Danfoss ECL Apex 10 User guide

Type
User guide
VI.JE.M1.02 © Danfoss 11/2004 DH-SMT VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
*087R9745*
*vijeM102*
User Guide
ECL Apex 10
Installation and configuration
VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10 ECL Apex 10
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 1
ECL Apex 10
Table of Contents
Mounting and wiring ...................................................................4
Mounting of an analog output extension module .................................... 4
Mounting of an additional I/O module .......................................................... 5
Wiring ......................................................................................................................... 6
Connect service tool ............................................................................................. 8
Login with user name SUPV ............................................................................... 8
Configuration ...............................................................................8
Change language .................................................................................................. 9
Unlock the configuration of the controller ................................................. 11
System setup ......................................................................................................... 12
Set application type ............................................................................................ 13
Your wiring notes! ............................................................................................... 17
Configuration of inputs and outputs ........................................................... 18
Schedule setup .....................................................................................................22
Lock and check configuration .........................................................................23
Reference control ................................................................................................. 24
Sensor filter and offset ....................................................................................... 25
Thermostats etc. ...................................................................................................25
Alarm priorities ..................................................................................................... 26
Backup / restore ................................................................................................... 27
I/O status and manual ...............................................................28
Overview ....................................................................................30
Schedule .....................................................................................32
Alarm ..........................................................................................33
Log ..............................................................................................34
First start of the controller ........................................................36
Check alarms .........................................................................................................36
Start the controller .............................................................................................. 37
2 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Before you start
1. Make a drawing of your system application
2. Select your inputs and outputs - and write down what you have chosen
3. Configure the controller
How to use these instructions
These instructions describe how the Danfoss district heating controller
ECL Apex 10 is set up.
Heating system example
In this user guide we describe the setup by means of an example comprising a
weather compensated heating circuit and a domestic hot-water (DHW) circuit.
Please note that the system diagrams in this instruction are principle drawings
and they do not contain all components that are necessary in your system.
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 3
ECL Apex 10
The heating supply is provided with a strainer and a differential pressure
switch / filter guard (DI1), as well as sensors to monitor primary temperature
(ST2) and pressure (SP1).
The heating circuit consists of a motorized control valve (M1), a heat exchanger
with flow (ST3) and return (ST4) temperature sensors, two sequentially
controlled pumps (P1 and P2) with flow (SP2) and return (SP3) pressure
transmitters. The heating circuit as such is weather compensated by means of
the outdoor temperature sensor (ST1).
The DHW comprises a motorized control valve (M2), a heat exchanger with flow
(ST5) and return (ST6) temperature sensors, one set of twin-pump controlled
pumps (P3 and P4) supervised by a differential pressure switch (DI2).
Fig. 1: Heating system example used in this user guide
Mounting and wiring
Mounting of an analog output extension module
1. Disconnect the ECL Apex 10 from the mains supply.
2. Remove the processing unit from the base part by pressing in the plates on
both sides.
3. Mount the extension module in the base part.
4. Remount the processing unit on the base part.
4 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Mounting of an additional I/O module
1. Move the protective cap from the ECL Apex 10 to the I/O module.
Remove the protective cap
from the connection plug on
the right-hand side of the base
part.
Place the cap on the connection
plug of the I/O module, which is
to be mounted on the far right-
hand side of the array.
2. Assemble the I/O module and the ECL Apex 10.
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 5
ECL Apex 10
6 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Example of electrical connections
1
Outdoor temp. sensor (ST1)
7 Flow pressure, primary (SP1)
6 Return temp. sensor, DHW (ST6)
5 Flow temp. sensor, DHW (ST5)
4
Return temp. sensor, heating (ST4)
3
Flow temp. sensor, heating (ST3)
2 Flow temp. sensor, primary (ST2)
11
Diff. pressure switch, DHW (DI2)
10 Diff. pressure switch, primary (DI1)
9
Return pressure, heating (SP3)
8
Flow pressure, heating (SP2)
12
Mot. control valve open, heating (M1)
13
Mot. control valve close, heating (M1)
14
Mot. control valve open, DHW (M2)
16 Circulation pump 1, heating (P1)
18
Circulation pump 1, DHW (P3)
19
Circulation pump 2, DHW (P4)
17
Circulation pump 2, heating (P2)
15 Mot. control valve close, DHW (M2)
Module (Mod)
Points (Pt)
Points (Pt)


 
 
 
 



 






Wiring
Light emitting diodes
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 7
ECL Apex 10
Table 2: Wiring of digital outputs
Load Output Module Point Active at
Motorized control valve open, heating (M1) DO1 1 12 Normal
Motorized control valve close, heating (M1) DO2 1 13 Normal
Motorized control valve open, DHW (M2) DO3 1 14 Normal
Motorized control valve close, DHW (M2) DO4 1 15 Normal
Circulation pump 1, heating (P1) DO5 1 16 NO
Circulation pump 2, heating (P2) DO6 1 17 NO
Circulation pump 1, DHW (P3) DO7 1 18 NO
Circulation pump 2, DHW (P4) DO8 1 19 NO
NO = Normally Open
NC = Normally Closed
Table 1: Wiring of analog inputs
Sensor Input Module Point Type
Outdoor temperature sensor (ST1) AI1 1 1 Pt 1000
Flow temperature sensor, primary (ST2) AI2 1 2 Pt 1000
Flow temperature sensor, heating (ST3) AI3 1 3 Pt 1000
Return temperature sensor, heating (ST4) AI4 1 4 Pt 1000
Flow temperature sensor, DHW (ST5) AI5 1 5 Pt 1000
Return temperature sensor, DHW (ST6) AI6 1 6 Pt 1000
Flow pressure, primary (SP1) AI7 1 7
User-
defined
Flow pressure, heating (SP2) AI8 1 8 AKS32-12
Return pressure, heating (SP3) AI9 1 9 AKS32-12
Differential pressure switch, primary (DI1) AI10 1 10 Normal
Differential pressure switch, DHW (DI2) AI11 1 11 Normal
Connect service tool
The service tool is connected to the
controller by placing the plug from
the PC or PDA into the service tool
socket on the controller.
The controller has to be switched
ON before the service tool program
is started.
The first time the service tool is connected to a new controller version, the
start-up of the service tool will take longer than usual.
Login with user name SUPV
To change the controller
configuration you have logon as
SUPV (supervisor) and enter the
belonging access code.
On delivery the controller is
supplied with the access code 123.
8 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Configuration
When you are logged on to
the controller, you will get this
overview. Normally it will be empty
until one or more circuits have
been configured. It will always be
possible to return to the overview
by pressing the button at the
bottom left.
If there is a red bell at the bottom
right, it tells you that there is an
active alarm.
Change language
On delivery the language of the service tool display is English. Follow this
procedure to change the language:
1. Go to the configuration menu
Press the orange setup button with the screw spanner at the bottom of the
display
2. Select Authorization
Press the line Authorization to
get to the user setup display.
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 9
ECL Apex 10
3. Change the settings for the user SUPV
Mark the line with the user name
SUPV.
Press the button Change.
4. Choose language
Press the OK button to save the
new settings.
5. Carry out a new login with the user name SUPV
To activate the chosen language,
it is necessary to carry out a new
login as SUPV. Press the padlock at
the top left corner of the display to
login again.
10 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Unlock the configuration of the controller
The controller must be stopped and unlocked in order to change the
configuration.
1. Go to the Configuration menu
2. Select Lock/unlock configuration
Press the line Lock/unlock
configuration.
3. Select Configuration lock
Press the field with the text
Locked.
4. Select Unlocked
Selected Unlocked and press
OK.
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 11
ECL Apex 10
System setup
1. Go to the Configuration menu
2. Choose System and clock setup
Press the line System and clock
setup.
You have to set the time and
date in order to activate the
control functions.
3. Set system settings
Controller name and Mains
frequency can be changed by
pressing the field and then entering
the new settings.
Set time and date by pressing
the field Year and then enter
the correct data incl. the desired
daylight saving time changeover
setting.
12 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Set application type
From factory the controller is not configured and the entire system must
be set up to cover the demands of the actual system. The choices you make
now will help you by limiting your possible choices later in the configuration
procedure.
1. Go to the Configuration menu
2. Select Application configuration
The number of submenus
will adapt itself so that only
relevant submenus are visible.
3. Choose the function of your circuit(s)
Choose the type of each circuit,
i.e. heating or DHW.
At reconfiguration, reset all
inputs and outputs before you
define the new configuration.
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 13
ECL Apex 10
4. Choose Control strategy (heating circuits only)
Constant temp. =
Constant temperature control (no
weather compensation)
6-pt weather comp. =
Weather compensation according
to a heat curve with 6 points
Std w.comp. + room T =
Standard weather compensation +
room temperature control
6-pt w.comp. + room T =
Weather compensation according
to a heat curve with 6 points +
room temperature control.
5. Select PI(D) type (heating as well as DHW circuits)
3-pt PI =
PI control, 3-point
(recommended)
0-10 V, PID =
PID control, 0-10 V
(requires ECA-OB 003A)
3-pt PID =
PID control, 3-point
14 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
6. Set Input type (heating circuits only)
Choose whether you want to
control the temperature in the
flow or as an average of the flow
and return temperatures
Flow temp. =
Flow temperature
Avg. temp. =
Average temperature
(flow temperature + return
temperature) / 2
7. Set Pump strategy (heating as well as DHW circuits)
Sequence =
Sequence controlled pumps
PID (0-10 V) =
PID controlled pump, 0-10 V
Twin pump =
Two pump control
Std controller =
Standard one pump control
Depending on chosen Pump
strategy, choose
- No. of pumps
- Pressure type
Pressure control (sensors)
Diff. pressure control (switch)
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 15
ECL Apex 10
8. Select Makeup water (heating circuit only)
ON/OFF =
ON/OFF controlled makeup pump
PID (0-10 V) =
PID controlled makeup pump
Depending on chosen Makeup
water type, choose
- No. of pumps
- Makeup pressure
Analog or Digital (sensor(s))
9. Set Universal limiter (heating as well as DHW circuits)
Analog =
Analog controlled limiter
Temperature =
Temperature controlled limiter
Pressure =
Pressure controlled limiter
This limiter is for special
applications only, e.g. for
limiting the flow temperature
based on the primary supply
temperature.
16 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
Your wiring notes!
Configuration of inputs and outputs!
Wiring of analog inputs (AI)
Sensor Input Mod. Pt Terminals Type
Wiring of digital outputs (DO)
Load Output Mod. Pt Terminals Active
at
DH-SMT VI.JE.M1.02 © Danfoss 11/2004 17
ECL Apex 10
Configuration of inputs and outputs
According to heating system example fig. 1
1. Go to the Configuration menu
2. Select Input and output setup
3. Select Application input selection
Select sensors according to your
wiring table on the previous page.
When finished go back to
I/O setup.
18 VI.JE.M1.02 © Danfoss 11/2004 DH-SMT
ECL Apex 10
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39