Amana AMVT Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
AMVT***P1400**
AIR HANDLERS INSTALLATION &
OPERATING INSTRUCTIONS
© 2022-2023 Daikin Comfort Technologies Manufacturing, L.P.
www.goodmanmfg.com - or - www.amana-hac.com
19001 Kermier Rd., Waller, TX 77484
P/N: IOG-4040B Date: February 2023
Contents
1 Important Safety Instructions .................................... 3
2 Shipping Inspection ................................................... 3
2.1 Parts ....................................................................... 3
2.2 Handling ................................................................. 3
2.3 Shipping Material Removal..................................... 3
3 Codes & Regulations ................................................. 3
4 Replacement Parts ..................................................... 3
5 Pre-Installation Considerations ............................... 3
5.1 Preparation ............................................................. 3
5.2 System Matches ..................................................... 3
5.3 Interconnecting Tubing ........................................... 3
5.4 Clearances ............................................................. 3
5.5 Horizontal Applications ........................................... 4
6 Installation Location ................................................... 4
 4
...................... 5
6.3 Horizontal Right Installation  ................... 5
6.4 Humid Environment Installations ............................ 5
6.4.1 All Installations – Humid Environments ............... 5
 5
6.4.1.3 Horizontal Installations – Humid Environments 5
7 Refrigerant Lines ........................................................ 6
7.1 Tubing Size ............................................................. 6
7.2 Tubing Preparation ................................................. 6
7.3 Tubing Connections ................................................ 7
7.4 Thermal Expansion Valve System Adjustment ....... 9
8 Condensate Drain Lines ........................................... 10
9 Ductwork .................................................................... 11
9.1 Return Ductwork .................................................... 11
10 Return Air Filters ..................................................... 11
11 Electric Heat ............................................................. 11
12 Electrical and Control Wiring ................................. 14
12.1 Building Electrical Service Inspection .................. 14
WARNING

This device, which was assembled by Daikin Comfort Technologies


FCC: FCC ID QOQBGM111. And this international radiator has an
Industry Canada ID: IC 5123A-BGM111.
This device complies with Part 15 of the FCC’s Rules. Operation of this
device is subject to two conditions:


interference that may cause undesirable operation.
And this device meets the applicable Industry Canada technical


Silicon Laboratories Finland Oy, which can be contacted by calling

The FCC responsible party is Daikin Comfort Technologies
Manufacturing, L.P. may be contacted by calling 713-861-2500, or at

This equipment complies with FCC radiation exposure limits. To ensure
compliance, human proximity to the antenna shall not be less than
20 cm during normal operations.
®
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.




























WARNING
2
12.2 Wire Sizing .......................................................... 14
 ............ 14
12.4 Electrical Connections – Supply Voltage ............. 14
 ........... 15
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits ..... 15
12.4.3 Air Handler With Circuit Breaker Heat Kit ......... 15
12.5 Low Voltage Connections .................................... 15
12.5.1 Thermostats ...................................................... 15
13 CoolCloud HVAC Phone Menu ............................... 15
14 Quick Start Guide for Communication Outdoor Units 16
14.1 Charging .............................................................. 17
15 Quick Start Guide for Non-Communicating Outdoor
Units ...................................................................................... 17
 ..................................................... 19
 ............................................ 19
18 Start-Up Procedure.................................................. 19

 ............................................................... 19
 .......................... 20
 ..................................................... 21
22 Electric Air Cleaner Warning .................................. 21
 ........................ 21
24 Start-up Procedure .................................................. 22
25 Regular Maintenance .............................................. 22
 ...................... 23
27 Air Handler Display ................................................. 25
 ............................................................ 27
29 Wiring Diagram ........................................................ 28
30 Start-Up Checklist ................................................... 31
RECOGNIZE SYMBOL THIS
AS A SAFETY PRECAUTION
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED
HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE.
WARNING
HIGH VOLTAGE
-

-

WARNING



WARNING
-
DO NOT

CAUTION




WARNING


UNBROKEN
-
-






Carbon monoxide producing devices (such as an automobile, space
heater, gas water heater, etc.) should not be operated in enclosed areas
such as unvenlated garages, ulity rooms or parking areas because of
the danger of carbon monoxide (CO) poisoning resulng from the exhaust
emissions. If a furnace or air handler is installed in an enclosed area such
as a garage, ulity room or parking area and a carbon monoxide producing
device is operated therein, there must be adequate, direct outside
venlaon.
CARBON MONOXIDE POISONING HAZARD
Special Warning for In stallao n of Furnace or Air Handling Units in
Enclosed Areas su ch as Garages, Ulity Rooms or Parking Areas
This venlaon is necessary to avoid the danger of CO poisoning which
can occur if a carbon monoxide producing device connues to operate in
the enclosed area. Carbon monoxide emissions can be (re)circulated
throughout the structure if the furnace or air handler is operang in any
mode.
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Los equipos ó aparatos que producen moxido
(tal como autovil, calentador de gas, calentador de
carbono (CO) que resulta de las
emisiones de gases de com busón.
gas, etc) no deben ser operados en áreas cerradas debido al riesgo
de envenenamiento por moxido de
Si el equipo ó aparato se opera en
dichas áreas, debe exisr una adecuada venlación directa al exterior.
de carbono
agua por medio de
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
RIESGO DE INTOXICACIÓN POR MOXIDO DE CARBONO
El moxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de moxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
Averssement special au sujet de l'installaon d'appareils de chauffage
ou de traitement d'air dans des endroits clos, tets les garages, les
locaux d'entreen et les staonnements.
B10259-216
RISQUE D'EMPOISONNEMENT AUMONOXYDE DE CARBONE
Evitez de mere en marche les appareils produisant du monoxyde
de carbone (tels que les automobile, les appareils de chauffage
autonome,etc.) dans des endroits non vens tels que les
d'empoisonnement au monoxyde de carbone. Si vous devez faire
fonconner ces appareils dans un endroit clos, assures-vous
qu'il y ait une venlaon directe provenant de l'exterier.
Le monoxyde de
des
carbone peut causer des maladies graves telles que
dommages permanents au cerveau et meme la mort.
Les émissions de monoxyde de carbone peuvent etre recircules dans les
endroits clos, si l'appareil de chauffage ou de traitement d'air sont
en marche.
Cee venlaon est cessaire pour éviter le danger d'intoxicaon
au CO pouvant su rvenir si un appareil produisant du monoxyde
de carbone connue de fonconner au sein de la zone confie.
Esta venlación es necesaria para evitar el peligro de envenenamiento
por CO, que puede ocurrir si un moxido
de carbono sigue operando en el lugar cerrado.
disposivo que produc e
3
1 Important Safety Instructions
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards.
It is the owner’s and installer’s responsibility to read
and comply with all safety information and instructions
accompanying these symbols. Failure to heed safety
information increases the risk of personal injury, property
damage, and/or product damage.
2 Shipping Inspection

side or top during transit may cause equipment damage.
The installer should inspect the product upon receipt for
shipping damage and subsequent investigation is the
responsibility of the carrier. The installer must verify the

accessories are correct prior to installation. The distributor
or manufacturer will not accept claims from dealers for
transportation damage or installation of incorrectly shipped
units.
2.1 Parts
Inspect the unit to verify all required components are
present and intact. Report any missing components
immediately to the manufacturer or to the distributor. Use

Make sure to include the full product model number and
serial number when reporting and/or obtaining service
parts.
2.2 Handling
Use caution when transporting / carrying the unit. Do not
move unit using shipping straps. Do not carry unit with
hooks or sharp objects. The preferred method of carrying
the unit after arrival at the job site is to carry via a two-
wheel hand truck from the back or sides or via hand by
carrying at the cabinet corners.
2.3 Shipping Material Removal
IMPORTANT: All Shipping Material used to protect the


3 Codes & Regulations
This product is designed and manufactured to comply with
applicable national codes. Installation in accordance with
such codes and / or prevailing local codes / regulations
is the responsibility of the installer. The manufacturer
assumes no responsibility for equipment installed in
violation of any codes or regulations.




.
Should you have any questions please contact the local

gov.
4 Replacement Parts
When reporting shortages or damages, or ordering repair
parts, give the complete product model and serial numbers
as stamped on the product. Replacement parts for this
product are available through your contractor or local
distributor. For the location of your nearest distributor
consult the white business pages, the yellow page section
of the local telephone book or contact:
HOMEOWNER SUPPORT
DAIKIN COMFORT TECHNOLOGIES
MANUFACTURING, L.P.
19001 KERMIER ROAD
WALLER, TEXAS 77484

5 Pre-Installation Considerations
5.1 Preparation
Keep this document with the unit. Carefully read all
instructions for the installation prior to installing product.
Make sure each step or procedure is understood and
any special considerations are taken into account before
starting installation. Assemble all tools, hardware and
supplies needed to complete the installation. Some items
may need to be purchased locally. Make sure everything
needed to install the product is on hand before starting.
5.2 System Matches



listed. NOTE: Installation of unmatched systems is not
permitted.
5.3 Interconnecting Tubing
Give special consideration to minimize the length of
refrigerant tubing when installing air handlers. Refer to
Remote Cooling / Heat Pump Service Manual RS6200006,
and TP-107 Long Line Set Application R-410A for tubing
guidelines. If possible, allow adequate length of tubing such


5.4 Clearances
The unit clearance from a combustible surface may be
0”. However, service clearance must take precedence. A
minimum of 24” in front of the unit for service clearance
is required. Additional clearance on one side or top will
be required for electrical wiring connections. Consult all

clearances. When installing this unit in an area that may

sturdy, non-porous material. In installations that may lead

protective barrier to prevent such damage. Always install


4
5.5 Horizontal Applications


installed under the entire unit and its condensate drain line
must be routed to a location such that the user will see the
condensate discharge.
6 Installation Location
NOTE: These air handlers are designed for indoor


If the unit is located in an unconditioned area with high
ambient temperature and/or high humidity, the air handler
may be subject to nuisance sweating of the casing. On

with a vapor barrier is recommended. A secondary drain
pan below the unit is also recommended to protect the
installation site.


shown in Figures 3, 4, 5 and 6. The unit may be installed


6.1 Upflow and Downflow Installation
(Figure 3 & 4)
1. Remove blower access panel and coil access panel.
The coil access panel and tubing panel may remain
screwed together during this procedure. Remove and


the blower access panel to the cabinet.
2. Slide the coil assembly out from the cabinet. Use the
drain pan to pull the assembly from the cabinet.
IMPORTANT: Do not use manifolds, copper lines, or

do so may result in braze joint damage and leaks.
3. Removal of the center support is required on units

screws that secure the center support to the cabinet.
Remove the center support.
4. The horizontal drip shield, side drain pan, and drain
pan extension must be removed. Follow the “Side
Drain Pan and Extension Removal Instructions”.
5. 
a. Using the drain pan to hold the coil assembly,
slide the coil assembly back into the cabinet.
b. 

c. Reinstall the coil access panels and reinstall
blower access panel removed in Step 1 as shown
in Figure 9.
6. 
a. 
b. Using the drain pan to hold the coil assembly,
slide the coil assembly back into the cabinet on

c. 

d. Reinstall the coil access panels and reinstall
blower access panel removed in Step 1 as shown
in Figure 10.
Side Drain Pan and Extension Removal Instructions

the drip shield support brackets to the condensate

from the bottom drain pan using a screwdriver or any small
lever. The side drain pan, drip shield brackets and the drain
pan extension may now be removed. From Figure 2, drain

condensate drain line must be attached to this drain port.

the side drain pan is removed, the drain port opening in the
access panel must be covered by the accessory drain port

Kit Number Application
DPK1 All Models
Side Drain Port Plug
Description
Drain Port Plug


SIDE DRAIN PAN
DPK1 DRAIN PLUG
COIL ACCESS PANEL
MAIN DRAIN PAN


5


6.2 Horizontal Left Installation (Figure 5)

Install unit as shown in Figure 5.

this application and condensate drain line must be attached


Remove red plugs from side drain pan before connecting
condensate drain pipes. Use removed plug to close drain
ports on vertical drain pan.
6.3 Horizontal Right Installation (Figure 6)




1. Before inverting the air handler, remove blower
access panel and coil access panel. The coil access
panel and tubing panel may remain screwed together
during this procedure. Remove and retain the seven


access panel to the cabinet.
2. Slide the coil assembly out from the cabinet. Use the
drain pan to pull the assembly from the cabinet.



3. Removal of the center support is required on units

screws that secure the center support to the cabinet.
Remove the center support.
4. 
5. Remove side drain pan extension if present.
6. Using the drain pan to hold the coil assembly, slide the

brackets as shown in Figure 8.
7. 

8. Reinstall the coil access panels and reinstall blower
access panel removed in Step 1 as shown in Figure 10.
9. Drain Connections for Horizontal Right Installation
a. 
drain for this application and condensate drain line


b. Remove red plugs from side drain pan before
connecting condensate drain pipes. Use removed
plug to close drain ports on vertical drain pan.

must

6.4 Humid Environment Installations



to assist with condensation management in humid


6.4.1 ALL INSTALLATIONS – HUMID ENVIRONMENTS
Installations in areas where the return air environment
sees humidity levels above 65% relative humidity, a High

and Kit assignment.
HHK0004 HHK0005 HHK0006 HHK0007 HHK0008
AMVT24B
AMVT30B
AMVT36B
AMVT36C
AMVT42C
AMVT48C
AMVT48C AMVT48D AMVT48B

6.4.1.2 Downflow Installations – Humid
Environments
To prevent the coil pan “sweating”, the mandatory


for each model.
DFKE-02 DFKE-03
AMVT24B
AMVT30B
AMVT36B
AMVT36C
AMVT42C
AMVT48C
AMVT48D
AMVT60D

6
6.4.1.3 Horizontal Installations – Humid
Environments

where the air handler is installed in the horizontal position

humidity levels above 65% relative humidity, a Condensate

Applicable Kit and Model listing can be found in Table 4.
CMK0018 CMK0019 CMK0020
AMVT24B
AMVT36C
AMVT30B
AMVT36B
AMVT42C
AMVT48C
AMVT48D
AMVT60D









7
7 Refrigerant Lines
WARNING
THIS PRODUCT IS FACTORY-SHIPPED WITH R410A AND DRY
-
PRIATE SERVICE TOOLS AND FOLLOW THESE INSTRUC-





If the unit is located in an unconditioned area with





7.1 Tubing Size

condenser/heat pump.
7.2 Tubing Preparation
All cut ends are to be round, burr free, and clean. Failure
to follow this practice increases the chances for refrigerant
leaks. The suction line is spun closed and requires tubing
cutters to remove the closed end.




NOTE: The use of a heat shield is strongly

Heat trap or wet rags


WARNING
A QUENCHING CLOTH IS STRONGLY RECOMMENDED TO
PREVENT SCORCHING OR MARRING OF THE EQUIPMENT


CAUTION
APPLYING TOO MUCH HEAT TO ANY TUBE CAN MELT THE
-
OUS SIZES MUST BE PROPORTIONAL TO THE SIZE OF THE


7.3 Tubing Connections
An adjustable TXV with bulb is installed on the vapor tube
from the factory.
1. 
panel.
2. 

pressure indicates possible leak.
3. Replace the panel.
4. Remove the spin closure on both the liquid and
suction tubes using a tubing cutter.
5. Insert liquid line set into liquid tube expansion and
slide grommet about 18” away from braze joint.
6. Insert suction line set into suction tube expansion and
slide insulation and grommet about 18” away from
braze joint.
7. Braze joints. Quench all brazed joints with water or a
wet rag upon completion of brazing.
8
Upper Tie Plate
Control
Deck
Downow
Bracket
Center
Support
Filter
Bracket
Filter
Access
Panel
Blower
Access
Panel
Coil
Access
Panel
UV
Knockout
Tubing
Panel







IMPORTANT NOTE: Ensure coil slides on the rails

Failure to do so will result in improper condensate



9
7.4 Thermal Expansion Valve System Adjustment
The following information for the indoor unit should be

necessary.
1. Total static pressure is .5” WC or less.
2. 
3. 
Sheet for Indoor Unit.
4. 
in Service Manual RS6200006.
5. The outdoor temperature must be 60°F or higher.
6. Set the room thermostat to COOL, fan switch to
AUTO.
7. Set the temperature control well below room
temperature.
Superheat adjustments should not be made until indoor
ambient conditions have stabilized. This could take up to
24 hours depending on indoor temperature and humidity.
Before checking superheat run the unit in cooling for 10
minutes or until refrigerant pressures stabilize. Use the
following guidelines and methods to check unit operation
and ensure that the refrigerant charge is within limits.

1. Purge gauge lines. Connect service gauge manifold to
base-valve service ports.
2. Temporarily install a thermometer on the liquid
line at the liquid line service valve and 4-6” from
the compressor on the suction line. Ensure the
thermometer makes adequate contact and is insulated
for best possible readings. Use liquid line temperature
to determine subcooling and vapor temperature to
determine superheat.
3. Check subcooling and superheat. The system should
have a subcooling of 8°F +/- 1°F and two-stage
compressor systems should have a Subcooling of 6°F
+/- 1°F. and superheat of 8°F +/- 1°F. If subcooling
and superheat are low, adjust TXV to 8°F +/- 1°F
superheat, then check subcooling.
a. If subcooling is low and superheat is high,
add charge to raise subcooling to 8°F +/- 1°F.
Two-stage compressor systems should have a
Subcooling of 6°F +/- 1°F then check superheat.
b. If subcooling and superheat are high, adjust
TXV valve to 8°F +/- 1°F superheat, then check
subcooling.

1. Attach a pipe clamp thermometer near the suction line
service valve at the outdoor unit.
a. Ensure the thermometer makes adequate contact
for the best possible readings.
2. TXV-based systems should have a Superheat value of
8°F +/- 1°F.
3. Adjust Superheat by turning the TXV valve stem
clockwise to increase and counterclockwise to
decrease. Adjustments should be made opening or
closing the valve by no more than ¼ turn at a time.
Allow the system to stabilize 15 to 20 minutes before
making additional adjustments if necessary.
4. After adjustments are complete replace cap on
adjustment stem and tighten 1/6 turn.
5. Remove gauges and check the Schrader ports for
leaks and tighten valve cores if necessary. Install caps






SUCTION PRESSURE SATURATED SUCTION
PSIG R-410A
50 1
52 3
54 4
56 6
58 7
60 8
62 10
64 11
66 13
68 14
70 15
72 16
74 17
76 19
78 20
80 21
85 24
90 26
95 29
100 31
110 36
120 41
130 45
140 49
150 53
160 56
170 60
SATURATED SUCTION PRESSURE
TEMPERATURE CHART

SUBCOOL FORMULA =

SUPERHEAT FORMULA =

10
LIQUID PRESSURE
SATURATED LIQUID
TEMPERATURE °F
PSIG R-410A
200 70
210 73
220 76
225 78
235 80
245 83
255 85
265 88
275 90
285 92
295 95
305 97
325 101
355 108
375 112
405 118
415 119
425 121
435 123
445 125
475 130
500 134
525 138
550 142
575 145
600 149
625 152
SATURATED LIQUID PRESSURE
TEMPERATURE CHART

8 Condensate Drain Lines
The coil drain pan has a primary and a secondary drain


be hand tightened to a torque of no more than 37 in-lbs. to
prevent damage to the drain pan connection. An insertion

expected at this torque.
1. Ensure drain pan hole is not obstructed.
2. To prevent potential sweating and dripping on to

condensate drain line located inside the building. Use

A secondary condensate drain connection has been
provided for areas where the building codes require it.

free drainage. Provide required support to the drain line to
prevent bowing.
If the secondary drain line is required, run the line
separately from the primary drain and end it where
condensate discharge can be easily seen.
NOTE: Water coming from secondary line means the
coil primary drain is plugged and needs immediate

CAUTION


Insulate drain lines located inside the building or above

condensate trap to ensure proper drainage.

in other locations where damage from condensate



The installation must include a “P” style trap that is located
as close as is practical to the evaporator coil. See Figure
12 for details of a typical condensate line “P” trap.
NOTE: Units operating in high static pressure



Air Handler
2.75" MI
N.
POSITIVE LIQUID
SEAL REQUIRED
AT TRAP
Connection
2" MIN.



please refer to the requirements listed in the Uniform

A drain trap in a draw-through application prevents air
from being drawn back through the drain line during fan
operation thus preventing condensate from draining, and
if connected to a sewer line to prevent sewer gases from
being drawn into the airstream during blower operation.
Use of a condensate removal pump is permitted when
necessary. This condensate pump should have provisions

occur. A trap must be installed between the unit and the
condensate pump.
11




Tip: Priming the “P” trap may avoid improper draining at
the initial installation and at the beginning of the cooling
season.
9 Ductwork
This air handler is designed for a complete supply and
return ductwork system.
CAUTION
DO NOT OPERATE THIS PRODUCT WITHOUT ALL THE

To ensure correct system performance, the ductwork is to
be sized to accommodate 350-450 CFM per ton of cooling
with the static pressure not to exceed 0.5” in w.c. Refer to
ACCA Manual D, Manual S and Manual RS for information
on duct sizing and application. Flame retardant ductwork
is to be used and sealed to the unit in a manner that will
prevent leakage.



9.1 Return Ductwork
DO NOT LOCATE THE RETURN DUCTWORK IN


 The return ductwork is to be connected to

10 Return Air Filters






may be performed at the air handler using the factory






11 Electric Heat
Refer to the installation manual provided with the electric
heat kit for the correct installation procedure. All electric

ONLY heat kits that are permitted to be used are the HKS
and HKTSD series. Refer to the air handler unit’s Serial

sheets to determine the heat kits compatible with a given
air handler. No other accessory heat kit besides the HKS
and HKTSD series may be installed in these air handlers.
The heating mode temperature rise is dependent upon the






Where: TR = Temperature Rise
kW = Heater Kit Actual kW
3412 = Btu per kW
  
   
   
1.08 = Constant
  
  











356810 15 19/20 25
800 12 19 23 31 37 56
1000 915 19 25 30 44
1200 812 15 21 25 37 49 62
1400 711 13 18 21 32 42 53
1600 6 9 12 15 19 28 37 46
1800 5 8 10 14 16 25 33 41
2000 57912 15 22 30 37
HEAT KIT NOMINAL kW
CFM


12
356810 15 19/20 25
800 11 18 22 30 35 54
1000 914 18 24 28 42
1200 712 15 20 24 35 47 56
1400 610 13 17 20 30 40 48
1600 6 9 11 15 18 27 35 42
1800 5 8 10 13 16 24 31 37
2000 47912 14 21 28 33
CFM
HEAT KIT NOMINAL kW


356810 15 19/20 25
800 10 17 21 28 33
1000 813 17 22 27 40
1200 711 14 19 22 33 45 56
1400 610 12 16 19 29 38 48
1600 5 8 10 14 17 25 33 42
1800 57912 15 22 30 37
2000 47811 13 20 27 33
CFM
HEAT KIT NOMINAL kW


Comfort Setting Menu Heater Kit Info
 There are 6 options
available in the Comfort Setting Menu which impacts
system target run time and electric heat functionality.
Electric heat operation adjustments only apply if a
communicating heat pump is installed. Comfort Setting
Options 1 – 5 have set values for the System Target
Runtime and option 6 enables additional menus to
customize all comfort settings. See list below for the


satisfy the thermostat slower or faster based on the
selection where option 1, with a 10 minute Target Runtime,
is attempting to satisfy much faster than option 5, with a 30
minute Target Runtime.
System Target Runtime:

Runtime

Runtime

Runtime

Runtime

Runtime
 This system will automatically
determine if the heat pump is capable of satisfying the
thermostat in the selected System Target Runtime. If the
heat pump is unable to satisfy in the selected time, electric
heat settings will determine how many attempts should be
given to the heat pump before temporarily locking it out
and using the furnace. These electric heat settings also
determine at what time the system should remove the
temporary heat pump lockout and run the heat pump again.
There are four adjustable items associated with back up
electric heat operation control. In the same way as the
System Target Time, each of these items have defaulted
values for Comfort Settings 1 – 5. Only when Comfort
Setting 6 is selected will each item be available for full
adjustment.
  This
is a value that determines how far past the target
runtime the system should continue running the
heat pump before transitioning to the furnace. For
example, assume this menu was set to 20% with a
target runtime of 20 minutes. If the thermostat did
not remove the heating call after 20 minutes, the
system would allow for an additional 20% heat pump


up electric heat after 24 minutes if the thermostat call
was still present. Each time this occurs, the system

strike is important when looking at the Over Target

  If the
heat pump has consecutively activated back up electric
heat for the selected Over Target Threshold amount
of times, meaning for this many consecutive cycles it
has been unable to satisfy the target time by itself, then
the heat pump will be temporarily locked out and the
furnace will become the primary heat source.
 
This only applies when the heat pump and back up
electric heat are activated on initial start-up. In this
case, the system will try to determine when the best
time to operate the heat pump individually again. To
determine this, the system looks at how easily the
air handler is able to satisfy the thermostat using the
heat pump with back up electric heat. Assume this
setting is 15% and the target time is 20 minutes If the
heat pump with back up electric heat can satisfy the




13
  If
the air handler is able to satisfy the thermostat using
the heat pump with back up electric heat for the
selected number of consecutive cycles the electric
heat operation will be temporarily removed. The heat
pump will then be used during the next cycle. If the
heat pump can satisfy the thermostat in less than the
System Target Runtime the back up heat operation
will be completely removed and the heat pump will
become the primary heat source again. If it fails to do
so, the strike count against the furnace will be reset
and the furnace will remain the temporary primary
heat source until the Under Target Threshold is
reached again.
The system will automatically make adjustments in an
attempt to satisfy the thermostat as close to this target
runtime as possible. After a power cycle or mode change


thermostat call. Based on the selected target runtime and
how long the initial cycle takes to satisfy the thermostat,
the control algorithm will adjust the system stage times for
a 2 stage unit or the capacity demand percentage for an
inverter / modulating unit for the next cycle. NOTE: actual
run times may change depending on variations of load
throughout the day.
The following table shows the default values for all Comfort

Comfort
Setti ng
Opti on
Target
Ti me
(Minutes)
Stage Up
Percentage
(%)
Stage Down
Percentage
(%)
Over Target
Threshhold
(Strike Count)
Under Target
Threshhold
(Strike Count)
110 20 20 210
215 20 20 4 8
320 20 20 6 6
425 20 20 8 4
530 20 20 10 2
The following table shows the ranges for each of item when
the adjustable Comfort Setting Option 6 is selected. The
table shows the minimum value, the maximum value and
the defaulted value. All items can be adjusted up or down





to 60 and make sure the other menus are set to match






356810 15 19 20 25
AMVT24BP14 550 650 700 800 850 875
AMVT30BP14 550 650 700 800 875 1050
AMVT36BP14 630 650 700 800 875 1050
AMVT36CP14 735 810 935 1020 1145 1345
AMVT42CP14 735 810 935 1020 1145 1345
AMVT48CP14 880 880 1045 1200 1420 1480
AMVT48DP14 1040 1170 1260 1300 1595 1595
AMVT60DP14 1135 1265 1375 1455 1815 1860 1925
HEATER KIT (Kw)
Model
14
Menu Minimum Value Maximum Value Default Value
Target Time (t9t) 1 minute 240 minutes 60 minutes
Stage Up Percent (SUP) 0% 100% 20%
Stage Down Percent (SdP) 0% 100% 20%
Over Target Threshold (Ott) 1 strike 254 strikes 20 strikes
Under Target Threshold (Utt) 1 strike 254 strikes 20 strikes
12 Electrical and Control Wiring



WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVIC-




WARNING
HIGH VOLTAGE!


AN 
THE ELECTRICAL GROUND CIRCUIT MAY CONSIST OF AN
APPROPRIATELY SIZED ELECTRICAL WIRE CONNECTING
THE GROUND LUG IN THE UNIT CONTROL BOX TO THE

OTHER METHODS OF GROUNDING ARE PERMITTED IF PER-
FORMED IN ACCORDANCE WITH THE NATIONAL ELECTRIC



GROUNDING IS TO BE IN ACCORDANCE WITH THE CANADI-

12.1 Building Electrical Service Inspection
This unit is designed for single-phase electrical supply
only. DO NOT OPERATE ON A THREE-PHASE POWER
SUPPLY. Measure the power supply to the unit. The supply
voltage must be measured and be in agreement with the
unit nameplate power requirements and within the range
shown.
12.2 Wire Sizing
Wire size is important to the operation of your equipment.
Use the following check list when selecting the appropriate
wire size for your unit.
• Wire used must carry the Minimum Circuit Ampacity


sizing. The unit MCA for the air handler and the
optional electric heat kit can be found on the unit
Series and Rating Plate.
• Wire must be sized to allow no more than a 2%
voltage drop from the building breaker/fuse panel to
the unit.

have varying ampacities - be sure to check the
temperature rating used
Refer to the latest edition of the National Electric Code or in
Canada the Canadian Electric Code when determining the
correct wire size.
12.3 Maximum Overcurrent Protection (MOP)


check with local or state codes for any special regional
requirements.
Protection can be in the form of fusing or HACR style
circuit breakers. The Series and Rating Plate provides the
maximum overcurrent device permissible.


Nominal
Input
Minimum
Voltage

Voltage
208-230 VAC 197 253


12.4 Electrical Connections – Supply Voltage
CAUTION
FIRE HAZARD!
-

IMPORTANT NOTE: Use copper conductors only from

Knockouts are provided on the air handler top panel and
sides of the cabinet to allow for the entry of the supply
voltage conductors, as shown in Figure 13. Separate
knockouts must be used for two circuit heat kits. Unless

on the cabinet sides are used for electrical conduit, an
adapter ring must be used in order to meet UL1995 safety
requirements. An NEC or CEC approved strain relief is
to be used at this entry point. Some codes/municipalities
require the supply wire to be enclosed in conduit. Consult
your local codes.
15
Side of
Cabinet
Top of
Cabinet


12.4.1 Air Handler Only (Non-Heat Kit Models)
IMPORTANT: Installation of Air Handler must follow any





The building supply connects to the stripped black and red
wires contained in the air handler electrical compartment
cavity. A ground screw is also contained in this area.
Attach the Supply wires to the air handler conductors as
shown in the unit wiring diagram using appropriately sized
solderless connectors or other NEC or CEC approved
means.
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits
A terminal block is provided with the HKS and HKTSD kit
to attach the power supply and air handler connections.
Follow the HKS and HKTSD Installation Manual and wiring
diagram for complete wiring details.
12.4.3 Air Handler With Circuit Breaker Heat Kit
The air handler has soft plastic cover on the upper access
panel and can be removed to allow the heater kit circuit
breaker to be installed. The circuit breakers have lugs
for power supply connection. See the HKS and HKTSD
Installation Instructions for further details.
12.5 Low Voltage Connections
Several combinations of low voltage schemes are possible,
depending on the presence of a heat kit and whether the
heat kit is single-stage or multi-stage, whether the outdoor
section is an air conditioner or heat pump, and whether
the outdoor section is single-stage or two-stage. The
24V-control voltage connects the air handler to the room
thermostat and condenser. Low voltage wiring must be
copper conductors. A minimum of 18AWG must be used
for installations up to 100 feet. Low voltage wiring must
be connected through the top of the cabinet or either side.
See the “Thermostat Wiring” section of this manual for
typical low voltage wiring connections.
12.5.1 Thermostats
Second-stage heat can be accomplished by a multi-stage
heating thermostat or the addition of an outdoor thermostat
as shown in wiring schematics on page 19. Follow the
thermostat manufacturer’s instructions for installation.
13 CoolCloud HVAC Phone Application









is no guarantee that interference will not occur in a





• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and
receiver.
• Connect the equipment into an outlet on a

connected.
• Consult the dealer or an experienced radio/ TV
technician for help.
16

device being used.

1234567890

This air handler is Bluetooth ready and functions with the
CoolCloud HVAC phone application designed to improve
the contractor’s setup / diagnostic experience. Users can

error codes, observe system menu testing of all operational

phone application is also capable of directly updating the
air handler software anytime updates are available. The
application will automatically notify the user.
NOTE: The software update may take up to 20 minutes

14 Quick Start Guide for Communication
Outdoor Units
EXTREMELY IMPORTANT: For all cooling calls
the system only requires a single Y input from the







outdoor unit and to control single stage electric heat




heat pump control or multistage control may result in

1. Connect all necessary thermostat wires to the
thermostat connector on the air handler control as
instructed by the applicable wiring diagrams shown in
this section.
2. Connect the 1 & 2 wires between the indoor and
outdoor unit for communicating operation.
NOTE: Verify two stage outdoor units include a

Two stage outdoor units may not behave properly
without this 24 VAC transformer.



3. Download the Cool Cloud HVAC phone application for

17

Communication Software and Air Handler Control





14.1 Charging
1. Two-stage outdoor units using the Cool Cloud HVAC
application:
a. Using the cooling icon after entering the outdoor
unit menus, energize the outdoor unit at 49%
capacity or lower.
b. Charge the outdoor unit as required using the
charging information provided with the outdoor
equipment.
15 Quick Start Guide for Non-Communicating
Outdoor Units
When setting up a ComfortBridge air handler for use
with a Non-Communicating outdoor unit you must





EXTREMELY IMPORTANT: For two stage electric heat

Internal algorithms will control staging automatically


1. Use the wiring diagrams on the next page to connect
low voltage thermostat wires.
NOTE: When installing the air handler with a non-
communicating heat pump, wire directly to the “O”
terminal on the non-communicating heat pump. See









18
2. Download the Cool Cloud HVAC phone application.
NOTE: When new versions of Bluetooth
Communication Software and Air Handler Control


optional or mandatory and installed by using the
phone application. Ensure all mandatory software
updates have been installed. Review notes for
optional software updates and install if necessary.
3. 
using the on board push buttons or the Cool Cloud
HVAC phone application. Select “” for single stage
Air Conditioners, “” for single stage Heat Pumps,
” for two stage Air Conditioners and “” for 2
stage Heat Pumps.
4. 

for the outdoor unit. See the following table.
NOTE: For the two stage non-communicating outdoor

stage operation.
Tonnage
Selecon Airow Tonnage
Selecon Airow Tonnage
Selecon Airow Tonnage
Selecon Airow
1 400 2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160 4.2 1680 5.5 2200
1.7 680 3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1440 4.8 1920



NOTE:
1. 
place.
2. The cooling/heat pump speed tap should be selected
based on the AHRI rating. Otherwise, select a speed
tap that provides a minimum 350 CFM per outdoor
ton. For satisfactory operation, external static
pressure must not exceed 0.5” WC.
EXAMPLE: For a 2 ton outdoor, 1.6T 10% trim is the


1.5 22.5 33.5 4 5
Minimum
Cooling/Heating CFM
@ .5" WC ESP
525 700 875 1050 1225 1400 1750
Outdoor Unit Tonnage

3. Use the CFM adjustment factors of 0.98 for horizontal

orientations.
Model 
AMVTC25B14
AMVTC29B14
AMVTC35B14
AMVTC37B14
1200
AMVTC33C14 1300
AMVTC31C14
AMVTC37C14
AMVTC39C14
1600
AMVTC37D14
AMVTC49C14
1800
AMVTC49D14
AMVTC59C14
1900
AMVTC59D14
AMVTC61D14
2100

4. Use the Cool Cloud HVAC phone application to
air handler operations.
NOTE: The phone application cannot test a non-
communicating outdoor unit 

15.1 Electric Heater Kit Testing
1. Select the electric heat icon after entering the air
handler menus while using the Cool Cloud phone
application.
2. Select any value less than 50% for low stage
operation and any value greater than 50% for high
stage operation.
3. 
properly for high stage operation.
MODEL NAME MAX CFM
AMVT24BP1400 1275
AMVT30BP1400 1450
AMVT36BP1400
AMVT36CP1400 1575
AMVT42CP1400
AMVT48CP1400 1700
AMVT48DP1400 1800
AMVT60DP1400 2200

19


blower to operate at a reduced speed during a combined

from the thermostat or humidistat. This lower blower

as it passes through the indoor coil. The control board

located on the thermostat wiring connector. The terminal

input is energized or de-energized. When using an external
dehumidistat, connect it between the R and DH terminals.
If the humidistat closes on humidity rise or the thermostat

” using
the push buttons or Cool Cloud HVAC phone application.
If the humidistat opens on humidity or the thermostat de-

set the Dehum Logic Menu to “” using the push buttons
or Cool Cloud HVAC phone application.

The control is equipped with a 24VAC Aux Alarm to be


connected AUX switch is normally closed and opens when
the water level in the evaporator coil base pan reaches
an undesirable level. The control responds by displaying
a “
unit. If the AUX switch is detected to be in the closed
position for 30 seconds, normal operation resumes and the
error message is no longer displayed.
18 Start-Up Procedure

The air handler includes three on-board push buttons
allowing users to navigate indoor and outdoor system
menus. The Right and Left buttons allow the user to
scroll through the main menus and to then scroll through

is used to enter into a main menu and to then permanently
select options within those menus.
NOTE: After scrolling to the desired option within a










function properly.
1. Make sure the installed 24VAC thermostat is capable
of controlling the accessory or accessories.
2. Connect the appropriate accessory control wires
to the accessory devices from the thermostat


3. If the thermostat is capable of providing a continuous

Make sure to connect the thermostat G terminal to
the G terminal on the indoor unit. Setup thermostat
to ensure G signal is energized during accessory
operation.

4. 
accessory using the indoor unit push button menus or
the Cool Cloud HVAC phone application.
5. Using the thermostat, independently test each
accessory in addition to the independently testing
continuous fan mode.
20
Key Mitigations:
1. Full featured TS (dehum & overcool)
2. Connect G and dehum wire correctly
3. Dehumidistat
1) Install Dehum wire
and DO NOT install G
Wire
2) Install Dehumidistat
in living space or
return duct
Is there a setting in the
thermostat to enable
Dehum without fan? (G)
Yes
No
During a call for Dehum,
does the thermostat
provide 24V to Dehum, Y,
and G?
Yes No
Choose that setting
Wire the system and test
functionality
Yes No
Wire the system and
test functionality
Dehumidification Control Options
Dry Environment
Yes No
Install any 24VAC
thermostat on the
market - Use Y, W, G
signals
Thermostat has a Dehum or
Configurable terminal with
Dehum option
Yes
No
Does your thermostat have a
whole house Dehumidifier
setting?
Install Dehumidistat in
living space or return
duct
If the Dehumidistat
opens on a rise on
humidity, then you
will set Dehum logic
to Low via Coolcloud
app or push buttons
If the Dehumidistat
closes on a rise in
humidity, then you
will set Dehum logic
to High via Coolcloud
app or push buttons
Thermostat only sends Dehum + G on a
call for Dehum
A Dehumidistat needs to be installed in
the living space or return duct
If the Dehumidistat opens
on a rise on humidity,
then you will set Dehum
logic to Low via Coolcloud
app or push buttons
If the Dehumidistat closes on
a rise in humidity, then you will
set Dehum logic to High via
Coolcloud app or push buttons

  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32