Nashua Tape 1415163 Installation guide

Type
Installation guide
Feb. 2009
The information presented herein was prepared at BERRY PLASTICS CORPORATION (25 Forge Parkway Franklin, MA 02038) by qualied technical personnel. To Berry Plastics’ knowledge it is true and accurate.
However, the information and recommendations are furnished for these products with the understanding that the purchaser or user, as the case may be, will independently determine that the product is suitable for the
intended use, and that such use complies with all applicable federal, state and local laws and regulations. The data are submitted only for the user’s information and consideration, and do not constitute a warranty of
any kind (including but not limited to a warranty of merchantability or of tness for a particular purpose), or a representation for which BERRY PLASTICS assumes any legal responsibility.
INSTALLATION GUIDE - FLEXIBLE DUCT
FOR USE WITH NASHUA 557, 558CA, FLEXFIX
®
, AND 324A
Connections
Splices
ADC Flexible Duct Performance & Installation Standards Fifth Edition 4.7.1
Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with Plain Ends
Step 1: : After desired length is determined, cut completely
around and through duct with knife or scissors. Cut wire
with wire cutters. Fold back jacket and insulation
1
.
Step 2: Slide at least 1” [25 mm] of core over tting and
past the bead. Seal core to collar with at least 2 wraps of
tape. Secure connection with clamp placed over the core
and tape and past the bead.
Step 3: Pull jacket and insulation back over core. Tape
jacket with at least 2 wraps of tape. A clamp may be used
in place of or in combination with the tape over the core
and tape and past the bead.
Step 3: Pull jacket and insulation back over cores. Tape
jackets together with at least 2 wraps of tape.
Step 2: Tape cores together with at least 2 wraps of
tape. Secure connection with 2 clamps placed over the
taped core ends and past the beads.
Step 1: Fold back jacket and insulation from core. Butt
two cores together on a 4” [100 mm] minimum length
metal sleeve.
1.
For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
The 2009, 2012, and 2015 International Energy Conservation Code (IECC) mandates the use of tapes listed and labeled in accordance
with Standard UL 181B and marked “181B-FX”. Nashua offers four products to meet this criteria - 557, 558CA, 324A, and FlexFix
®
.
Check with local code authorities for requirements specic to your municipality.
  • Page 1 1

Nashua Tape 1415163 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI