STARBUCKS N2Fusion User manual

Category
Coffee makers
Type
User manual
Service Manual
This manual is updated as new information and models are released. Visit our website for the latest manual.
www.manitowocfsg.com
Part Number 020007115 10/06/2016
N₂Fusion
Nitrogen Beverage Dispenser
Safety Notices
As you work on Manitowoc equipment, be sure to pay close
attention to the safety notices in this manual. Disregarding
the notices may lead to serious injury and/or damage to the
equipment.
Throughout this manual, you will see the following types of
safety notices:
n
Warning
Text in a Warning box alerts you to a potential personal
injury situation. Be sure to read the Warning statement
before proceeding, and work carefully.
,
Caution
Text in a Caution box alerts you to a situation in which
you could damage the equipment. Be sure to read
the Caution statement before proceeding, and work
carefully.
Procedural Notices
As you work on Manitowoc equipment, be sure to read the
procedural notices in this manual. These notices supply
helpful information which may assist you as you work.
Throughout this manual, you will see the following types of
procedural notices:
Important
Text in an Important box provides you with information
that may help you perform a procedure more efficiently.
Disregarding this information will not cause damage or
injury, but it may slow you down as you work.
NOTE: Text set off as a Note provides you with simple, but
useful, extra information about the procedure you are
performing.
Read These Before Proceeding
,
Caution
Proper installation, care and maintenance are
essential for maximum performance and trouble-free
operation of your equipment. Visit our website www.
manitowocfsg.com for manual updates, translations, or
contact information for service agents in your area.
Important
Routine adjustments and maintenance procedures
outlined in this manual are not covered by the warranty.
n
Warning
Read this manual thoroughly before operating, installing
or performing maintenance on the equipment. Failure
to follow instructions in this manual can cause property
damage, injury or death.
n
Warning
Do not use electrical appliances or accessories other
than those supplied by Manitowoc for your ice machine
model.
n
Warning
Two or more people or a lifting device are required to lift
this appliance.
n
Warning
This equipment contains high voltage electricity and
refrigerant charge. Installation and repairs are to be
performed by properly trained technicians aware of
the dangers of dealing with high voltage electricity and
refrigerant under pressure. The technician must also be
certified in proper refrigerant handling and servicing
procedures. All lockout and tag out procedures must be
followed when working on this equipment.
n
Warning
Do not damage the refrigeration circuit when installing,
maintaining or servicing the unit.
n
Warning
Do not operate equipment that has been misused,
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications. This
appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless
they have been given supervision concerning use of the
appliance by a person responsible for their safety. Do
not allow children to play with this appliance.
n
Warning
All covers and access panels must be in place and
properly secured, before operating this equipment.
n
Warning
Do not obstruct machine vents or openings.
n
Warning
Do not store gasoline or other flammable vapors or
liquids in the vicinity of this or any other appliance.
n
Warning
Do not clean with water jet.
n
Warning
It is the responsibility of the equipment owner to
perform a Personal Protective Equipment Hazard
Assessment to ensure adequate protection during
maintenance procedures.
n
Warning
When using electric appliances, basic precautions must
always be followed, including the following:
a. Read all the instructions before using the
appliance.
b. To reduce the risk of injury, close supervision
is necessary when an appliance is used near
children.
c. Do not contact moving parts.
d. Only use attachments recommended or sold by
the manufacturer.
e. Do not use outdoors.
f. For a cord-connected appliance, the following
must be included:
Do not unplug by pulling on cord. To unplug,
grasp the plug, not the cord.
Unplug from outlet when not in use and
before servicing or cleaning.
Do not operate any appliance with a
damaged cord or plug, or after the appliance
malfunctions or is dropped or damaged in
any manner. Contact the nearest authorized
service facility for examination, repair, or
electrical or mechanical adjustment.
g. Follow applicable lock out tag out procedures
before working on equipment.
h. Connect to a properly grounded outlet only.
THIS PAGE INTENTIONALLY LEFT BLANK
Table of Contents
Part Number 020007115 10/06/2016 5
Section 1
General Information
Model Numbers .................................................................................................................. 9
Model Nomenclature: ..........................................................................................................................9
About N₂Fusion™ ................................................................................................................ 9
Serial Number Location .....................................................................................................9
Specifications ...................................................................................................................10
Dimensions ............................................................................................................................................ 10
Capacity & Weight ............................................................................................................................... 10
Product Delivery Location ................................................................................................................ 11
Refrigerant Charge .............................................................................................................................. 11
Electrical ................................................................................................................................................. 12
System Pressures ................................................................................................................................. 13
Section 2
Installation
Step-by-Step Installation .................................................................................................15
Pre-installation Checklist .................................................................................................................. 15
Remote Tower Installation ............................................................................................................... 16
Nitrogen Regulator & Tank Assembly ..........................................................................................17
Nitrogen Installation/Replacement .............................................................................................. 18
Nitrogen Connections & Pressures ............................................................................................... 18
N
2
Quick Disconnect & Drain ........................................................................................................... 19
Keg & Pump Regulators ....................................................................................................................19
Keg Connections ................................................................................................................................. 21
Door Hinge Reversal........................................................................................................................... 22
Section 3
Operation
Product Dispense Operation ........................................................................................... 23
Prerequisites: .........................................................................................................................................23
Operation .............................................................................................................................................. 23
Taps & Nozzles ...................................................................................................................................... 23
Flow Control & Locking Collar ........................................................................................................ 24
Kegs .......................................................................................................................................................... 24
Keg Change ........................................................................................................................................... 24
Priming the System ............................................................................................................................ 25
Nitrogenator ......................................................................................................................................... 25
Refrigerated Cabinet Operation .....................................................................................26
In-Line Strainer ..................................................................................................................................... 26
6 Part Number 020007115 10/06/2016
Table of Contents (continued)
Section 4
Maintenance
General Maintenance ....................................................................................................... 27
Door Gasket Maintenance ............................................................................................................... 28
Drain Maintenance - Inside Lower Cabinet ................................................................................28
Refrigerators .......................................................................................................................................... 28
Stainless Steel Care & Cleaning ...................................................................................................... 28
Doors/Hinges ........................................................................................................................................ 29
Preventing Corrosion ......................................................................................................................... 29
Other Monthly Tasks ........................................................................................................................... 29
General Cleaning ................................................................................................................................. 29
Cleaning Supplies ............................................................................................................................... 30
Daily & Weekly Cleaning ................................................................................................................... 31
Extended Shutdown Procedure ......................................................................................32
Other Operations .............................................................................................................33
Doors/Hinges ........................................................................................................................................ 33
Section 5
Troubleshooting
Dispensing Issues ............................................................................................................................... 35
Dispensing Flowchart ....................................................................................................................... 36
Pouring ....................................................................................................................................................37
Coffee Dispense System....................................................................................................................37
Pump Flowchart.................................................................................................................................. 38
No Power Flowchart ........................................................................................................................... 39
Refrigerator Cabinet Issues ..............................................................................................................39
Refrigerated Cabinet Flowchart ..................................................................................................... 40
Cabinet Temperature Out of Range .............................................................................................. 41
High Product Temperature .............................................................................................................. 41
Refrigeration System Diagnostics ..................................................................................42
Refrigeration System Checklists ..................................................................................................... 42
Discharge Pressure High Checklist ................................................................................................ 42
Discharge Pressure Low Checklist ................................................................................................. 42
Suction Pressure High Checklist .................................................................................................... 42
Suction Pressure Low Checklist ...................................................................................................... 42
Section 6
Controls
Prime/Clean Button ..........................................................................................................43
Priming Mode ....................................................................................................................................... 43
Cleaning Mode ..................................................................................................................................... 44
Error Code ..............................................................................................................................................44
Refrigerated Cabinet ........................................................................................................44
Controls/Programming/Settings ................................................................................................... 44
Part Number 020007115 10/06/2016 7
Table of Contents (continued)
Section 7
Component Check Procedures
Component Identification ...............................................................................................45
External ................................................................................................................................................... 45
Power Supply ........................................................................................................................................46
High Pressure Cutout (HPCO) Control..........................................................................................46
Compressor Electrical Diagnostics ................................................................................................ 47
Diagnosing Start Components ....................................................................................................... 47
Compressor Electrical Diagnostics ................................................................................................ 48
Compressor Drawing Locked Rotor ..............................................................................................48
Diagnosing Capacitors ......................................................................................................................48
Filter-Driers ............................................................................................................................................ 49
System Contamination Clean-Up .................................................................................... 50
General .................................................................................................................................................... 50
Determining Severity Of Contamination ....................................................................................50
Cleanup Procedure ............................................................................................................................. 51
Replacing Pressure Controls ........................................................................................................... 52
Section 8
Charts
Total System Refrigerant Charge ....................................................................................53
Section 9
Diagrams
Wiring Diagram .................................................................................................................................... 55
Plumbing Diagram ..............................................................................................................................56
Programmable logic controller (PLC) State Diagrams ...........................................................57
THIS PAGE INTENTIONALLY LEFT BLANK
Part Number 020007115 10/06/2016 9
Model Numbers
This manual covers the following models:
MODEL NOMENCLATURE:
ND 2 1 T S 0 0
I II III IV V VI VII VIII
Dispenser Type
Number of
Taps
Towers
Tower
Mounting
Handle & Nozzle Cabinet Type Electrical & Refrigerant
Customer
Specific
ND = Nitro Dispenser
2 = Two
(one still,
one gas)
3 = Four
(one still,
three gas)
4 = Four
(two still,
two gas)
1 = Single
2 = Dual
3 = Dual Fonts *
4 = Four Fonts *
* Each Font Mounts 1 Tap
T = Top Mount
on Base
R = Remote
Counter Top
B = Black Plastic
S = Stainless Polished
C = Coffee Wood
Handle & Polished
Stainless Nozzle
0 = 406 Star
1 = BIM Base
2 = Global Under
Counter
3 = Slimwide
Cabinet
(SBX Gen 2)
0 = 115/60 - R404a
1 = 220/60 - R404a
2 = 230-240/50 R404a
3 = 100/60 - R404a
4 = 100/50 - R404a
5 = 115/60 - R290
6 = 220/60 - R290
7 = 230-240/50 R404a
8 = 100/60 - R290
9 = 100/50 - R290
A = Double
System
NC = Nitro Coffee
About N₂Fusion™
The N₂Fusion™ Nitrogen Beverage Dispenser is a self-
contained dispensing unit that allows the operator to
dispense chilled and/or nitrogenized drink combinations of
coffee. It holds product containers or kegs in a refrigerated
reach-in base enclosure.
The operator controls the product pour on the unit using
mechanical beer style taps. Drink size options are manually
controlled. Purging and cleaning are controlled through
and internal push button located in the upper left corner
of the refrigeration cabinet. A blue LED ring will illuminate
around the button to provide feedback to the user during
purge, cleaning, and/or errors.
Periodic software updates through the PLC on the rear
of the unit may be required for maintenance, additional
features, and/or improvements.
NOTE: These units are intended for indoor use.
Serial Number Location
The serial number on N
2
Fusion™ Nitrogen Beverage
Dispenser is printed on the left side of the interior wall.
Always have the serial number of your unit available
when calling for parts or service.
Sample Serial Tag
Section 1
General Information
10 Part Number 020007115 10/06/2016
General Information Section 1
Specifications
DIMENSIONS
A
C
D
B
E
F
G
H
I
Model A B C D E F G H I
ND21TS00
27.3”
(69cm)
34.0”
(86cm)
28.4”
(72cm)
20.7”
(53cm)
13.6”
(35cm)
16.1”
(41cm)
44.6”
(113cm)
10.6”
(27cm)
7.3”
(19cm)
ND21TS01
ND21TS02
ND21TS03
ND21TS04
ND21RS00 30.75”
(78cm) *
ND21RS02
* This dimension represents units using 1.25” (3.175cm) low profile casters, regular casters are 1.25” (3.175cm) taller.
n
Warning
To avoid instability the installation area must be
capable of supporting the weight of the equipment.
Additionally the equipment must be level side to side
and front to back.
CAPACITY & WEIGHT
Model Max Capacity Volume Weight
ND21TS00
3 - 3 Gallon (11.36L) Coffee Kegs 5.7Ft
3
(161L) 168lbs (76kg)
ND21TS01
ND21TS02
ND21TS03
ND21TS04
ND21RS00
ND21RS02
Part Number 020007115 10/06/2016 11
Section 1 General Information
PRODUCT DELIVERY LOCATION
n
Warning
This equipment must be positioned so that the plug is
accessible unless other means for disconnection from
the power supply (e.g., circuit breaker or disconnect
switch) is provided.
n
Warning
Adequate means must be provided to limit the
movement of this appliance without depending on or
transmitting stress to the electrical conduit or gas lines.
n
Warning
To avoid instability the installation area must be capable
of supporting the combined weight of the equipment
and product. Additionally the equipment must be level
side to side and front to back.
n
Warning
This equipment is intended for indoor use only. Do not
install or operate this equipment in outdoor areas.
n
Warning
Do not position the air intake vent near steam or heat
exhaust of another appliance.
The location selected for the equipment must meet the
following criteria. If any of these criteria are not met, select
another location.
Units are intended for indoor use only.
The location MUST be level both front to back and side to
side, stable and capable of supporting the weight of the
equipment.
Position the equipment so it will not tip or slide.
Recommended air temperature is 41° - 86°F (5° - 30°C), and
must not exceed 90°F (32°C), climate class 4.
Location must have proper ventilation, DO NOT install in an
enclosure/enclosed cabinet with no access to ambient air.
The location must not be near heat-generating equipment
or in direct sunlight and must be protected from weather.
Verify floor of install location is within 1/2” (1.3 cm) of level
front to back, side to side.
Keep equipment area clear of combustible material.
Do not install the equipment directly over a drain. Steam
rising up out of the drain will adversely affect operation, air
circulation, and damage electrical /electronic components
Do not install in an area where a high-pressure water jet
could be used for cleaning.
Clearances
DANGER
Minimum clearance requirements are the same for
noncombustible locations as for combustible locations.
The flooring under the appliance must be made of a
noncombustible material.
DANGER
Risk of fire/shock. All minimum clearances must be
maintained. Do not obstruct vents or openings..
Sides 0" (0 cm)
Back 3” (76mm)
Front 30" (76 cm)
n
Warning
Do not obstruct machine vents or openings this includes
installing in an enclosed cabinet where the unit will not
have access to ambient air.
Heat of Rejection
Model BTU/hr
ND21TS00
1430 (0.42 kW)
ND21TS01
ND21TS02
ND21TS03
ND21TS04
ND21RS00
ND21RS02
REFRIGERANT CHARGE
Important
Due to continuous improvements, this information is for
reference only. Please refer to the serial number tag to verify..
Model Type Refrigerant Charge
ND21TS00
R404A 7.0 oz (198g)
ND21TS01
ND21TS02
ND21TS03
ND21TS04
ND21RS00
ND21RS02
12 Part Number 020007115 10/06/2016
General Information Section 1
ELECTRICAL
DANGER
Check all wiring connections, including factory terminals,
before operation. Connections can become loose during
shipment and installation.
n
Warning
The machine must be wired and grounded in
accordance with national and local electrical codes.
Minimum Circuit Ampacity
The minimum circuit ampacity is used to help select the wire
size of the electrical supply. (Minimum circuit ampacity is not
the N2Fusion Systems running amp load.) The wire size (or
gauge) is also dependent upon location, materials used, length
of run, etc., it must be determined by a qualified electrician.
Voltage
A dedicated electrical circuit is required, a power cord is
provided with all units. Some models are available in different
voltages and may be equipped with a different plug.
The following precautions must be observed:
The equipment must be grounded.
A separate fuse/circuit breaker must be provided for
each unit.
A qualified electrician must determine proper wire size
dependent upon location, materials used and length
of run (minimum circuit ampacity can be used to help
select the wire size).
The maximum allowable voltage variation is ±10% of
the rated voltage at equipment start-up (when the
electrical load is highest).
Check all green ground screws, cables and wire
connections to verify they are tight before start-up.
Minimum Circuit Amperage Chart
Important
Due to continuous improvements, this information is for
reference only. Please refer to the serial number tag to verify..
Model Voltage/Cycle/Phase
Total
Amps
HP
Breaker
Size (Max)
ND21TS00
115/60/1 6.0 A
1/5 15 A
ND21RS00
ND21TS01 220/60/1 2.5 A
ND21TS02
220-230/50/1 2.5 A
ND21RS02
ND21TS03 100/60/1 6.0 A
ND21TS04 100/50/1 6.0 A
Preparing the power cord (International units only)
The following instructions cover the installation of a 220 VAC,
50/60 Hz (international) unit. An appropriate 3-wire power
receptacle must be located within 6 ft (1.8 m) of the unit. Unpack
the unit from its transportation packaging and visually check for
any signs of damage.
NOTE: Only use an approved plug for the country in which the
unit is being installed.
Important
The wires in the power cord/mains lead are colored in
accordance with the following code:
• Green / Yellow = Ground/Earth
• Blue = Neutral
• Brown = Line/Live
1. Locate a 3-terminal plug. This plug (not furnished with
unit) must have a ground-wire-connecting terminal.
2. Locate the loose end of the power cord attached to
the unit. All three (3) wires are stripped to 1/2” (1.3 cm)
length from the end.
3. Connect all three (3) wires to the plug using the
1/2” (1.3 cm) stripped ends or any other terminal
requirements. Different plugs and terminals may
require different stripped lengths.
4. Inspect the cord and plug connection for any loose or
bare wires.
Grounding Instructions
This appliance must be grounded/earthed. In the event
of malfunction or breakdown, grounding provides a
path of least resistance for electric current to reduce the
risk of electric shock. This appliance is equipped with a
cord having an equipment-grounding conductor and
a grounding plug. The plug must be plugged into an
appropriate outlet that is properly installed and grounded/
earthed in accordance with all local codes and ordinances.
Check with a qualified electrician or serviceman if the
grounding instructions are not completely understood or if
in doubt as to whether the product is properly grounded.
Do not modify the plug provided; if it will not fit the outlet,
have the proper outlet installed by a qualified electrician.
Do not use an extension cord or an adapter plug with this
equipment.
NOTE: For 220-240 VAC, 50/60 Hz International Units, a
ground male plug must be supplied at the installation of
the unit.
Part Number 020007115 10/06/2016 13
Section 1 General Information
n
Warning
When using electric appliances, basic precautions must
always be followed, including the following:
A. Read all the instructions before using the
appliance.
B. To reduce the risk of injury, close supervision
is necessary when an appliance is used near
children.
C. Do not contact moving parts.
D. Only use attachments recommended or sold by
the manufacturer.
E. Do not use outdoors.
F. For a cord-connected appliance, the following
must be included:
Do not unplug by pulling on cord. To unplug,
grasp the plug, not the cord.
Unplug from outlet when not in use and
before servicing or cleaning.
Do not operate any appliance with a
damaged cord or plug, or after the appliance
malfunctions or is dropped or damaged in
any manner. Contact the nearest authorized
service facility for examination, repair, or
electrical or mechanical adjustment.
G. Follow applicable lock out tag out procedures
before working on equipment.
H. Connect to a properly grounded outlet only. See
Grounding Instructions.
SYSTEM PRESSURES
Supply to the Unit
n
Warning
Do Not exceed 90 psi (.621 MPa, 621 kPa, 6.21 bar) to
the unit! Excessive pressure to the unit may cause failure
and damage to the unit.
This table shows the Minimum / Maximum supply Nitrogen
required for each regulator at no flow conditions.
MINIMUM MAXIMUM
N₂
Supply
Primary
Regulator
85 psi
(.586 MPa , 586 kPa, 5.86 bar)
90 psi
(.621 MPa , 621 kPa, 6.21 bar)
Unit
Regulator 1
Keg
16 psi +/- 2 psi
(.110 MPa, 110 kPa, 1.10 bar)
Unit
Regulator 2
Pump
34 psi +/- 2 psi
(.234 MPa, 234 kPa, 2.34 bar)
14 Part Number 020007115 10/06/2016
General Information Section 1
THIS PAGE INTENTIONALLY LEFT BLANK
Part Number 020007115 10/06/2016 15
Step-by-Step Installation
These instructions are provided to assist the qualified installer. Contact your Manitowoc Foodservice Service Agent or call
Manitowoc Foodservice for information regarding start-up services.
DANGER
Use appropriate safety equipment during installation
and servicing.
DANGER
Installation must comply with all applicable fire and
health codes in your jurisdiction.
n
Warning
Remove all removable panels before lifting and installing.
n
Warning
Do not damage the refrigeration circuit when installing,
maintaining or servicing the unit.
Important
All plumbing must conform to local, state and national
codes.
Important
Failure to follow these installation guidelines may affect
warranty coverage.
PREINSTALLATION CHECKLIST
Any damage should be noted and reported to the
delivering carrier immediately.
Check the lower portion of the unit to be sure
casters are not bent.
Visually inspect the refrigeration package,
compressor compartment housing. Be sure lines
are secure and base is still intact.
Inspect installation location behind the unit for
electrical outlet location and Nitrogen (N
2
).
Power unit up by plugging into power source.
Check for correct voltage at outlet dedicated for
the Nitrogen Beverage Dispenser.
Verify floor of install location is within 1/2” (1.3 cm)
of level front to back, side to side and all casters are
touching the floor.
n
Warning
The mass of this appliance will allow it to move
uncontrolled on an inclined surface. Adequate means
must be provided to prevent uncontrolled movement
at all times.
Check that internal connections are secure and did
not vibrate loose during shipment.
Installation location has proper ventilation where
unit has access to ambient air.
Section 2
Installation
16 Part Number 020007115 10/06/2016
Installation Section 2
REMOTE TOWER INSTALLATION
These instructions are only for units that require remote
placement of the dispensing tower. If this is a self contained
unit with out remote setup continue to “Nitrogen Regulator
& Tank Assembly on page 17.
Checklist
Tower location should be no more than 20.70in
(53cm) from edge of the counter.
Mount tower within 6 linear ft (1.83m) from side of
base cabinet.
Make sure location has space for the drip tray
shipped with the unit.
NOTE: Drip trays equipped with a drain are also available
but are not standard equipment.
Location
1. Identify the counter top location for the tower making
sure there is room for the drip tray, conduit routing
under the counter, and is away from any heat source.
Important
If the drip tray is equipped with a drain make sure install
location is near a floor drain.
2. Using the provided counter top template mark where
the 2in (5cm) conduit and tower mount screw holes will
be drilled.
3. Cut and drill holes in the counter using the markings.
NOTE: Drip trays equipped with a drain will need a ⁄” (2.22cm)
hole drilled into the counter using the provided template for
routing to a floor drain.
Mounting & Routing
Important
Make sure the rubber counter top gasket is in place on
the tower before routing conduit and mounting tower.
To Cabinet
TAP #1
Plain
TAP #2
Nitro/Gas
4. Route conduit from the tower down through the 2in
(5cm) hole and mount the tower to the counter top
with the provided plate and screws.
NOTE: Make sure the rubber gasket is properly seated on
the tower and seals to the counter top.
5. Run the conduit from the tower to the N2Fusion™ cabinet.
6. Remove the two (2) screws from the solenoid cover
mounted to the inside top of the cabinet to gain access
to solenoids 1 and 2.
7. Route tubing through the top of the cabinet and attach
to the corresponding solenoids.
NOTE: Tubing already routed to the solenoids in the cabinet
should be marked with yellow 1 & 2 stickers.
n
Warning
Do not add line to the conduit this can cause poor drink
quality and the unit may not perform properly.
Part Number 020007115 10/06/2016 17
Section 2 Installation
Important
Allow four (4)ft (1.22m) of tubing for a service loop to
allow the cabinet to be pulled out during service and
cleaning. Cut off extra tubing if needed.
8. Once connections have been made put the solenoid
cover back into place.
Drip tray
9. Place drip tray or drain pan in proper location lined up
below the dispensing taps.
Important
Drip trays equipped with a drain need to be sealed to
the counter top, be sure to follow all local codes.
NITROGEN REGULATOR & TANK ASSEMBLY
DANGER
Tank under high pressure. Do not drop or allow tank to
fall over. Tank must be chained and secured to prevent
movement as per OSHA requirements. Do not attempt to
handle or connect to tank unless properly trained.
Nitrogen cylinders contain high-pressure gas which can
be hazardous if not handled properly. Make sure you READ
and UNDERSTAND the following procedures for nitrogen
cylinders BEFORE installation.
Important
Use only food grade nitrogen (99.5% pure).
1. ALWAYS connect the nitrogen cylinder to the primary
regulator and NEVER directly to the unit, keg, or
dispensing system. Failure to do so could result in an
explosion with possible death or injury when the cylinder
valve is opened.
2. ALWAYS follow correct procedures when cylinders are
changed.
3. ALWAYS secure the cylinder in an upright position with a
chain.
4. NEVER drop or throw a nitrogen cylinder.
5. ALWAYS keep a nitrogen cylinder away from heat. Store
extra cylinders in a cool place (preferably 70ºF). Securely
fasten with a chain in an upright position when storing.
6. ALWAYS check the D.O.T. test date on the cylinder neck
before installation. Ask your gas supplier for D.O.T. test
requirements.
7. NEVER connect a product container unless there is a safety
in the pressure system at or on the nitrogen regulator.
18 Part Number 020007115 10/06/2016
Installation Section 2
NITROGEN INSTALLATION/REPLACEMENT
NOTE: During initial installation of the unit a bracket for the
nitrogen cylinder must be installed to solid wall nearby and
a chain used to secure it to the bracket.
n
Warning
Verify gauge orientation
before setting pressures!
C
E
B
D
A
NITROGEN
NITROGEN
INTEGRAL SAFETY
DEVICE
TO PRODUCT
CONTAINER
100
1500
bar
200
R
U
L
LEFT
USE NO OIL
500
psi
3000
2500
150
1000
2000
50
8
120
psi
140
10
6
80
4
40
60
160
100
2
bar
LR
R
20
1. Make sure cylinder valve A is closed.
2. Unscrew (counter clockwise) regulator key “B” as far out
as it will go. (The regulator is now in the off position).
3. Remove regulator from empty cylinder at “D.
4. Remove dust cap from new cylinder at “D”. Open and
close valve A quickly to blow dust from outlet.
5. With cylinder valve A in closed position, re-attach
regulator to cylinder at “D”.
6. Open valve A all the way. (This is important because
this cylinder valve seals in two places).
7. Screw regulator key “B” in (clockwise) until required
pressure is reached “E”.
NOTE: Drinks will not pour if outlet valve A is closed.
NITROGEN CONNECTIONS & PRESSURES
1. Set inlet from food grade nitrogen tank to back of the
dispenser to 85 - 90 psi
(.586 - .621 MPa, 586 - 621 kPa, 5.86 - 6.21 bar).
Line OUT
Pressure to Unit
Line IN
N Tank Pressure
n
Warning
Line Out Pressure
Do Not exceed 90 psi
(.621 MPa, 621 kPa, 6.21 bar)
to the unit!
Part Number 020007115 10/06/2016 19
Section 2 Installation
N
2
QUICK DISCONNECT & DRAIN
,
Caution
Installer should always check the locking collars on the taps
are tight prior to connecting the Nitrogen supply line. If
these collars are loose they can leak at the tower shank when
pressurized.
Flow
Control
Locking
Collar
Important
All plumbing must conform to local, state and national codes.
2. Hook up nitrogen supply line to quick disconnect.
3. Run drip pan drain line and purge tube to floor drain.
N
2
Supply
Connection
Drain Line
Floor Drain
N
2
Purge Tube
2" Air Gap
NOTE: Purge tube releases under pressure, make sure it is
fastened down.
4. Ensure drain line is not kinked or otherwise blocked for
proper drainage.
KEG & PUMP REGULATORS
5. Once the nitrogen line is hooked up to the unit check the
pressures on the two (2) regulators located in the back of
the unit.
Regulator 1
Keg
Regulator 2
Nitrogenator
6. Verify the following pressures;
MINIMUM MAXIMUM
Unit
Regulator 1
Keg
16 psi +/- 2 psi
(.110 MPa, 110 kPa, 1.10 bar)
Unit
Regulator 2
Pump
34 psi +/- 2 psi
(.234 MPa, 234 kPa, 2.34 bar)
7. If adjustment is required proceed to “Regulator
Adjustment Procedure” on page 20, if no ajustment is
needed proceed to “” on page 20
20 Part Number 020007115 10/06/2016
Installation Section 2
Regulator Adjustment Procedure
DANGER
ELECTRICAL SHOCK HAZARD! The power supply is located
in the upper right behind the cover and has live heat sinks.
Unplug from power source when removing cover..
8. Unplug the unit from its power source.
9. Remove the rear panel to gain access to the regulators.
Regulator 1
Keg
Regulator 2
Nitrogenator
Shown with Rear Panel Removed
10. Unlock each regulator by pulling up on the yellow lock
ring and set to zero by turning the adjustment knob
counter clockwise.
11. Pull the keg pressure relief valve, then the nitrogenator
PRV until hissing stops and all pressure has been
relieved from the system.
12. Set each regulator by slowly turning the adjustment
knob clockwise to increase the pressure.
Important
If the target pressure is missed and the regulator pressure
is too high, start over. Set the regulator back to zero then
relieve all system pressure from the keg and nitrogenator.
(See Step 11)
A. Set Regulator 1- Nitrogen Tank to Coffee Keg.
Set to 16 psi +/- 2 psi
(.110 MPa, 110 kPa, 1.10 bar).
Push the yellow lock ring down to prevent the
adjustment knob from moving.
NOTE: Setting regulator 1 too high can cause the plain
coffee/product to nitrogenate.
B. Set Regulator 2- Nitrogen Tank to Nitrogenator.
Set to 34 psi +/- 2 psi
(.234 MPa, 234 kPa, 2.34 bar).
Push the yellow lock ring down to prevent the
adjustment knob from moving.
NOTE: Setting regulator 2 less than 32 psi(.221 MPa, 221 kPa,
2.21 bar) can prevent drinks from nitrogenating properly.
13. Reattach the rear panel and plug unit back into its
power source.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

STARBUCKS N2Fusion User manual

Category
Coffee makers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI