Altronix NetWay16M Installation guide

Category
PoE adapters
Type
Installation guide

Altronix NetWay16M, a managed midspan solution, offers PoE and data transmission for up to 16 PoE-compliant cameras or edge devices over Ethernet cables, reaching distances of up to 328 ft. per port. It supports IEEE 802.3af/at standards, supplying 30W of power per port with a total power of 300W. The NetWay16M features individual port status LEDs, a user interface for programming PoE shutdown and port monitoring, and protection against short circuits and legacy non-PoE devices. Additionally, it can be rack or shelf-mounted, providing flexibility in installation.

Altronix NetWay16M, a managed midspan solution, offers PoE and data transmission for up to 16 PoE-compliant cameras or edge devices over Ethernet cables, reaching distances of up to 328 ft. per port. It supports IEEE 802.3af/at standards, supplying 30W of power per port with a total power of 300W. The NetWay16M features individual port status LEDs, a user interface for programming PoE shutdown and port monitoring, and protection against short circuits and legacy non-PoE devices. Additionally, it can be rack or shelf-mounted, providing flexibility in installation.

Power over the Ethernet
PoE Managed Midspan Solution for
Standard Network Infrastructure
Installation Guide
Models Include:
NetWay8M NetWay16M
- Eight (8) Port PoE Midspan Injector - Sixteen (16) Port PoE Midspan Injector
DOC#: NETM
Rev. 052110
More than just power.™
- 2 - NetWay8M/ NetWay16M
Overview:
Altronix NetWay8M/NetWay16M Managed Midspans provide power and pass data for PoE compliant cameras/edge devic-
es. Cameras/edge devices may be located up to 100m (328 ft.) from the NetWay unit. A NetWayXT repeater module can be
utilized to extend the distance an additional 100m (328 ft.) for a total range of up to 200m (656 ft.). A maximum range of
600m (1968 ft.) is possible using multiple repeaters, based on camera/device port requirement. NetWay Managed Midspans
are capable of supporting non-PoE compliant fixed and PTZ IP cameras utilizing NetWay1512 or NetWay3012 adapters.
NetWayM Specifications:
NetWay8M:
•Eight(8)portsofcameras/edgedevicesoverethernet(CAT5)
cable up to a distance of 100m (328 ft.) per port.
•115VAC60Hz,3amp(NetWay8M).
NetWay16M:
•Sixteen(16)portsofcameras/edgedevicesoverethernet(CAT5)
cable up to a distance of 100m (328 ft.) per port.
•115VAC60Hz,4.9amp(NetWay16M).
Common Specifications:
Agency Listings:
•UL/CULListedforInformationTechnologyEquipment
(UL60950-1).
• ULListedforAccessControlSystems(UL294).
• CEapproved.
Power:
•UnitsuppliesPoEoutputvoltage(55V),andupto30Wmax.
full power per port. Total power: NetWay8M - 150W,
NetWay16M - 300W.
•IEEE802.3afandIEEE802.3atcompliant(PoEPlus).
•Alloutputcircuitsarepowerlimited.
•Shortcircuitprotection.
Functions:
•ProgrammblePoEshutdownforeachport.Utilizedto
reset cameras/edge devices
(see Technical Specifications pg. 5).
• PoEmanualshutdown(ForUL60950-1applications
only) (see Technical Specifications pg. 5).
•Autodetectionandprotectionoflegacy
non-PoE cameras/edge devices.
Features:
•LANorlaptopconnectionenablesprogrammingof
PoE shutdown and port monitoring.
•Userinterface(Fig. 5, pg. 7).
•Illuminatedmasterpowerdisconnectcircuitbreaker
with manual reset (switch).
•IndividualportstatusLEDs.
•IEC320-3-wiregroundedlinecord(detachable).
•Unitcanberackorshelfmounted.
•1UrackmountchassisforuseinstandardEIA19”rack.
Accessories:
NetWay1512:
•15Wadapterfornon-PoEcompliantIPcameras.
(ForUL60950-1applicationsonly).
NetWay3012:
•25Wadapterfornon-PoEcompliantIP
fixed or PTZ cameras.
(ForUL60950-1applicationsonly).
NetWayXT:
•PoErepeatermoduleextendsrange100m(328ft.)
(ForUL60950-1applicationsonly).
Installation Instructions:
WiringmethodsshallbeinaccordancewiththeNationalElectricalCode(ANSI/NFPA70),localcodes,andtheauthoritieshaving
jurisdiction.
NetWayM is not intended to be connected to outside plant leads. These products are for indoor use only and must be
installed within the protected premises.
1. AttachmountingbracketstoNetWayMunitforrackorwallmountinstallation(Figs. 8 or 9, pg. 10).
Affix rubber pads to NetWayM for shelf installation (Fig. 10, pg. 10).
2. Securetheunitinarackorplaceunitonashelfasdesired.
Note:Thefollowingfactorsshouldbetakenintoconsiderationwheninstallingtheserackmountunits:
a.Theunitistobeinstalledinaspacewherethemaximumambienttemperaturedoesnotexceed104ºF(40ºC).
b.Takecaretoinsurethereissufficientairflowaroundtheunitandthatobstructionsdonotimpedeit.
c.Whenmountingunitsinrack,takecaretoavoidunevenloadingwhichcancauseahazardouscondition.
3. Setilluminatedmasterpowerdisconnectcircuitbreakertothe(OFF)position(Fig. 1g, pg. 3).
4. PlugthegroundedAClinecord(included)intotheIEC320connectoroftheNetWayMunit
(Fig. 1h, pg. 3).Plugunitintoareliableearthgroundedsocket.Whenusingmultipleunitsthesumoftheindividual
nameplateratingsshouldnotexceedthesupplycircuitrating.DonotConnectToAReceptacleControlledByA
Switch.
5. Connectstructuredcablesfromportmarked[IN]onNetWayMtothecorrespondinginputsofanethernetswitchor
video server (Fig. 1b, pg. 3, Fig. 4, pg. 5).
Note:AllcablingandwiremustbeULListedand/orRecognizedwiresuitablefortheirapplication.
6. Connectstructuredcablesfromportmarked[OUT]onNetWayMtoPoEcompliantcamera/edge
devices (Fig. 1a, pg. 3, Fig. 4, pg. 5).
Note: ForUL294applications,theproductsaretobetestedaspartofacompleteAccessControlSystemandin
accordancewithULListedAccessControlDevices.
NetWay8M/ NetWay16M - 3 -
Fig. 1
1a OUT1-8(NetWay8M),OUT1-16(NetWay16M):StructuredcabletoPoEcompliantcameras/edgedevices.
1b IN1-8(NetWay8M),IN1-16(NetWay16M):Structuredcabletoethernetswitchorvideoserver.
1c LED(s)1-8(NetWay8M),1-16(NetWay16M):PortstatusLEDs.
1d Reset:Restoresunittofactorysettings.
1e +---,PoEShutdown:Lowvoltagetriggerinput(see Technical Specifications pg. 5).
1f Ethernet:LANorlaptopconnectionenablesNetWayMprogrammingandstatusmonitoring.
AC POWER
NetWay8M & NetWay16M - Rear Panel
NetWay8M - Front Panel
NetWay16M - Front Panel
+ PoE - -
SHUTDOWN
+ PoE - -
SHUTDOWN
1a
1b
1c
1d
1e 1f
1g
1h
Note: AllinterconnecteddevicesmustbeULListed.
7. UponcompletionofwiringsetilluminatedmasterpowerdisconnectcircuitbreakertotheRESET(ON)
position (Fig. 1g, pg. 3).
8. PortstatusLEDsontheNetWayMwillinitializewhenPoEdevicesareconnectedasfollows:
- LEDwillilluminatewhendevicesareIEEE802.3afcompliant.
- LEDwillblinkonceandilluminatewhendevicesareIEEE802.3atcompliant(PoEPlus).
9. To utilize the PoE shutdown feature it is necessary to do the following:
a. Connect a device that will provide a low voltage trigger input (see Technical Specifications pg. 5) to terminals
marked[+---,PoEShutdown]ontheNetWayM(Fig. 1e, pg. 2). When voltage is applied, the PoE shutdown
enabledPoEport(s)willdroptozerovolts.Removingthelowvoltagetriggerinputatthe[+---,PoEshutdown]
terminals will allow the PoE port(s) to operate normally and supply power to PoE compliant devices. Power will
resetinapproximately4seconds.AlthoughthereisnooutputvoltagetopowerPoEdevicesduringshutdown,data
signals may still be present on the data pair lines of the structured cable.
b. Individual ports must be programmed utilizing the user interface (see User Interface and Programming, pgs. 6-9).
Port Status and LED Flash Codes:
Port Status Flash Codes Description
AllPortsOff SequentialLEDPortScan No devices connected
PortOff OFF LEDOFF
PortOn ON LEDON
Class4detectionPort Blinks2times Enables power to PoE devices.
Non-compliantDevice 2Hz Will prevent port from turning on.
PortOverloadFault 5Hz Will prevent port from turning on.
4PortOverloadGrouped 5Hz 4LEDs
Will prevent ports from turning on.
8PortOverloadGrouped 5Hz
LED’s1-8PowerSupplyOverloadforports1-8.
LED’s9-16PowerSupplyOverloadforports9-16.
- 4 - NetWay8M/ NetWay16M
1g Illuminatedmasterpowerdisconnectcircuitbreaker(switch):
• OFFpositionCircuitbreakertrippedSwitchnotilluminated.
• RESET(ON)positionSwitchilluminated.
1h IEC320Connector:115VAC60Hz(groundedlinecordincluded).
Installing a NetWay1512 adapter for 12VDC IP cameras up to 13W:
1. Mount NetWay1512 in proximity to IP camera (Fig. 2, pg. 4). Affix one side of velcro (supplied) to NetWay1512
and the place the second side of the velcro in the desired location.
2. Connectstructuredcablefromportmarked[IN]on
NetWay1512toanyportsmarked[OUT]ofNetWayM
(Fig. 2, pg. 4, Fig. 1a, pg. 3).
3. Connectstructuredcablefromportmarked[OUT]on
NetWay1512 to the IP camera (Fig. 2, pg. 4).
4. Connect12VDCoutputfromNetWay1512terminals
marked[---12VDC+]tothepowerinputofthe
IP camera (Fig. 2, pg. 4). Polarity must be observed.
5. PowerLEDindicatorwillilluminateonNetWay1512
under normal conditions (Fig. 2, pg. 4).
Installing a NetWay3012 adapter for 12VDC IP PTZ up to 25W:
1. Mount NetWay3012 in proximity to IP camera utilizing mounting hole (Fig. 3, pg. 5).Useaproperfastenerand/or
wall anchor when securing NetWay3012 to the wall.
2. Connectstructuredcablefromportmarked[IN]onNetWay3012Mtoportsmarked[OUT]ofNetWayM
(Fig. 3, pg. 5, Fig. 1a, pg. 3).
3. Connectstructuredcablefromportmarked[OUT]onNetWay3012MtotheIPfixedorPTZcamera(Fig. 3, pg. 5).
4. Connect12VDCoutputfromNetWay3012terminalsmarked[+12VDC---]tothepowerinputofthe
IP camera (Fig. 3, pg. 5). Polarity must be observed.
5. PowerLEDindicatorwillilluminateonNetWay3012undernormalconditions(Fig. 3, pg. 5).
Installing NetWayXT repeater module:
1. Mount NetWayXT in desired location utilizing the mounting hole (Fig. 3, pg. 4).Useaproperfastenerand/orwall
anchor when securing NetWayXT to the wall.
2. Connectstructuredcablefromportmarked[OUT]onNetWayMtoportmarked[IN]onthe
NetWayXT (Fig. 3, pg. 4, Fig. 1a, pg. 3).
3. Connectstructuredcablefromportmarked[OUT]onNetWayXTtothePoEcamera/edgedeviceornextNetWayXT
repeater (Fig. 3, pg. 4).
4. PortstatusLEDswillilluminateonNetWayXTindicatingtheportisoperational(refer to LED definitions on pg. 4).
5. PowerLEDwillilluminateindicating12VDCoutput(Fig. 3, pg. 4).
Port LED definitions for NetWayXT repeater:
Status GreenLED YellowLED
OFF Indicatesitisconnectedas10Base-Tornolink. Indicatesnolink.
ON Indicatesitisconnectedas100Base-TX. Indicatesalink.
Blinking --------------------------- Indicates activity.
Fig. 3 - NetWayXT
NetwayXT
Repeater
www.altronix.com
IN
OUT
Power
LED
Structured
Cable from
NetWayM
Structured Cable
from IP Camera/
Edge Device
or next
NetWayXT
www.altronix.com
IN
OUT
Netway1512
Adapter
12VDC
- -- Output +
- - +
12VDC
Output
Structured
Cable from
NetWayM
Structured Cable
from IP Camera/Device
Powe
r
LED
Fig. 2 - NetWay1512
NetWay8M/ NetWay16M - 5 -
NetWay8M/NetWay16M Typical Application:
Fig. 4
Technical Specifications:
Parameter Description
No. of Ports NetWay8M - Eight (8) Ports.
NetWay16M-Sixteen(16)Ports.
Input power requirements NetWay8M:115VAC60Hz,3amp.
NetWay16M:115VAC60Hz,4.9amp.
Fuse:4A/125V(NetWay16Mhas2fuses).
Note:Toreducetheriskoffire,replaceonlywithsametypeandratingoffuse.
Indicators PortStatusLED
PoEShutdownVoltage
andCurrentRange
5VDCto24VDCor12VACto24VAC
Minimumcurrent:2mAfor5VDC
Minimum current for higher voltages: 10mA
Environmental Conditions
OperatingAmbientTemperature: UL60950-1-32ºFto104ºF(0ºCto40ºC).
UL294-32ºFto120.2ºF(0ºCto49ºC).
Relativehumidity:85%,+/---5%
StorageTemperature:---4ºto158ºF(---20ºto70ºC)Storage
OperatingAltitude:---1000to10,000ft.(---304.8to3048m).
RegulatoryCompliance UL/CULListedforInformationTechnologyEquipment(UL60950-1).
ULListedforAccessControlSystems(UL294).
CE approved
NetWay8M
Card
Reader
HID Solo
Strike
NVR/Network Server
Ethernet Switch
Programming
and Status
PoE Camera
PoE Camera
NetWayXT
Extends Ethernet
100m (328 ft.)
NetwayXT
Repeater
IN
OUT
Power
www.altronix.com
12VDC
IP camera
NetWay1512
www.altronix.com
IN
OUT
Netway1512
Adapter
12VDC
+ Output -- -
I.T.E.
43KC
PoE +
Camera
+ PoE - -
SHUTDOWN
Typical UL294 Application:
- 6 - NetWay8M/ NetWay16M
NetWay8M/NetWay16M User Interface and Programming:
Note: A constant PC connection is not required for proper operations and is used as a local programming/monitoring tool only.
Step1. SetLocalAreaConnectionofyourlaptoptoDHCPmode.
For Windows XP:
a.OpenNetworkConnectionsbyclickingStartbutton,thenclickingSettings,thenclickingNetwork Connections.
b.RightclicktheLocal Area Connection.ClickProperties. Administrator permission required
If you are prompted for an administrator password or confirmation, type the password or provide confirmation.
c.DoubleclickInternet Protocol (TCP/IP) menu item.
d. Choose the Obtain an IP address automatically option.
e.ClickOK. Close all windows.
For Windows Vista:
a.OpenNetworkConnectionsbyclickingtheStartbuttonPictureoftheStartbutton,clickingControl Panel,
clickingNetwork and Internet,clickingNetwork and Sharing Center,andthenclickingManage Network
connections.
b.RightclicktheLocal Area Connectionicon,andthenclickProperties. Administrator permission required
If you are prompted for an administrator password or confirmation, type the password or provide confirmation.
c.ClicktheNetworkingtab.Underthisconnectionusesthefollowingitems,clickeitherInternet Protocol
Version 4 (TCP/IPv4) or Internet Protocol Version 6 (TCP/IPv6),andthenclickProperties.
d.TospecifyIPv4IPaddresssettings,clickObtain an IP address automatically,andthenclickOK.
e.TospecifyIPv6IPaddresssettings,clickObtain an IPv6 address automatically,andthenclickOK.
For Windows 7:
a.OpenNetworkConnectionsbyclickingtheStartbuttonPictureoftheStartbutton,clickingControl Panel,
clickingNetwork and Internet,clickingNetwork and Sharing Center,andthenclickingChange Adapter
Settings.
b.RightclicktheLocal Area Connectionicon,andthenclickProperties. Administrator permission required
If you are prompted for an administrator password or confirmation, type the password or provide confirmation.
c.ClicktheNetworkingtab.Underthisconnectionusesthefollowingitems,clickeitherInternet Protocol
Version 4 (TCP/IPv4) or Internet Protocol Version 6 (TCP/IPv6),andthenclickProperties.
d.TospecifyIPv4IPaddresssettings,clickObtain an IP address automatically,andthenclickOK.
e.TospecifyIPv6IPaddresssettings,clickObtain an IPv6 address automatically,andthenclickOK.
Step2. ConnectalaptoporPCtotheEthernetportofyourNetWayMunit,orconnectyourNetWayMandlaptop/PCto
aDHCProuterifNetWayMisinDHCPmode.TheNetWayMunitshouldbepoweredupatthismoment.
Step3. Openabrowserwindow(itisnecessarytoupdateyourbrowsersoftwaretothelatestversionsothatthepages
display and function correctly).
Step4. EntertheNetWayMIPaddress(thedefaultIPaddressis192.168.168.168),orentertheNetWayMhostnameif
inDHCPmode(defaulthostnameis“NetWayM1”,)intotheaddressbar.Statuspagewillbedisplayed.
Step5. ClickSetuplink.Setuppagewillbedisplayed.YoumaynowprogramyourNetWayM.
All NetWayM units come factory set:
a. Ports - Enabled.
b.Ports-PoEshutdownDisabled.
c. Power Allocation Mode - Class restricted.
Port Priority:
NetWayM allows you to prioritize ports so that power will be allocated to the port with the highest priority first and the
lowest priority last. This will ensure that ports with the higher priority will continue to operate in the event the
NetWayM is overloaded. Priority is designated 1 through 8, with 1 as the highest and 8 as the lowest.
NetWay8M - Port priority is factory set at 1 through 8 for ports 1 through 8.
NetWay16M - Port priority is factory set at 1 through 8 for ports 1 through 8 and 1 through 8 for ports 9 through 16.
1. To reassign port priority select desired number from the drop down box for that corresponding port.
It is necessary to assign the port with the highest priority first and continue in ascending order.
2. ClickSubmit to save the changes or proceed with programming.
Note: Access Control Ports must have highest priority.
Port Identification:
NetWayMallowsyoutoidentifyeachport(IDupto8characters).
1. TypethedesiredIDintothetextboxforeachcorrespondingport.
2. ClickSubmit to save the changes or proceed with programming.
NetWay8M/ NetWay16M - 7 -
PoE port setup:
Individual ports may be disabled if those ports are not used or to avoid the connection of unauthorized PoE devices.
1. TodisableoneormoreportsclickontheDisable radio button(s) in the PoE column (Fig. 5, pg. 7).
2. ToenableoneormoreportsclickontheEnable radio button(s) in the PoE column (Fig. 5, pg. 7).
Note: ToenableallportsclickontheEnable AlllinkbelowPoEcolumn.
3. ClickSubmit to save the changes or proceed with programming.
PoE port shutdown:
Individual ports may be set for PoE shutdown. PoE shutdown affects only enabled ports and only
occurs when a trigger input is applied to the PoE shutdown terminals on the NetWayM.
1. ToenablePoEshutdownforoneormoreportsclickontheEnable radio button(s) in the PoE shutdown
column (Fig. 5, pg. 7).
2. TodisablePoEshutdownforoneormoreportsclickontheDisable radio button(s) in the PoE shutdown
column (Fig. 5, pg. 7).
Note:ToenableordisablePoEshutdownforallportsclickoncorrespondinglinkbelowPoEshutdowncolumn.
3. ClickSubmit to save the changes or proceed with programming.
Power Allocation Mode:
NetWayM features the ability to select how total power is allocated to the ports.
- Class Restricted Power Mode - each port will be allocated the maximum rated power that the PoE device will
broadcast.
- Dynamic Power Mode - each port will supply the specific amount of power that the PoE device requires
for operation.
Note:BesurenottoexceedthetotalpowerNetWay8M/NetWay16Misratedat.
1. ClickonthecorrespondingradiobuttontosetthePowerModedesired(Fig. 5, pg. 7).
2. ClickSubmit to save the changes or proceed with programming.
Fig. 5 - NetWay8M/NetWay16MSetupPage
- 8 - NetWay8M/ NetWay16M
Configuring NetWay8M/NetWay16M for network connection:
SinceeveryNetworkConfigurationisdifferent,pleasecheckwithyourNetworkAdministratortoseeifyourNetWay8M/
NetWay16MshouldusestaticIPaddresses,orDHCPassignedIPaddressesand/anInboundPortassignmentpriortoset-
tingupnetworkconnection.
1. ClickNetworkSettingslink.
If you are prompted for an administrative password, type and submit the password.
Note:Defaultsettingshavepasswordrequirementsturnedoff.
2. NetworkSetuppagewillbedisplayed.YoumaynowconfigureyourNetWay8M/NetWay16Mfornetwork
connection.
Fig. 6-NETWORKSETTINGMENU.ThismenuisforconfiguringtheNetWay8M/NetWay16Munitsforanetwork
connection.
Network Type:
StaticIP:UsercansetafixedIPfornetworkconnection.
DHCP:DHCPserverinLANwillautomaticallyanassignIPconfigurationforthenetworkconnection
IP:ThisfieldshowstheNetWay8M/NetWay16McurrentIPAddress.AstaticIPaddressmustbesetmanually.IfDHCP
this value will be assigned automatically.
SubnetMask:ThisfieldshowsthesubnetmaskforyournetworksotheNetWay8M/NetWay16Mwillberecognized
withinthenetwork.IfDHCPisselected,thisvaluewillbeassignedautomatically.
InboundPort:PortnumberforHTTP/WEBcommunication.
HostName:NameoftheNetWay8M/NetWay16MdeviceontheLAN
Additional information:
1.IfusingDHCP,allsettingswillbedetectedautomatically.
WhileDHCPisausefultoolfordeterminingthenetworksettings,ifyousetupyourNetWay8M/NetWay16Minthis
manner its IP address may change at different times for different reasons, particularly after a power failure. If the IP
address of the NetWay8M/NetWay16M changes, you may have difficulties accessing your NetWay8M/NetWay16M lo-
cally and/or remotely.
ItisstronglyrecommendedthatyouconnectviahostnamewhenunitsconfiguredasDHCP.
PleasedonotsettheDHCPaddressissuedtotheNetWay8M/NetWay16MbytherouterasitsstaticIPaddressunlessyou
takespecificstepsthatprogramyourroutertopreventsuchaddressconflicts.
2.IfusingaStaticIP(recommended),youwillneedtoinputtheinformationmanually.InorderforDDNStowork,you
mustentervaliddata,compatiblewithyournetwork,forallofthenetworksettingfields:IPaddress,SubnetMask,In-
boundPortandHostName.
3.Ifyouareconnectingthrougharouter,makesurethatyouhave‘openedup’alltherequirednetworkportsintheport
forwardingsectionofyourrouter’ssetupoptions.Thatis,youhavedirectedtheroutertosendanyincomingtrafficusing
thoseIPportstotheLANIPaddressoftheNetWay8M/NetWay16M.Usefulinformationaboutrouterportforward-
ingcanbefoundatwww.portforward.com.Differentroutersmayusedifferenttermsforportforwardingfunction.For
instance,D-Linkcallsitvirtualserver,Netopiacallsitpinholes.
NetWay8M/ NetWay16M - 9 -
The default port for NetWay8M/NetWay16M is: 80
Note:Port80isthedefaultportusedforwebbrowsing.Becauseofthis,inordertopreventtheaverageuserfromhost-
ingawebserver,mostISPsBLOCKtrafficusingport80fromreachingtheaveragesite.Ifyouonlyplantomonitoryour
NetWay8/NetWay16MonaLAN,youcanuseport80,anddon’thavetoconcernyourselfwithrouters.However,ifyou
desireremoteaccesstoyourNetWay8M/NetWay16M,youMUSTselectfunctionalportsandsetuptheportforwarding
inyourrouter.Otherports,suchas8080and8000aresometimesblockedbyISPsaswell.Whatport(s)shouldbeused?
Thereare65,535validIPportstochoosefrom.Thesearebrokendownintothreegroups:
•WellKnownPorts0thru1023
•RegisteredPorts1024thru49151
•Dynamicand/orPrivatePorts49152thru65535
So,ratherthanencounteraportconflictbychoosingaportcommonlyusedforanotherpurpose(likeport25forSMTP
mailorport448forsecuresockets),choosean‘unusual’portnumber.Forexample,add50,000toyourhousenumber:
50,123islesslikelytoleadtoaportconflict.Foralistoftheknownand
registered ports, see http://www.iana.org/assignments/port-numbers
Reset Features:
Reset Password:
1. Setilluminatedmasterpowerdisconnectcircuitbreakertothe(OFF)position(Fig. 1g, pg. 3).
2. SetilluminatedmasterpowerdisconnectcircuitbreakertotheRESET(ON)position(Fig. 1g, pg. 3)
whiledepressingthe[RESETbutton]onthefrontoftheNetWayM(Fig. 1d, pg. 3).
3. NetWayMstatusLEDswilldisplayaflashingpatternwhichindicatesresetwassuccessful(Fig. 1c, pg. 3).
Reset IP to Factory Settings:
1. Duringnormaloperationdepressthe[RESETbutton]onthefrontoftheNetWayMforapproximately
1 second (Fig. 1d, pg. 3).
2. NetWayMstatusLEDswilldisplayaflashingpatternwhichindicatesresetwassuccessful(Fig. 1c, pg. 3).
3. Factorysettingsare:DHCPserverandtheIPaddressis[192.168.168.168].
- 10 - NetWay8M/ NetWay16M
NetWay8M/NetWay16M Rack Mount Chassis Mechanical Drawing & Dimensions:
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presenceofaninsulated“DANGEROUSVOLTAGE”withintheproductsenclosurethatmaybeofsufficient
magnitudetoconstituteanelectricshock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION:Toreducetheriskofelectricshockdonotopenenclosure.There
arenouserserviceablepartsinside.Referservicingtoqualifiedservicepersonnel.
8.5"
.75"
19.125"
17.625"
1.625"
AC POWER
(ON)
+ PoE - -
SHUTDOWN
+ PoE - -
SHUTDOWN
Fig. 7
NetWay8M/ NetWay16M - 11 -
Wall Mount Installation
1-Installmountingbrackets(A)ontheleftandrightsideofrackchassis using
four(4)flatheadscrews(B)(included)(Fig. 9a).
2- Place unit at desired location and secure with mounting screws
(not included) (Fig. 9b).
Caution: It is necessary to
makesuremountingscrews
are securely fastened to a
beam when installing the
unit vertically.
B
A
Mounting Options:
Fig. 8
Rack Mount Installation
1- Removeanddiscardfactoryinstalledscrewsfrombothsidesofrackchassis(Fig. 8a).
2-Installmountingbrackets(A)ontheleftandrightsideofrackchassis using the
four(4)flatheadscrews(B)(included)(Fig. 8b).
3- PlaceunitintodesiredEIA19”rackpositionandsecurewithmountingscrews(not included) (Fig. 8c).
Fig. 10
Fig. 9
Shelf Installation
1- Position and affix rubber pads (C) (included) at each
corner on the bottom of the unit (Fig. 10).
2- Place unit in desired location.
B
A
C
Mounting Hardware (Included):
Fig. 9b
Fig. 9a
C
A
B
Fig. 8b
Fig. 8a
Fig. 8c
Top Top Top
Front
Left
Front
Left
FrontLeft
LeftSide
RubberPad
Two(2)mountingbrackets
Six(6)flatheadscrews
formountingbrackets.
Four(4)rubberpads.
Remove
Dotted lines indicate studs
behind sheetrock.
- 12 - NetWay8M/ NetWay16M
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:[email protected],MadeinU.S.A.
IINetWay8M/NetWay16M H03K
Notes:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Altronix NetWay16M Installation guide

Category
PoE adapters
Type
Installation guide

Altronix NetWay16M, a managed midspan solution, offers PoE and data transmission for up to 16 PoE-compliant cameras or edge devices over Ethernet cables, reaching distances of up to 328 ft. per port. It supports IEEE 802.3af/at standards, supplying 30W of power per port with a total power of 300W. The NetWay16M features individual port status LEDs, a user interface for programming PoE shutdown and port monitoring, and protection against short circuits and legacy non-PoE devices. Additionally, it can be rack or shelf-mounted, providing flexibility in installation.