A 0.18 0.50 5.12 5.8
Power Input kW 0.040 0.119 1.121 1.28
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAPK91A (
1)
Outdoor Unit SAPCM1821A
12
13
7-2. Electric Wiring Diagram
Indoor Unit SAPK91A
To avoid electrical shock hazard, be sure to
disconnect power before checking, servicing
and/or cleaning any electrical parts.
WARNING
14
Outdoor Unit SAPCM1821A
To avoid electrical shock hazard, be sure to
disconnect power before checking, servicing
and/or cleaning any electrical parts.
WARNING
8. INSTALLATION INSTRUCTIONS
To prevent abnormal heat gen-
eration and the possibility of
fire, don’t place obstacles,
enclosures and grills in front of
or surrounding the air condi-
tioner in a way that may block
air flow.
AVOID:
direct sunlight.
nearby heat sources that may affect performance of
the unit.
areas where leakage of flammable gas may be expect-
ed.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner
of the room can be uniformly air-conditioned. (High on
a wall is best)
select a location that will hold the weight of the unit.
select a location where tubing and drain pipe have the
shortest run to the outside.
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2a)
Indoor Unit
5 cm
min.
5 cm
min.
5 cm min.
INDOOR UNIT
Front View
Wall-mounted Type
Wall-Mounted Type
Front View
Fig.2a
WARNING
Minimum height
from floor level
1.5m
Indoor Unit
Wall
Floor level
For stable operation of
the air conditioner, do
not install wall-mounted
type indoor units under
1.5m from floor level.
CAUTION
Fig. 2b
8-1. Installation Site Selection
Maximum Allowable Tubing Length(L)and Elevation
Difference(H).
The Multi-Split System outdoor unit should be installed as
close to the indoor units as possible. Maximum allowable
length of the refrigerant tubing and elevation difference
between outdoor and indoor units are shown in Table 1.
15
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Less than elevation
difference (H) between
the 2 units
Fig. 1
Max allowable
tubing length
at shipment.(m)
Limit tubing length (L).
(m)
7.5 15 7
Limit of elevation
difference (H).
(m)
15
Required amount of
additional
refrigerant*(g/m)
Table 1
* If total tubing length becomes 7.5 to 15 m (max.),charge additional refrigerant (R22) by 15 g/m.
No additional charge of compressor oil is necessary.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62

Sanyo SAP–CM1821A Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI