Also, some Monitor packages allow the changing of the
port configuration from a “user screen.” Consult your Moni-
tor user’s manual or contact your McQuay Service repre-
sentative for more details.
If you do not have the ability to change the port con-
figuration by the use of a keypad or a “user screen,” perform
the following procedures.
Setting up Communications
Use a PC with the appropriate Monitor software.
1.
Directly connect an IBM compatible PC to port A of the
controller by using the PC cable from the PC Commu-
nications Cable Kit. The PC Communications Cable Kit
is available from McQuay International.
2.
3.
4.
Access the
MicroTech
Monitor software by typing run
at the
(C:\>)
prompt.
Press <Enter>.
Press <Enter> at the prompt, “Press
<Esc
to bypass
Communications Initiation,
<Enter>
to continue..:’
This will begin communications between the PC and
the controller.
Note: If communications does not begin, contact
your McQuay Service representative for more detailed
information.
Reading the Port A Speed
Once communications begin, the Main Menu appears on
the PC screen.
1.
2.
3.
4.
Press F7 Support Menu to access the Support Menu.
Press
F1
Read/Write Memory from the Support Menu.
This will bring up the Read/Write Memory screen.
Type “B” followed by the address of the controller you
are connected to. This sets up the box address. For
example: If you are connected to the level-l controller,
type in B0000. The address
“00.FF”
will also work for
direct connection.
Type in R8010 for a 100 series controller or
R0A10
for
a 200 series controller to find the controller port speed.
Refer to the lists below for more information on 100
and 200 series controllers.
.
.
.
.
.
.
.
.
.
.
.
.
.
100 Series Controller
Chiller Plant Controller (CPC)
Application Specific Controller (ASC)
Centrifugal Chiller Unit Controller
200 Series Controller
Network Master Panel (NMP)
Application Specific Controller 200 (ASC-200)
Loop Water Controller (LWC)
Remote Monitoring and Sequencing Panel (RMS)
Remote Monitoring and Control Panel (RMC)
Chiller System Controller Panel (CSC)
Self-contained Air Conditioning Unit Controller
Reciprocating Chiller Unit Controller
Screw Chiller Unit Controller
Applied Rooftop Unit Controller
Writing the new Port A Speed
The speed of the controller port will be shown in a hexa-
decimal form such as
9B.
The first digit (9) is the port B
speed and the second digit (B) is the port A speed. See
Table 5.
Type
W8010
for a 100 series controller or
W0A10
for a
200 series controller to change the controller port
speed.
A prompt on the screen will ask, “New Value for
00.00 (Box Address), 8010 or
[0A10]
(Memory Lo-
cations) or <ENTER> for no change.”
Select the speed needed using Table 5.
If the port speed was originally B6, the speed of
port A would be 1200. If the speed of port A should be
9600, you would type BB. This would set the port
speed to 9600 baud.
Type the new port speed (for example, BB).
Press <Enter>.
Never change the port B baud rate.
Will cause loss of communications with the network.
The users should not change the port B baud rate under
any circumstance or they will lose communications with
the rest of the network.
Table 5. Controller Communications Port Speeds.
I”~’
msi
Rarte
I
I
,,,;.i--
~~
-1
300
I
4
I
1200
6
2400
8
4800
9
Resetting the Software
After entering the port speed, the controller needs to be
reset. The controller can be reset by performing a Software
Reset. Perform the execution of the Software Reset on the
Read/Write screen.
Type
W0204
(program code for Software Reset).
Press
<Enter>.
A prompt on the screen will ask, “New
Value for 00.00 0204 or <ENTER> for no change.”
Type an even number (0,2,4,6...) at the command. An
even number allows the program to reset and keep
running, an odd number (1,3,5...) stops the program
from running.
Press <Enter>. This stores the new port speed.
Correcting the Checksum
After the new port speed is stored, the Program Checksum
needs to be corrected. The Program Checksum must match
the EOS Checksum in order for the program to run. Perform
the following steps to change the Program Checksum.
These steps are also performed from the
Read/Write
screen.
1.
Type R8002 (100 series controller) or ROA02 (200
series controller) to read the EOS Checksum. The EOS
Checksum is shown in hexadecimal form. Write down
or remember the EOS Checksum.
Page 7
/
IM 564