bolid S2000-KPB Product information

  • Hello! I've analyzed the provided datasheet of Bolid S2000-KPB control panel. This document includes detailed information about alarm loop connections, power supply configurations, output usage and load connection modules. I'm ready to answer all your questions regarding S2000-KPB.
  • What type of devices can be connected to the outputs?
    Where should load connection modules be installed?
    What should be used instead of load connection module if output is not in use?
    Can normally open and normally closed detectors be in the same circuit?
7
8
9
10
3
4
1
2
5
6
1
2
3
4
5
6
7
8
9
10
11
12
XT1.1
XT1.2
XT1.3
XT1.4
XT1.5
XT1.6
Out.1 -
Out.1 +
Out.2 -
Out.2 +
Out.3 -
Out.3 +
Out.4 -
Out.4 +
Out.5 -
Out.5 +
Out.6 -
Out.6 +
XT2.3
loop 1+
loop 1-
«1»
«2»
«3»
«4»
«5»
«6»
Lamp
Lock
Discharge
Circuit
Discharge
Circuit
Discharge
Circuit
XT2.5
XT2.1
RS-485A
RS-485B
+Umain
0 V
+12 V...+24 V
0 V
to the power supply 1
RS-485
to the console,
S2000-ASPT, or PC
COM
XT2.2
+Uback
0 V
+12 V...+24 V
0 V
to the power supply 2 READY
S2000-KPB
Siren
1
2
4
3
red
black black
while
Load Connection Module
(LCM)
1
2 3
4
к
ч ч
б
LCM
Notes:
1. The type of executive devices to be connected to the outputs is to be defined by user and can
differ from the shown devices.
2. The load connection modules should be installed in proximity to the executive devices.
3. If an output is not in use, a 1kOhm - 0.5 W resistor can be used instead of the load
connection module.
4. Normally open and normally closed detectors can be combined and brought into the same
circuit if only a single detector can be in activated status.
XT2.4
loop 2+
loop 2- PRES
MASS
to alarm loops
4.7kOhm 2 kOhm
4.7 kOhm
3.3 kOhm
An example of an alarm
loop with a normally
closed detector
An example of an alarm
loop with a normally
open detector