Danfoss ECL Apex 10 Operating instructions

Type
Operating instructions
Technical manual
ECL Apex 10
Control parameters and functions
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004
VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004
Technical manual ECL Apex 10, control parameters and functions
Boost .....................................................................................................5
Room ....................................................................................................5
Energy ..................................................................................................5
Primary flow .......................................................................................5
Universal ..............................................................................................5
Sliding DHW priority .......................................................................5
Reference ............................................................................................5
Sliding frost protection ..................................................................5
Wind ......................................................................................................5
Sun .........................................................................................................5
Weather compensation ...............................6
Settings ......................................................6
-- Heat curve -- .............................................6
Slope ....................................................................................................6
Parallel displacement ....................................................................7
Flow temp. - max .............................................................................7
Flow temp. - min .............................................................................7
X1 .... X6 ..............................................................................................7
Y1 .... Y6 ..............................................................................................7
-- Room temp. influence -- ..........................8
Influence - max ................................................................................8
Influence - min .................................................................................8
Time constant ..................................................................................8
-- Optimizer -- ..............................................9
Optimizer ...........................................................................................9
Optimizer based on: .....................................................................9
Optimizing constant .......................................................................9
-- Reduction -- .............................................9
Total stop ...........................................................................................9
Temperature based on ............................................................... 10
0% at ................................................................................................ 10
100% at ............................................................................................ 10
-- Heating cut-out -- ..................................10
Cut-out at ........................................................................................ 10
Accum. time constant .................................................................11
Accum. temperature .....................................................................11
-- Sliding frost protection -- .....................11
Outdoor setpoint ..........................................................................11
Gain ....................................................................................................11
-- Condition -- ............................................11
Reference ramping .......................................................................11
Boost ..................................................................................................11
-- DHW priority -- .......................................12
Deviation ..........................................................................................12
Time constant ................................................................................12
Master circuit ..................................................................................12
-- Return temp. limitation -- .....................12
Return temp. reference ................................................................12
Setpoint ............................................................................................12
Table of Contents
Introduction .................................................1
Common readout values ............................1
Flow .......................................................................................................1
Ref. .........................................................................................................1
Return ...................................................................................................1
Outdoor ...............................................................................................1
General .........................................................1
Control mode ...................................................................................1
Control status ....................................................................................1
Control status ....................................................................................1
Status ....................................................................................................1
Comfort setpoint ............................................................................2
Setback setpoint .............................................................................2
Comfort setpoint ............................................................................2
Setback setpoint .............................................................................2
Comfort setpoint ............................................................................2
Setback setpoint .............................................................................2
Setback flow temp. ........................................................................2
Valve (%) .............................................................................................2
Valve ......................................................................................................2
Circulation pump (%) .....................................................................2
Circulation pump 1 ... 4 ..................................................................2
Circulation pump alarm .................................................................2
Return temp. reference ..................................................................3
Makeup valve ....................................................................................3
Makeup pump (%) ...........................................................................3
Makeup pump 1 ... 2 ........................................................................3
Makeup pump alarm ......................................................................3
Inputs ............................................................3
Outdoor temperature ....................................................................3
Room temperature ..........................................................................3
Flow pressure - sec. .........................................................................3
Return pressure - sec. .....................................................................3
Makeup pressure ..............................................................................3
Makeup pressure switch ...............................................................3
Diff. pressure switch ........................................................................3
Circ. pump 1 ... 2 - overload ..........................................................4
Energy value ......................................................................................4
Energy unit .........................................................................................4
Primary flow .......................................................................................4
Unit ........................................................................................................4
Universal input (%) ..........................................................................4
Universal input (°C) .........................................................................4
Universal input (bar) .......................................................................4
Wind input ..........................................................................................4
Sun input [W/m
2
] .............................................................................4
Supply temperature ........................................................................4
Sec. return temperature ................................................................4
Limiters .........................................................5
Return ...................................................................................................5
Ramping ..............................................................................................5
Heating cut-out ................................................................................5
VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
Low outdoor temp. (X1) ..............................................................13
Lower limit (Y1) ..............................................................................13
High outdoor temp. (X2) ............................................................13
Upper limit (Y2) ...............................................................................13
Influence - max ...............................................................................13
Influence - min ................................................................................13
Time constant ..................................................................................14
Min ref. ...............................................................................................14
-- Energy limitation -- ...............................14
Actual value .....................................................................................14
Energy reference ............................................................................14
Unit .....................................................................................................14
Setpoint .............................................................................................14
Low outdoor temp. (X1) ...............................................................14
Lower limit (Y1) ...............................................................................14
High outdoor temp. (X2) .............................................................15
Upper limit (Y2) ...............................................................................15
Time constant ..................................................................................15
-- Flow limitation -- ....................................15
Actual primary flow ......................................................................15
Primary flow ref. .............................................................................15
Unit ......................................................................................................15
Setpoint .............................................................................................15
Low outdoor temp. (X1) .............................................................. 16
Lower limit (Y1) .............................................................................. 16
High outdoor temp. (X2) ............................................................ 16
Upper limit (Y2) .............................................................................. 16
Time constant ................................................................................. 16
-- Anti bacteria function -- .........................16
Setpoint ............................................................................................ 16
-- Universal influence -- .............................16
Actual input (%) ............................................................................. 16
Actual input (°C) .............................................................................17
Actual input (bar) ...........................................................................17
Setpoint .............................................................................................17
Influence - max ...............................................................................17
Influence - min ................................................................................17
Time constant ..................................................................................17
-- Wind influence -- ....................................17
Actual input ....................................................................................17
Setpoint ........................................................................................... 18
Influence - max .............................................................................. 18
Influence - min ............................................................................... 18
-- Sun influence -- .......................................18
Actual input [W/m
2
] ..................................................................... 18
Setpoint ........................................................................................... 18
Influence - max .............................................................................. 18
Influence - min ............................................................................... 18
Controls ......................................................19
-- Control -- .................................................19
Proportional band (Xp) ................................................................19
Reset time (Tn) .............................................................................19
Rate time (Tv) ................................................................................19
Motor running time ....................................................................19
Neutral zone .................................................................................19
Valve exercise .............................................................................. 20
Alarm delay .................................................................................. 20
Above diff. ..................................................................................... 20
Below diff. ..................................................................................... 20
Alarm ref. - min ........................................................................... 20
-- Circulation pumps -- ...............................21
Circulation pump .......................................................................... 21
Pump pressure diff. ................................................................... 21
Pressure setpoint ....................................................................... 21
Changeover time ........................................................................ 21
Changeover day ......................................................................... 21
Changeover delay ...................................................................... 21
Stabilization time ........................................................................ 21
Auto clear alarm function ....................................................... 21
Auto clear alarm ......................................................................... 21
Pump exercise ............................................................................. 22
- Days between ............................................................................. 22
Post-run .......................................................................................... 22
Start reference ............................................................................ 22
Start outdoor ............................................................................... 22
Proportional band (Xp) ............................................................. 22
Reset time (Tn) ............................................................................. 22
Neutral zone * 10 .......................................................................... 22
Rate time (Tv) ............................................................................... 23
Min output ................................................................................... 23
Pump start delay ........................................................................ 23
Select rotation ............................................................................. 23
- Days between rotation .......................................................... 23
-- Makeup water -- .................................... 23
Makeup water ................................................................................ 23
Pressure setpoint .......................................................................... 23
Hysteresis ......................................................................................... 23
Stabilization time .......................................................................... 23
Pump exercise ............................................................................. 24
- Days between ............................................................................. 24
Proportional band (Xp) ............................................................. 24
Reset time (Tn) ............................................................................. 24
Neutral zone * 10 .......................................................................... 24
Rate time (Tv) ............................................................................... 25
Min output ................................................................................... 25
Overview ................................................... 26
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 1
Technical manual ECL Apex 10, control parameters and functions
Introduction
This manual lists all readouts and settings of the ECL Apex
10. With the help of this list, it will be possible to enter all
relevant settings. As the ECL Apex 10 has a dynamic user
interface, each choice you make will rule out other choices.
This means that not all the listed settings will be available in
the configuration process.
The circuit type is illustrated with pictograms right above
each readout / setting depending on the circuit it is valid for:
The heating circuit as and the domestic hot-water (DHW)
as .
Provided that the Pt 1000 sensors are correctly configured,
the value 250 will correspond to disconnected or
deactivated and -150 to short-circuited.
Common readout values
?
Flow
Readout value
°C
Measured flow temperature.
?
Ref.
Readout value
°C
Calculated flow temperature reference.
?
Return
Readout value
°C
Measured return temperature.
?
Outdoor
Readout value
°C
Measured outdoor temperature (filtered).
General
Control mode ?
Setting range Factory setting
Auto, Comfort,
Setback, Standby
Auto
The operation mode can be set if no external mode ctrl is
connected.
Automatic operation
This is the normal mode. The temperature is controlled
according to schedule with automatic changeover between
comfort and setback temperature periods.
Constant comfort temperature
The schedule is overruled.
Constant setback temperature
The schedule is overruled.
Standby
Heating is stopped. The system is protected against frost.
?
Control status
Readout value
Setback, Pre-Comfort,
Comfort , Pre-Setback,
Standby
In the control status you can see how the controller
operates, i.e. which mode it is in during automatic operation.
Pre-Comfort / Pre-Setback
Indicate heating periods, set by optimizer.
?
Control status
Readout value
Setback,
Comfort , Standby
In the control status you can see how the controller
operates, i.e. which mode it is in during automatic operation.
?
Status
Readout value
Passive, Active,
Anti bacteria
2 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
Comfort setpoint ?
Setting range Factory setting
10 ... 150 °C 50 °C
Set the desired flow temperature during comfort periods.
Setback setpoint ?
Setting range Factory setting
10 ... 150 °C 45 °C
Set the desired flow temperature during setback periods.
Comfort setpoint ?
Setting range Factory setting
10.0 ... 30.0 °C 20.0 °C
Can only be set if the chosen ‘Control strategy’ is either
‘Standard weather compensation + room temperature
control’ or ‘Weather compensation according to heat curve
with 6 points + room temperature control’.
Set the desired room temperature during comfort periods.
Setback setpoint ?
Setting range Factory setting
10.0 ... 30.0 °C 16.0 °C
Can only be set if the chosen ‘Control strategy’ is either
‘Standard weather compensation + room temperature
control’ or ‘Weather compensation according to heat curve
with 6 points + room temperature control’.
Set the desired flow temperature during setback periods.
Comfort setpoint ?
Setting range Factory setting
10.0 ... 150.0 °C 50.0 °C
Can only be set if the chosen ‘Control strategy’ is ‘Constant
temperature control’ (no weather compensation).
Set the desired flow temperature during comfort periods.
Setback setpoint ?
Setting range Factory setting
10.0 ... 150.0 °C 20.0 °C
Can only be set if the chosen ‘Control strategy’ is ‘Constant
temperature control’ (no weather compensation).
Set the desired flow temperature during setback periods.
Setback flow temp. ?
Setting range Factory setting
-150.0 ... 0.0 K -40.0 K
Can only be set if the chosen ‘Control strategy’ is ‘Weather
compensation according to a heat curve with 6 points’.
During setback the 6-point heat curve will be lowered by
this value.
?
Valve (%)
Readout value
0.0 ... 100.0%
Is only displayed if ‘0-10 V, PID’ is selected.
?
Valve
Readout value
Stopped, Opening, Closing,
Inactive
Is only displayed if ‘3-pt. PI(D)’ is selected.
?
Circulation pump (%)
Readout value
0.0 ... 100.0%
Is only displayed if ‘PID (0-10 V)’ is selected.
?
Circulation pump 1 ... 4
Readout value
ON / OFF
Is only displayed if ‘Circulation pump’ is selected.
?
Circulation pump alarm
Readout value
Bell / No bell
Is only displayed if ‘Twin pump’ is selected.
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 3
Technical manual ECL Apex 10, control parameters and functions
?
Return temp. reference
Readout value
°C
Is only displayed if a return temperature sensor is selected.
?
Makeup valve
Readout value
Opened / Closed
Is only displayed if ‘Makeup water’ is selected.
?
Makeup pump (%)
Readout value
0.0 ... 100.0%
Is only displayed if ‘Makeup water’ and ‘PID (0-10 V)’ are
selected.
?
Makeup pump 1 ... 2
Readout value
ON / OFF
Is only displayed if ‘Makeup water’ is ‘ON / OFF’ controlled.
?
Makeup pump alarm
Readout value
Bell / No bell
Is only displayed if ‘Makeup water’ is ‘ON / OFF’ controlled.
Inputs
?
Outdoor temperature
Readout value
°C
Is only displayed if an outdoor temperature sensor is selected.
?
Room temperature
Readout value
°C
Is only displayed if a room temperature sensor is selected.
?
Flow pressure - sec.
Readout value
bar
Is only displayed if a flow pressure sensor is selected.
Measured flow pressure on the secondary side of the heat
exchanger.
?
Return pressure - sec.
Readout value
bar
Is only displayed if a return pressure sensor is selected.
Measured return pressure on the secondary side of the heat
exchanger.
?
Makeup pressure
Readout value
bar
Is only displayed if ‘Makeup water’ is ‘ON / OFF ‘ and ‘Analog’
is selected.
?
Makeup pressure switch
Readout value
Alarm / No alarm
Is only displayed if ‘Makeup water’ is ‘ON / OFF ‘ and ‘Digital
is selected.
?
Diff. pressure switch
Readout value
Alarm / No alarm
Is only displayed if a differential pressure switch is set up.
4 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
?
Circ. pump 1 ... 2
- overload
Readout value
Alarm / No alarm
Is only displayed if ‘Circulation pump’ and ‘Circulation pump
- overload’ sensor are selected.
?
Energy value
Readout value
Value only
Is only displayed if ‘Energy’ sensor is selected.
?
Energy unit
Readout value
W, kW, MW, GW
Is only displayed if ‘Energy’ sensor is selected.
?
Primary flow
Readout value
X.X
Is only displayed if ‘Primary flow’ sensor is selected.
?
Unit
Readout value
l/s, m
3
/s, l/min, m
3
/min,
l/h, m
3
/h
Is only displayed if ‘Flow limiter’ sensor is selected.
?
Universal input (%)
Readout value
%
Is only displayed if ‘Universal limiter, PI’ and ‘Analog’ are
selected.
?
Universal input (°C)
Readout value
°C
Is only displayed if ‘Universal limiter, PI’ and ‘Temperature’ are
selected.
?
Universal input (bar)
Readout value
bar
Is only displayed if ‘Universal limiter, PI’ and ‘Pressure’ are
selected.
?
Wind input
Readout value
m/s
Is only displayed if ‘Wind limiter, P’ sensor is selected.
?
Sun input [W/m
2
]
Readout value
X.X
Is only displayed if ‘Sun limiter, P’ sensor is selected.
?
Supply temperature
Readout value
°C
Is only displayed if a ‘Supply temperature’ sensor is selected.
?
Sec. return temperature
Readout value
°C
Is only displayed if a ‘Sec. return temperature’ sensor is
selected.
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 5
Technical manual ECL Apex 10, control parameters and functions
Limiters
If the flow temperature reference is different from the
expected value, the reason can be an influence from a
limiter.
?
Return
Readout value
Active / Passive
Is only displayed if ‘Return temperature’ sensor is selected.
?
Ramping
Readout value
Active / Passive
Is only displayed if ‘Reference ramping’ > 0 min
?
Heating cut-out
Readout value
Active / Passive
Is only displayed if ‘Outdoor temperature‘ sensor is selected.
?
Boost
Readout value
Active / Passive
Is only displayed if ‘Boost’ > 0%.
?
Room
Readout value
Active / Passive
Is only displayed if ‘Room temperature’ sensor is selected.
?
Energy
Readout value
Active / Passive
Is only displayed if ‘Energy ’ sensor is selected.
?
Primary flow
Readout value
Active / Passive
Is only displayed if ‘Primary flow‘ sensor is selected.
?
Universal
Readout value
Active / Passive
Is only displayed if ‘Universal limiter, PI’ is selected.
?
Sliding DHW priority
Readout value
Active / Passive
?
Reference
Readout value
Active / Passive
Is only displayed if ‘Reference control’ is set up.
?
Sliding frost protection
Readout value
Active / Passive
?
Wind
Readout value
Active / Passive
Is only displayed if ‘Wind limiter, P’ sensor is selected.
?
Sun
Readout value
Active / Passive
Is only displayed if ‘Sun limiter, P’ sensor is selected.
6 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
Weather compensation
The ECL Apex 10 is a weather compensated flow
temperature controller, which means that the ECL Apex 10
controls the heating circuit temperature in accordance with
the outdoor temperature.
The ECL Apex is controlled according to the following
control strategies:
Constant temp. =
Constant temperature control (no weather compensation)
6-pt weather comp. =
Weather compensation according to a heat curve with 6
points
Std w.comp. + room T =
Standard weather compensation + room temperature
control
6-pt w.comp. + room T =
Weather compensation according to a heat curve with 6
points + room temperature control
Settings
-- Heat curve --
The heat curve consists of four parameters: slope, parallel
displacement and min/max flow temperature.
Standard heat slope
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
Slope 20a
Setting range Factory setting
0.1 ... 3.6 1.8
Is displayed if ‘Control strategy’ is ‘Std w.comp. + room T’.
The heat curve slopee depends on the heating system and
area specific design parameters.
Example I
Design parameter:
Designed outdoor temperature (T
out
) -12 °C
Designed flow temperature (T
flow
) 80 °C
Designed room temperature (T
room
) 20 °C
For designed flow temperature higher than 40 °C, the heat
curve slope (S) can be calculated as:
S =
T
flow
- 25
2.5 x T
room
- T
out
- 30
S =
80 - 25
2.5 x 20 - (- 12) - 30
S ≈ 1.7
Example II
Design parameter:
Designed outdoor temperature (T
out
) -20 °C
Designed flow temperature (T
flow
) 35 °C
Designed room temperature (T
room
) 21 °C
For designed flow temperatures lower than 40 °C, the heat
curve slope (S) can be calculated as:
S =
T
flow
- 20
1.3 (2.5 x T
room
- T
out
- 30)
S =
35 - 20
1.3 (2.5 x 21 - (- 20) - 30)
S ≈ 0.3
For quick setting, the graph can be used. The graph
is intended for a T
room
of 20 °C. If the design data from
example I is used, the slope will be approx. 1.7.
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 7
Technical manual ECL Apex 10, control parameters and functions
6 point heat curve
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
100
110
o
C
o
C
(X1, Y1)
(X6,
Y6)
X1 .... X6 ?
Setting range Factory setting
X1 -50 ... 150 °C -30 °C
X2 -50 ... 150 °C -20 °C
X3 -50 ... 150 °C -10 °C
X4 -50 ... 150 °C 0 °C
X5 -50 ... 150 °C 10 °C
X6 -50 ... 150 °C 20 °C
Is displayed if ‘Control strategy’ is ‘6-pt weather comp.’ or ‘6-pt
w.comp. + room T’.
The lowest value must be X1 and the highest value X6, i.e.
X1 < X2 < X3 < X4 < X5 < X6.
Y1 .... Y6 ?
Setting range Factory setting
Y1 -50 ... 150 °C 100 °C
Y2 -50 ... 150 °C 90 °C
Y3 -50 ... 150 °C 80 °C
Y4 -50 ... 150 °C 60 °C
Y5 -50 ... 150 °C 50 °C
Y6 -50 ... 150 °C 30 °C
Is displayed if ‘Control strategy’ is ‘6-pt weather comp.’ or ‘6-pt
w.comp. + room T’.
Parallel displacement 20b
Setting range Factory setting
-40 ... 40 K 0 K
Is not displayed if the chosen control strategy is ‘Constant
temperature’.
The parallel displacement has a direct influence on the flow
reference temperature (T
ref
).
Flow temp. - max 20a
Setting range Factory setting
10 ... 150 °C 90 °C
The set max flow temperature must be higher than the min
flow temperature.
The max flow temperature is set to avoid a too high flow
temperature, e.g. when the heating system supplies the
floor heating system.
Flow temp. - min 20a
Setting range Factory setting
10 ... 150 °C 10 °C
The set min flow temperature must be lower than the max
flow temperature.
The min flow temperature is set to avoid a too low flow
temperature, e.g. when the heating system is supplied from
cast-iron boilers.
If the outdoor temperature is higher than 10 °C, it is
recommended only to change the parallel displacement.
For outdoor temperatures below -5 °C, it is recommended
only to change the slope.
8 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
-- Room temp. influence --
This limitation is based on a PI regulation where P
(influence) responds quickly to deviations and I (time
constant) responds slower and over time removes the small
offsets between the reference and actual measured values.
This is done by changing the flow temperature reference.
Influence - max 3a
Setting range Factory setting
-9.9 ... 0.0 -4
Can only be set if ‘Room temperature’ sensor is selected and
‘Control strategy’ is either ‘Std w.comp. + room T’ or ‘6-pt
w.comp. + room T’.
Influence - min 3b
Setting range Factory setting
0.0 ... 9.9 0
Can only be set if ‘Room temperature’ sensor is selected and
‘Control strategy’ is either ‘Std w.comp. + room T’ or ‘6-pt
w.comp. + room T’.
Time constant ?
Setting range Factory setting
600 .... 60000 s 6000 s
Can only be set if ‘Room temperature’ sensor is selected and
‘Control strategy’ is either ‘Std w.comp. + room T’ or ‘6-pt
w.comp. + room T’.
When the value is set to 6000 s, the I attribution is OFF.
There are two basic principles for setting the room
temperature influence:
A: Max room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a max
limitation of the room temperature. The controller will allow
for free heat gains, i.e. solar radiation or heat from a fire
place, etc.
The max influence determines how much the room
temperature should influence the flow temperature
reference.
Influence
Desired room
temperature
Ro
om
temperature
Influence - max
Example I
The actual room temperature is 2 degrees too high.
The influence - max is set to -4.0.
The influence - min is set to 0.0.
The heat curve slope is 1.8.
Result:
The flow temperature reference is changed by
2 x (-4.0) x 1.8 = -14.4 degrees.
B: Reference room temperature control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as a
temperature reference for the rest of the rooms.
(However, should you have a few radiator thermostats
installed, make sure that they are fully open).
The room temperature sensor in the reference room
registers the difference between the desired and the actual
room temperature. The flow temperature reference will be
corrected to eliminate this difference.
Influence
Desired room temperature
Ro
om
temperature
Influence - max
Influence - min
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 9
Technical manual ECL Apex 10, control parameters and functions
Example II
The actual room temperature is 2 degrees too low.
The influence - max is set to -3.5.
The influence - min is set to 2.0.
The heat curve slope is 1.8.
Result:
The flow temperature reference is changed by
2 x 2.0 x 1.8 = 7.2 degrees.
Example III
The actual room temperature is 2 degrees too high.
The influence - max is set to -3.5.
The influence - min is set to 2.0.
The heat curve slope is 1.8.
Result:
The flow temperature reference is changed by
2 x (-3.5) x 1.8 = -12.6 degrees
-- Optimizer --
Optimizes the start and stop times for the comfort
temperature period to obtain the best comfort at the lowest
energy consumption. The lower the outdoor temperature,
the earlier the heating cut-in.
The optimized start and stop times can be based on either
room or outdoor temperature.
Optimizer 14
Setting range Factory setting
ON / OFF OFF
Optimizer based on: 20
Setting range Factory setting
Outdoor / Room Outdoor
Can only be set if the ‘Optimizer’ is set to ON.
The optimization is based on outdoor temperature if the
‘Control strategy’ is set to ‘Constant temp.’ or ‘6-pt weather
comp..
Optimizing constant 14
Setting range Factory setting
10 ... 59 25
Can only be set if the ‘Optimizer’ is set to ON.
Adjust the optimizing time constant. The value
consists of a two digit number.
The two digits have the following meaning:
Digit 1 Heat accumulation of
the building
System type
1 Light
Radiator system2 Medium
3 Heavy
4 Medium
Floor heating
systems
5 Heavy
Digit 2 Dimensioning
temperature
Capacity
1 - 50 °C Large
5 - 25 °C Normal
9 - 5 °C Small
Dimensioning temperature:
The lowest outdoor temperature (usually determined by
your system designer in connection with the design of the
heating system) at which the heating system can maintain
the designed room temperature.
-- Reduction --
Total stop 21
Setting range Factory setting
ON / OFF OFF
Decide whether you want a total stop (standby)during the
setback temperature period.
ON:
The desired flow temperature is lowered to 10 °C. The min
setting of the flow temperature is overruled.
Desired flow
temp. (˚C)
10 ˚C
Time
10 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
OFF:
No total stop
Desired flow
temp. (˚C)
10 ˚C
Time
Temperature based on 11?
Setting range Factory setting
Auto / Fixed Auto
Is only displayed if ‘Total stop’ is ‘OFF.
Auto:
The setback temperature depends on the outdoor
temperature. The lower the outdoor temperature, the less
the temperature reduction.
Fixed:
The setback temperature reduction will be constant at all
outdoor temperatures.
0% at 11?
Setting range Factory setting
-30 ... 20 °C -5 °C
Can only be set if ‘Temperature based on’ = ‘Auto’.
Set the outdoor temperature at which the reduction of the
flow temperature is 0%.
When the outdoor temperature is below the set value, there
is no reduction during setback.
100% at 11?
Setting range
Factory setting
-30 ... 20 °C 10 °C
Can only be set if ‘Temperature based on’ = ‘Auto’.
Set the outdoor temperature at which the reduction of the
flow temperature is 100%.
When the outdoor temperature is above the set value, you
will get a full 100% reduction.
100%
0%
-20 -10-29 0 2015
Re
duction
Outdoor
temp. (˚C)
0% at 100% at
-- Heating cut-out --
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set
limit. The heating system switches ON again when the
outdoor temperature and the accumulated temperature falls
below the set limit.
Heating cut-out is only active in automatic operation.
18 ˚C
Ac
tual outdoor
temperature
Ac
cum.
temperature
Heating Heating OFF Heating
Temp.
Ti
me
Cut-out at 21
Setting range Factory setting
0 ... 60 °C 18 °C
Can only be set if ‘Outdoor temperature’ sensor is selected.
Set the outdoor temperature at which you want the heating
system to stop.
The valve closes and after the post-run time is exceeded, the
heating circulation pump stops.
The limitations set in ‘Flow temp. min’ will be ignored.
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 11
Technical manual ECL Apex 10, control parameters and functions
Accum. time constant
10.4.7
Setting range Factory setting
200 ... 4000 min 1000 min
Can only be set if ‘Outdoor temperature’ sensor is selected.
This constant is used for calculating the accumulated
outdoor temperature.
?
Accum. temperature
Readout value
°C
Is only displayed if ‘Outdoor temperature’ sensor is selected.
-- Sliding frost protection --
Outdoor setpoint 57
Setting range
Factory setting
-30 ... 20 °C 0 °C
Can only be set if ‘Outdoor temperature’ sensor is selected.
Gain 57
Setting range Factory setting
0.0 ... 4.0 0.0
Can only be set if ‘Outdoor temperature’ sensor is selected.
Outdoor
temp. (˚C)
˚C
10
0
Gain = 1
Increased
s
etback temp. ref
-20 -10 0 2010
Outdoor setpoint
If the outdoor temperature during total stop at setback
or standby falls below the outdoor setpoint, the flow
temperature reference will be increased by the difference
between the outdoor setpoint minus the actual outdoor
temperature multiplied by the gain.
Example:
Outdoor setpoint: 0 °C
Gain: 2.0
Actual outdoor temp.: -14 °C
Result:
The flow temperature reference will be increased by 2 x 14
= 28 degrees.
-- Condition --
Reference ramping 13
Setting range Factory setting
0 ... 99 min 0 min
Reference ramping is the time in which the flow
temperature reference increases slowly to avoid load peaks
in the supply.
In order to avoid load peaks in the supply network, the flow
temperature reference can be set to increase slowly after a
period with setback temperature. This causes the valve to
open slowly.
Boost 123
Setting range Factory setting
0 ... 99% 0%
The boost shortens the heating-up period by increasing the
flow temperature by the percentage you set.
In order to shorten the heating-up period after a setback
temperature period, the flow temperature reference can be
increased temporarily (max 1 hour). At optimizing the boost
period is limited according to the calculated pre-comfort
period.
If a room temperature sensor is connected, the boost stops
when the room temperature is reached.
The boost also stops at the end of an optimizing period.
12 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
-- DHW priority --
Deviation 43
Setting range Factory setting
0 ... 40 K 5 K
Choose whether the heating circuit is to operate in
dependence of the DHW circuit.
Dependent parallel operation, i.e. the desired heating
temperature depends on the heat demand for hot water.
Choose how much the DHW temperature can fall before the
desired heating temperature has to be decreased.
Temp. ˚C
De
viation
Desired DHW
temp.
Ac
tual
DHW temp.
Low
est
acceptable
DHW temp.
100%
parallel
operation
Pa
rallel operation
with decreased
heating temp.
Time
If the actual DHW temperature deviates more than the set
value, the motorized control valve for the heating circuit
will close to such an extent that the DHW temperature
stabilizes at the lowest acceptable value.
Time constant ?
Setting range Factory setting
0 ... 1000 s 0 s
Set the integration time for the DHW priority.
When the value is set to 0, the function is OFF. At a low value,
the reaction is fast and when set to a high value, the reaction
is slow.
Master circuit ?
Setting range Factory setting
None / Circuit 1 ... 5 None
Choose the DHW circuit that must have priority.
-- Return temp. limitation --
This limitation is based on a PI regulation where P
(influence) responds quickly to deviations and I (time
constant) responds slower and over time removes the small
offsets between the reference and actual measured values.
This is done by changing the flow temperature reference.
?
Return temp. reference
Readout value
°C
Is only displayed if ‘Return temperature’ sensor is selected.
Setpoint 30
Setting range Factory setting
10 ... 110 °C 50 °C
Can only be set if ‘Return temperature’ sensor is selected.
When the return temperature falls below or gets higher
than the set value, the controller automatically changes the
desired flow temperature to obtain an acceptable return
temperature.
The return temperature limitation for the heating circuit
is based on the outdoor temperature. If no outdoor
temperature sensor is connected, the temperature used in
the calculation is 0 °C. When the outdoor temperature drops,
a higher return temperature typically is accepted.
The relationship between the return temperature limits and
outdoor temperature is set in two coordinates.
The upper limit coordinates are set in X2 and Y2 and the
lower limit coordinates in X1 and Y1.
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 13
Technical manual ECL Apex 10, control parameters and functions
80
60
40
20
-15 0 +15
T
out
T
return
Lo
w outdoor
temp. (X1)
High outdoor
temp. (X2)
Upper limit
(Y2)
Low
er limit
(Y1)
Low outdoor temp. (X1) 33
Setting range Factory setting
-45 ... 15 °C -15 °C
Can only be set if ‘Return temperature’ sensor are selected.
Lower limit (Y1) 34
Setting range Factory setting
10.0 ... 110.0 °C 60.0 °C
Can only be set if ‘Return temperature’ sensor are selected.
High outdoor temp. (X2) 31
Setting range Factory setting
-45 ... 15 °C 15 °C
Can only be set if ‘Return temperature’ sensor are selected.
Upper limit (Y2) 32
Setting range Factory setting
10.0 ... 110.0 °C 40.0 °C
Can only be set if ‘Return temperature’ sensor is selected.
Influence - max 35
Setting range Factory setting
-9.0 ... 9.0 -0.4
Can only be set if ‘Return temperature’ sensor is selected.
Set the influence of the max return temperature limitation.
Influence higher than 0:
The flow temperature reference is increased, when the
return temperature gets higher than the set limit.
Influence lower than 0:
The flow temperature reference is decreased, when the
return temperature gets higher than the set limit.
Influence
Influence - max > 0
Influence - max < 0
Return temp. reference Return temp.
0
Influence - min 36
Setting range Factory setting
-9.0 ... 9.0 0.0
Can only be set if ‘Return temperature’ sensor is selected.
Set the influence of the min return temperature limitation.
Influence higher than 0:
The flow temperature reference is increased, when the
return temperature gets below the set limit.
Influence lower than 0:
The flow temperature reference is decreased, when the
return temperature falls below the set limit.
0
Influence
Influence - min > 0
Influence - min < 0
Return temp. reference
Return temp.
14 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
Time constant 37
Setting range Factory setting
5 ... 4000 s 50 s
Can only be set if ‘Return temperature’ sensor is selected.
Controls how fast the actual return temperature adapts to
the return temperature reference.
Adjust the time constant for the return temp. limitation. The
setting will eliminate the difference between the acceptable
and the actual return temperature. The difference is
integrated to adjust the flow temperature reference.
When the value is set to 4000 s the I attibution is OFF.
When the value is set to 0, the function is OFF. At a low value,
the reaction is fast and when set to a high value, the reaction
is slow.
Min ref. ?
Setting range Factory setting
10 ... 150 °C 10 °C
Can only be set if ‘Return temperature’ sensor is selected.
The return temp. limitation cannot influence the calculated
flow temperature reference to values lower than min ref.
-- Energy limitation --
This limitation is based on a I regulation where I (time
constant) over time removes the small offsets between
the reference and actual measured values. This is done by
changing the flow temperature reference.
?
Actual value
Readout value
X.X
Is only displayed if ‘Energy’ sensor is selected.
?
Energy reference
Readout value
X.X
Is only displayed if ‘Energy’ sensor is selected.
?
Unit
Readout value
W, kW, MW, GW
Is only displayed if ‘Energy’ sensor is selected.
The units are determined in ‘General input setup - Analog
inputs’.
Setpoint 37
Setting range Factory setting
0 ... 30000 30000
Can only be set if ‘Energy’ sensor is selected.
When the energy consumption exceeds the setpoint, the
calculated flow temperature reference in the DHW circuit is
decreased.
The energy limitation for the heating circuit is based on the
outdoor temperature. If no outdoor temperature sensor is
connected, the temperature used in the calculation is
0 °C. When the outdoor temperature drops, a higher energy
consumption typically is accepted.
The relationship between the energy limits and outdoor
temperature is set in two coordinates.
The upper limit coordinates are set in X2 and Y2 and the
lower limit coordinates in X1 and Y1.
The below units are determined in ‘General input setup
- Analog inputs’.
Low outdoor temp. (X1) ?
Setting range Factory setting
-45 ... 15 °C -30 °C
Can only be set if ‘Energy’ sensor is selected.
Lower limit (Y1) ?
Setting range Factory setting
0.0 ... 100000.0 999.0
Can only be set if ‘Energy’ sensor is selected.
DH-SMT VI.JD.Z1.02 © Danfoss 11/2004 15
Technical manual ECL Apex 10, control parameters and functions
High outdoor temp. (X2) ?
Setting range Factory setting
-45 ... 15 °C 0 °C
Can only be set if ‘Energy’ sensor is selected.
Upper limit (Y2) ?
Setting range Factory setting
0.0 ... 100000.0 999.0
Can only be set if ‘Energy’ sensor is selected.
T
out
Unit
Lo
w outdoor
temp. (X1)
High outdoor
temp. (X2)
Upper limit
(Y2)
Low
er limit
(Y1)
Time constant ?
Setting range Factory setting
0 ... 1000 s 10 s
Can only be set if ‘Energy’ sensor is selected.
Controls how fast the actual energy consumption adapts to
the max energy reference.
Adjust the time constant for the energy limitation. The
setting will eliminate the difference between the acceptable
and the actual energy consumption. The difference is
integrated to adjust the flow temperature reference.
When the value is set to 0, the function is OFF. At a low value,
the reaction is fast and when set to a high value, the reaction
is slow.
-- Flow limitation --
The limitation is based on a I regulation where I (time
constant) over time removes the small offsets between
reference and actual measured values. This is done by
changing the flow temperature reference.
?
Actual primary flow
Readout value
X.X
Is only displayed if ‘Primary flow’ sensor is selected.
?
Primary flow ref.
Readout value
X.X
Is only displayed if ‘Primary flow’ sensor is selected.
?
Unit
Readout value
l/s, m
3
/s, l/min, m
3
/min,
l/h, m
3
/h
Is only displayed if ‘Primary flow’ sensor is selected.
The units are determined in ‘General setup - Analog inputs’.
Setpoint ?
Setting range Factory setting
0 ... 30000 30000
Can only be set if ‘Primary flow’ sensor is selected.
Set the max allowed flow for the DHW circuit.
When the energy consumption exceeds the setpoint, the
calculated flow temperature reference in the DHW circuit is
decreased.
The flow limitation for the heating circuit is based on the
outdoor temperature. If no outdoor temperature sensor is
connected, the temperature used in the calculation is
0 °C. When the outdoor temperature drops, a higher flow
limitation typically is accepted.
The relationship between the flow limits and outdoor
temperature is set in two coordinates.
The upper limit coordinates are set in X2 and Y2 and the
lower limit coordinates in X1 and Y1.
16 VI.JD.Z1.02 © Danfoss 11/2004 DH-SMT
Technical manual ECL Apex 10, control parameters and functions
The below units are determined in ‘General input setup
- Analog inputs’.
T
out
Unit
Lo
w outdoor
temp. (X1)
High outdoor
temp. (X2)
Upper limit
(Y2)
Low
er limit
(Y1)
Low outdoor temp. (X1) ?
Setting range Factory setting
-45 ... 15 °C -30 °C
Can only be set if ‘Primary flow’ sensor is selected.
Lower limit (Y1) ?
Setting range Factory setting
0.0 ... 100000.0 999.0
Can only be set if ‘Primary flow’ sensor is selected.
High outdoor temp. (X2) ?
Setting range Factory setting
-45 ... 15 °C 0 °C
Can only be set if ‘Primary flow’ sensor is selected.
Upper limit (Y2) ?
Setting range Factory setting
0.0 ... 100000.0 999.0
Can only be set if ‘Primary flow’ sensor is selected.
Time constant ?
Setting range Factory setting
0 ... 1000 s 10 s
Can only be set if ‘Primary flow’ sensor is selected.
Controls how fast the actual flow adapts to the max flow
reference.
Adjust the time constant for the flow limitation. The setting
will eliminate the difference between the acceptable and
the actual flow. The difference is integrated to adjust the
flow temperature reference.
When the value is set to 0, the function is OFF. At a low value,
the reaction is fast and when set to a high value, the reaction
is slow.
-- Anti bacteria function --
The DHW will be charged according to schedule at the set
temperature to protect against bacteria.
Setpoint ?
Setting range Factory setting
10 ... 150 °C 70 °C
Can only be set if ‘Anti bacteria‘ is active.
The Anti bacteria schedule can be activated in the
‘Schedule setup’
-- Universal influence --
This limitation is based on a PI regulation where P
(influence) responds quickly to deviations and I (time
constant) responds slower and over time removes the small
offsets between the reference and actual measured values.
This is done by changing the flow temperature reference.
How the universal influence operates depends on type of
sensor connected to the input. This function is very flexible
and is only used for very special applications.
The universal influence allows you to modify the flow
temperature reference based on any sensor type connected
to the ECL Apex 10, e.g. temperature, pressure or analog
inputs. If the measured value deviates from the user-defined
setpoint, the flow temperature could be increased or
decreased.
?
Actual input (%)
Readout value
%
Is only displayed if ‘Universal limiter, PI’ and ‘Analog’ are
selected.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Danfoss ECL Apex 10 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI