  • Hello! I am an AI chatbot trained to assist you with the EDWARDS 116DEXMSINH-GW Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation Instructions for 116DEXMSINH Series
AdaptaBeacon
®
Supervised DC Steady-On Lights for
Use in Hazardous Locations
DescriptionDescription
DescriptionDescription
Description
The 116DEXMSINH AdaptaBeacon 24-28V DC steady-on sig-
naling appliances are heavy duty diode-polarized lights
intended for use in general utility signaling (non-fire
alarm) applications requiring electrical supervision of sig-
naling circuit field wiring. The rotating assembly motor
driven at approximately 60 rpm. These devices are UL and
cUL listed for use in Class I, Division 1, Group C and D,
Class I, Division 2, Group C and D, Class II, Divisions 1 and
2, Group F and G, Class II, Division 1, Group E, and Class III
Division 1 and 2 hazardous locations with operating tem-
perature codes per following chart.
They are UL and cUL Listed as Type 3R, 4X, and Marine
enclosures.
The beacons are available with pendant, bracket, ceiling,
or stanchion mounting modules. See Figure 1.
InstallationInstallation
InstallationInstallation
Installation
Install this unit in accordance with the applicable require-
ments in the latest edition of the National Electrical Code
and Canadian Electrical Code.
mm) NPT threaded conduit (not supplied) to the
box. Install the unit on the conduit. Proceed to
step 2.
b. Ceiling Mount Models (Figure 3): Mount the
catalog number 116EX-C, ceiling/wall mounting
module, using appropriate hardware (not supplied)
suitable for the mounting surface. Proceed to step
2.
c. Bracket Mount Models (Figure 4): Install the
catalog number 116EX-C ceiling/wall mounting
module using appropriate hardware (not supplied)
for the mounting surface. Install the catalog
number 116EX-B wall mounting elbow to the wall
box. Run the unit's wiring through the elbow to
the wall box. Proceed to step 2.
d. Stanchion Mount Models (Figure 5): Install the
catalog number 116EX-S, stanchion mounting
module, to the main housing. Run the unit's wires
through the 1 1/4" conduit to the appropriate
junction box. Install the unit on the conduit.
Proceed to step 2.
2. Connect field earth ground wire to ground screw or
earth ground via conduit system.
3. Wire the unit in accordance with Figure 6. See Table
2 for required supply wire temperature ratings.
4. As appropriate, install the fixture on the mounting
module.
WARNING
To reduce the risks of ignition of hazardous atmo-
spheres and shock, do not apply power to the unit
until installation has been completed and unit is
tightly assembled and secured.
1. Mount using the following applicable method.
a. Pendant Mount Models (Figure 2): Install the
catalog number 116EX-P, pendant mounting
module, to the main housing. Install explosion-
proof hanger box (not supplied). Secure 3/4" (19
5. Apply power to the unit and ensure proper function.
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
P/N 3100810 ISSUE 1 © 2004
Cheshire, CT 06410 203-699-3300 (Ph)
203-699-3365 (Cust. Serv. Fax)
203-699-3078 (Tech. Serv. Fax)
STANCHION
116EX-S 1 1/4" HUB
CEILING
116EX-C 3/4" HUB
PENDANT
116EX-P 3/4" HUB
116EX-C
116 SERIES HOUSING AND GLOBE
ASSEMBLY WITH GUARD
WALL
116EX-B 3/4" HUB
Figure 1. Mounting Options
P/N 3100810 ISSUE 1
Figure 2. Detail of Pendant Mounting Figure 3. Detail of Ceiling Mounting
Figure 4. Detail of Wall Bracket Mounting Figure 5. Detail of Stanchion Mounting
12"
12 3/4"
7 1/4"
1"
13"
13 3/4"
7 1/4"
5/16"
4"
4"
6 3/4"
5/16"
4"
4"
6 3/4"
1"
12 9/16"
9 7/16"
16 1/16"
16 13/16"
1/4"
1 1/4"
Conduit
13 1/4"
12 3/4"
13 1/2"
Figure 6. Wiring Diagram
NOTE: For use without field wire supervision installer can tie the two white leads together and tie the two
black leads together.
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
From Power Source
or
Previous Signaling Device
End-of-Line Resistor,
when required with
supervised system
KEY:
Light symbol -
Wire nut symbol -
(+)
White
(+)
White
(+)
White
(+)
White
Black
(-)
Black
(-)
Black
(-)
Black
(-)
Series
116DEX
Series
116DEX
(+)
(-)
P/N 3100810 ISSUE 1
MaintenanceMaintenance
MaintenanceMaintenance
Maintenance
Disassemble the unit as follows (Figure 7):
counterclockwise direction. Remove the ring and
globe assembly.
3. Refer to Table 1 for the correct replacement catalog
number and replace the necessary part.
4. To replace, simply screw the unit on until it seats firmly
onto its gasket. Tighten the unit another 1/8 to 1/4
turn. Tighten the setscrew.
5. Reinstall the guard, where applicable, and secure using
the three supplied screws.
6. After the unit is assembled, apply power and make
sure the unit functions properly.
1. Loosen the (3) guard screws and remove the guard.
2. Loosen the globe and ring assembly set screw. Insert
a suitable tool into the notches in the globe and ring
assembly and loosen the assembly by prying in a
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
To reduce the risk of ignition of hazardous atmo-
spheres and shock, disconnect from the supply and
circuit and allow five (5) minutes for stored energy to
dissipate before disassembling the unit.
Figure 7. Disassembly of the 116EX Series AdaptaBeacons
Strobe Tube
Globe & Ring
Assembly
Guard
P/N 3100810 ISSUE 1
Contacting Edwards:
Phone: (203) 699-3300
Website: http://www.edwards-signals.com
Table 1. 116 Series AdaptaBeacons
Catalog Electrical Conduit Lamp
Description Number Ratings Size Replacement
Beacon Less 116DEXMSINH*-GW 24 - 28V DC N/A 50LMP-20WH
Mounting Module 0.8A or
Ind. Trade No.
25T8DC
Ceiling/Wall 116EX-C N/A 3/4" NPT N/A
Mounting Module
Pendant 116EX-P N/A 3/4" NPT N/A
Mounting Module
Stanchion 116EX-S N/A 1 1/4" NPT N/A
Mounting Module
Wall Bracket 116EX-B N/A N/A N/A
Mounting Elbow
*Letter in this position denotes color of the globe: A - amber, B - blue, C - clear, G - green, R - red or
M - magenta
Table 2. Ratings
Operating Temperature
Ambient Supply Wire Class I, Div. 2 Class I, Div. 1 & 2 Class II & III, Div. 1 Class II & III, Div. 2
Temp. Temp. Marking Groups A, B Groups C, D Groups E, F, G Group G
40°C 75°C T3 (200°C) T6 (85°C) T4A (120°C) T4A (120°C)
55°C 90°C T3 (200°C) T6 (85°C) T4 (135°C) T4 (135°C)
65°C 105°C T2D (215°C) T6 (85°C) T4 (135°C) T4 (135°C)
/