Rosemount 3051P In-Line Pressure Transmitter Owner's manual

Category
Measuring, testing & control
Type
Owner's manual
Reference Manual
00809-0700-4001, Rev AC
April 2020
Rosemount
3051P In-Line Pressure
Transmitter
with HART
®
Protocol
2
Contents
Chapter 1 Introduction.............................................................................................................. 5
1.1 Using this manual........................................................................................................................ 5
1.2 Models covered........................................................................................................................... 5
1.3 Product recycling/disposal...........................................................................................................5
Chapter 2 Configuration............................................................................................................ 7
2.1 Safety messages.......................................................................................................................... 7
2.2 System readiness.........................................................................................................................8
2.3 HART
®
installation flowchart......................................................................................................10
2.4 Transmitter overview.................................................................................................................11
2.5 Configuration overview............................................................................................................. 14
2.6 Configuration basics.................................................................................................................. 14
2.7 Verifying configuration..............................................................................................................17
2.8 Basic setup of the transmitter.................................................................................................... 19
2.9 Configuring the LCD display.......................................................................................................24
2.10 Detailed transmitter setup.......................................................................................................25
2.11 Performing transmitter tests................................................................................................... 30
2.12 Configuring burst mode...........................................................................................................32
2.13 Establishing multidrop communication................................................................................... 34
Chapter 3 Hardware installation.............................................................................................. 37
3.1 Overview................................................................................................................................... 37
3.2 Safety messages........................................................................................................................ 37
3.3 Considerations...........................................................................................................................38
3.4 Installation procedures.............................................................................................................. 39
3.5 Rosemount 306 Manifold.......................................................................................................... 48
Chapter 4 Electrical installation................................................................................................49
4.1 Overview................................................................................................................................... 49
4.2 Safety messages........................................................................................................................ 49
4.3 Local Operating Interface (LOI)/LCD display...............................................................................50
4.4 Configuring transmitter security................................................................................................52
4.5 Set transmitter alarm.................................................................................................................55
4.6 Electrical considerations............................................................................................................ 55
Chapter 5 Operation and maintenance.....................................................................................63
5.1 Overview................................................................................................................................... 63
5.2 Safety messages........................................................................................................................ 63
5.3 Recommended calibration tasks................................................................................................64
5.4 Calibration overview.................................................................................................................. 65
Reference Manual Contents
00809-0700-4001 April 2020
Rosemount 3051P 3
5.5 Trimming the pressure signal.....................................................................................................68
5.6 Trimming the analog output......................................................................................................72
5.7 Switching HART
®
revision.......................................................................................................... 75
Chapter 6 Troubleshooting...................................................................................................... 77
6.1 Overview................................................................................................................................... 77
6.2 Safety messages........................................................................................................................ 77
6.3 Troubleshooting for 4-20 mA output......................................................................................... 78
6.4 Diagnostic messages................................................................................................................. 80
6.5 Disassembly procedures............................................................................................................ 86
6.6 Reassembly procedures............................................................................................................. 88
6.7 Service support..........................................................................................................................88
Chapter 7 Safety instrumented systems requirements............................................................. 91
7.1 Safety instrumented systems (SIS) certification......................................................................... 91
7.2 Safety certified identification..................................................................................................... 91
7.3 Installation in safety instrumented systems (SIS) applications....................................................91
7.4 Configuring in safety instrumented systems (SIS) applications...................................................92
7.5 Safety instrumented systems (SIS) operation and maintenance.................................................93
7.6 Inspection..................................................................................................................................95
Appendix A Reference data......................................................................................................... 97
A.1 Product certifications and installation drawings.........................................................................97
A.2 Ordering information, specifications, and dimensional drawings...............................................97
Appendix B Field Communicator menu trees and Fast Keys......................................................... 99
B.1 Menu trees................................................................................................................................ 99
B.2 Fast Keys..................................................................................................................................103
Appendix C Local operator interface (LOI)................................................................................. 105
C.1 Local operator interface (LOI) menu tree................................................................................. 105
C.2 Local operator interface (LOI) menu tree - extended menu...................................................... 106
C.3 Entering numbers....................................................................................................................107
C.4 Entering text............................................................................................................................108
Contents Reference Manual
April 2020 00809-0700-4001
4 Emerson.com/Rosemount
1 Introduction
1.1 Using this manual
The sections in this manual provide information on installing, operating, and maintaining
the Rosemount 3051P. The sections are organized as follows:
Configuration provides instruction on commissioning and operating Rosemount 3051P
Transmitters. It also includes information on software functions, configuration
parameters, and online variables.
Hardware installation contains mechanical installation instructions and field upgrade
options.
Electrical installation contains electrical installation instructions, and field upgrade
options.
Operation and maintenance provides detailed information on calibrating and changing
HART
®
Revisions.
Troubleshooting provides troubleshooting techniques for the most common operating
problems.
Safety instrumented systems requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety
Instrumented Systems.
Specifications and reference data provides information on how to access reference and
specification data, as well as ordering information.
Field Communicator menu trees and Fast Keys provides the menu trees and HART Fast
Keys used to operate the transmitter.
Local operator interface (LOI) provides menu trees and instructions on using the LOI.
1.2 Models covered
The following Rosemount Pressure Transmitters are covered by this manual:
Rosemount 3051P In-Line Gage Pressure Transmitter: Measures gage pressure up to
4,000 psig (275.8 BarG).
Rosemount 3051P In-Line Absolute Pressure Transmitter: Measures absolute pressure
up to 4,000 psig (275.8 BarG).
1.3 Product recycling/disposal
Consider recycling equipment and packaging. Dispose of the product and packaging in
accordance with local and national legislation.
Reference Manual
Introduction
00809-0700-4001 April 2020
Rosemount 3051P 5
Introduction Reference Manual
April 2020 00809-0700-4001
6 Emerson.com/Rosemount
2 Configuration
2.1 Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of the Rosemount 3051P Product Data Sheet
for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or non-
incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts. Improper assembly of manifolds
to traditional flange can damage sensor module.
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 7
WARNING
Improper assembly of manifolds to traditional flange can damage the device.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
2.2 System readiness
If using HART
®
based control or asset management systems, confirm the HART
capability of such systems prior to commissioning and installation. Not all systems are
capable of communicating with HART Revision 7 devices.
For instructions on how to change the HART revision of your transmitter, see Switching
HART
®
revision.
2.2.1
Confirm correct device driver
Procedure
1. Verify the latest Device Driver (DD/DTM
) is loaded on your systems to ensure
proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the latest DD.
3. Select desired product and download the DD.
a) Reference Table 2-1 for the correct DD.
Table 2-1: Device Revisions and Files
Identify device Find device driver
files
Review instructions Review
functionality
Software
release
date
NAMUR
hardware
revision
(1)
NAMUR
software
revision
(1)
HART
®
software
revision
(2)
HART
universal
revision
Device
revision
(3)
Manual document
number
Changes to software
August
2016
1.1.xx 1.0.xx 03 7 10 00809-0700-4001 HART Revision 5
and 7 selectable
Configuration Reference Manual
April 2020 00809-0700-4001
8 Emerson.com/Rosemount
Table 2-1: Device Revisions and Files (continued)
Identify device Find device driver
files
Review instructions Review
functionality
5 9 Local operator
interface (LOI)
Scaled variable
Configurable
alarms
Expanded
engineering units
Updated
electronics
hardware design
Intrinsic Safety
temperature
classification
change
(1) NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx,
represent minor product changes as defined per NE53. Compatibility and functionality are preserved, and products can
be used interchangeably.
(2) HART software revision can be read using a HART capable configuration tool. Value shown is minimum revision that
could correspond to NAMUR revisions.
(3) Device driver file names use device and DD revision, e.g., 10_01. HART Protocol is designed to enable legacy device
driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver
must be downloaded. Emerson recommends downloading new device driver files to ensure full functionality.
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 9
2.3 HART
®
installation flowchart
Configuration Reference Manual
April 2020 00809-0700-4001
10 Emerson.com/Rosemount
2.4 Transmitter overview
The Rosemount 3051P In-Line Pressure Transmitter is offered for gage pressure (GP) and
absolute pressure (AP) measurements. The transmitter uses piezoresistive sensor
technology for AP and GP measurements.
The major components of the transmitter are the sensor module and the electronics
housing. The sensor module contains the oil-filled sensor system (isolating diaphragm, oil
fill system, and sensor). The electronics board is located within the electronics housing.
The electrical signals from the sensor module are transmitted to the electronics board
which contains the memory module and the analog to digital signal converter (A/D
converter). The signal is then converted to a 4–20mA analog output signal or HART
®
digital signal. The electronics housing contains the output electronics board, the optional
external configuration buttons, and the terminal block. The basic block diagram of the
transmitter is illustrated in Figure 2-2.
When pressure is applied to the isolating diaphragm, the oil deflects the sensor, which
then changes its capacitance or voltage signal. This signal is then changed to a digital
signal by the Signal Processing. The microprocessor then takes the signals from the Signal
Processing and calculates the correct output of the transmitter. This signal is then sent to
the D/A converter, which converts the signal back to the analog signal and then
superimposes the HART signal on the 4–20 mA output.
An optional LCD display can be ordered that connects directly to the interface board,
which maintains direct access to the signal terminals. The display indicates output and
abbreviated diagnostic messages. A glass display cover is provided. For 4-20 mA HART
output, the LCD display features a two-line display. The first line displays the actual
measured value; the second line of six characters displays the engineering units. The LCD
display can also display diagnostic messages.
Note
LCD display uses a 5x6 character display and can display output and diagnostic messages.
The local operator interface (LOI) display uses an 8x6 character display and can display
output and diagnostic messages as well as and LOI menu screens. The LOI display comes
with two buttons mounted on the front of the display board. See Figure 2-1.
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 11
Figure 2-1: LCD/LOI display
LCD display LOI display
Configuration Reference Manual
April 2020 00809-0700-4001
12 Emerson.com/Rosemount
Figure 2-2: Block Diagram of Operation
A. Sensor module and electronics
B. 4-20 mA signal to control system
C. Field Communicator
D. Signal processing
E. Temperature sensor
F. Pressure sensor
G. Sensor module memory
H. Microprocessor
Sensor linearization
Rerange
Damping
Diagnostics
Engineering units
Communication
I. Memory
Configuration
J. Digital-to-analog signal conversion
K. Digital communication
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 13
2.5 Configuration overview
This section contains information on commissioning and tasks that should be performed
on the bench prior to installation, as well as tasks performed after installation as described
in Performing transmitter tests.
Field Communicator, AMS Device Manager, and local operator interface (LOI) instructions
are given to perform configuration functions. For convenience, Field Communicator Fast
Key sequences are labeled “Fast Keys,” and abbreviated LOI menus are provided for each
function below.
Full Field Communicator menu trees and Fast Key sequences are available in Field
Communicator menu trees and Fast Keys. LOI menu trees are available in Local operator
interface (LOI).
2.6 Configuration basics
CAUTION
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
You can configure the transmitter either before or after installation. Configuring the
transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI
ensures all transmitter components are in working order prior to installation. Verify that
the security switch is set in the unlock position ( ) to proceed with configuration. See
Figure 4-2 for switch location.
2.6.1
Configuring on the bench
To configure on the bench, you will need a power supply and a Field Communicator, AMS
Device Manager, or local operator interface (LOI), option M4.
Wire equipment as shown in Figure 2-3. To ensure successful HART
®
communication, a
resistance of at least 250 Ωs must be present between the transmitter and the power
supply; see Power supply for details. Connect the Field Communicator leads to the
terminals labeled “COMM” on the terminal block.
Configuration Reference Manual
April 2020 00809-0700-4001
14 Emerson.com/Rosemount
Figure 2-3: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. R
L
≥ 250 (necessary for HART communication only)
2.6.2
Configuration tools
Configuring with a Field Communicator
There are two interfaces available with the Field Communicator: traditional and
dashboard.
This manual describes all steps using a Field Communicator using dashboard interfaces.
Figure 2-4 shows the Device Dashboard interface. As stated in System readiness, it is
critical that the latest device descriptors (DDs) are loaded into the Field Communicator.
Visit Emerson.com or FieldCommGroup.org to download the latest DD library.
Field Communicator menu trees and Fast Keys are available in Field Communicator menu
trees and Fast Keys.
Figure 2-4: Device Dashboard
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B
Online
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 15
Configuring with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current
device descriptor (DD) for this device. Download the latest DD at Emerson.com or
FieldCommGroup.org.
Note
This manual describes all steps using AMS Device Manager version 11.5.
Configuring with a local operator interface (LOI)
To use the LOI, order the transmitter with option code M4. To activate the LOI push either
configuration button. Configuration buttons are located on the LCD display (must remove
housing cover to access), or underneath the top tag of the transmitter. See Table 2-2 for
configuration button functionality and Figure 2-5 for configuration button location.
When using the LOI for configuration, several features require multiple screens for a
successful configuration. Data entered will be saved on a screen-by-screen basis; the LOI
will indicate this by flashing SAVED on the LCD display each time.
LOI menu trees are available in Local operator interface (LOI).
Figure 2-5: LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
Configuration Reference Manual
April 2020 00809-0700-4001
16 Emerson.com/Rosemount
Table 2-2: LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER
2.6.3 Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of
the transmitter, set the process application loop to manual control.
The Field Communicator, AMS Device Manager, or local operator interface (LOI) will
prompt you to set the loop to manual when necessary. The prompt is only a reminder;
acknowledging this prompt does not set the loop to manual. You must set the loop to
manual control as a separate operation.
2.7 Verifying configuration
Emerson recommends verifying various configuration parameters prior to installing them
into the process.
The various parameters are detailed out for each configuration tool. Depending on what
configuration tool(s) are available follow the steps listed relevant to each tool.
2.7.1
Verifying configuration with Field Communicator
Review configuration parameters listed in Table 2-3 prior to transmitter installation. A Full
list of configuration parameters that can be reviewed and configured using a Field
Communicator are located in Field Communicator menu trees and Fast Keys.
Fast Key sequences for the latest device descriptor (DD) are shown in Table 2-3. For Fast
Key sequences for legacy DDs, contact your local Emerson Representative.
Procedure
From the HOME screen, enter the Fast Key sequences listed
Table 2-3: Device Dashboard Fast Key Sequence
Function Fast Key sequence
HART
®
7 HART 5
Alarm and saturation levels 2, 2, 2, 5 2, 2, 2, 5
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 17
Table 2-3: Device Dashboard Fast Key Sequence (continued)
Function Fast Key sequence
HART
®
7 HART 5
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Primary variable 2, 1, 1, 4, 1 2, 1, 1, 4, 1
Range values 2, 1, 1, 4 2, 1, 1, 4
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4
2.7.2 Verifying configuration with AMS Device Manager
Procedure
1. Right click on the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.7.3
Verifying configuration with local operator interface
(LOI)
Procedure
1. Press any configuration button to activate the LOI.
2. Select VIEW CONFIG to review the below parameters.
3. Use the configuration buttons to navigate through the menu.
Review the following pareameters prior to installation:
Tag
Units
Transfer Function
Alarm and Saturation Levels
Primary Variable
Range Values
Damping
Configuration Reference Manual
April 2020 00809-0700-4001
18 Emerson.com/Rosemount
2.7.4 Verifying process variables configuration
This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys 3, 2, 1
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary, and
quaternary variables.
2.8 Basic setup of the transmitter
This section provides the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to Configuring scaled variable for
setup instructions.
2.8.1
Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 1, 1, 4
Setting pressure units with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
Reference Manual Configuration
00809-0700-4001 April 2020
Rosemount 3051P 19
Setting pressure units with a local operator interface (LOI)
Procedure
1. Follow Figure 2-6 to select desired pressure and temperature units.
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
Example
Figure 2-6: Selecting Units with LOI
2.8.2 Reranging the transmitter
The range values command sets each of the lower and upper range analog values to a
pressure. The lower range point represents 0 percent of range and the upper range point
represents 100 percent of range.
In practice, the transmitter range values may be changed as often as necessary to reflect
changing process requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or local operator interface (LOI).
Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 1
Configuration Reference Manual
April 2020 00809-0700-4001
20 Emerson.com/Rosemount
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110

Rosemount 3051P In-Line Pressure Transmitter Owner's manual

Category
Measuring, testing & control
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI