Page 3 of 18 Rev D May 2016
Recommended Clearances
For safe operation the following clearances must be used when installing this fire.
Due to the installation being carried out by a variety of tradesmen and or owners is it imperative the operator
check for hot spots when the fire is operating, any spot hotter than 65 deg C must be protected by heat
shield.
When operating the fire if any surface that is combustible i.e. wood, lining or furniture gets to the
temperature where it is hot to touch with the back of your hand then you should be looking at
improving the heat reflectors for greater margin of safety.
This can be by installing heat deflectors or increasing the clearance to the fire.
Custom heat deflectors can be made on request by contacting Tarlan Technical Ltd. Or any sheet metal
company.
Minimum Recommended clearances:
Rear of Fire:
Combustible Surface:
From Fire to a combustible surface – i.e. wood or polystyrene insulated wall without any heat deflectors –
From Rear Heat shield : wood to be 360mm –polystyrene insulated panel 400mm.
From Sides: 310mm
Any panel temperature must not exceed 65 °C
If an additional metal sheet is placed on the wall, use spacers to hold off the wall 25mm, at the bottom of
sheet the gap from sheet to floor must be at least a 25mm as well as the top gap must be open, and then
recommended clearance can be reduced to 100mm – see attached 0404 test report and table 3.1
Sides of Fire:
Clearance from stainless heat shield to any combustible surface is 250 mm; if walls have non-combustible or
have sheet metal heat shield fitted then gap can be reduced to 100mm, closer clearances are possible but
please consult us.
Pedestal or base of fire:
150mm Pedestal: - A non combustible sheet such as cement board 6mm thick must be placed between the
mounting base and the floor.
75mm Pedestal: A non combustible 6mm sheet under mounting plate and tiles must be placed to extend
100mm past each side of the fire (do not tile under the pedestal or they will crack when bolts are drawn up)