SPX Cooling Technologies Recold Maintenance Checklist Owner's manual

Type
Owner's manual
Procedure Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Clean Basin
(Monthly)
Check Operating
Water Level
(As Required)
Check Water Distribution
(Quarterly)
Check Belt Tension
(Monthly)
Clean Air Inlet Screens
(As Required)
Lubricate Fan
Shaft Bearings
(Every 3 Months)
Clean and Touch Up
Protective Finish
(Once a Year)
Flush Out
Spray Headers
(Once a Year)
Check Bleed-Valve
Setting
(Weekly)
Inspect general operating condition of the unit weekly by checking for unusual vibration, sound or feel (such as an overheated motor), and proper bleed-valve setting.
MAINTENANCE CHECK LIST
Cooling Tower Cleaning:
Any evaporative-type cooling tower must be thoroughly cleaned on a regular
basis to minimize the growth of bacteria, including Legionella Pneumophila,
to avoid the risk of sickness or death. Service personnel must wear proper
personal protective equipment. Do NOT attempt any service unless the fan
motor is locked out.
WARNING Lubricant Recommendations
Mobil shc 460
Recold-1192
REV. E 2011
550 W MERCURY LANE | BREA, CALIFORNIA 92821 UNITED STATES | 714 529 6080 | [email protected]
| spxcooling.com