PQL-556178WEM

Superior Life PQL-556178WEM User manual

  • Hello! I'm an AI assistant that has analyzed the provided installation instructions for the PQL LED SPEC-SELECT Wrap with 8W EM Battery. This document covers various aspects of installation, including surface mounting, chain mounting, electrical connections, and safety precautions. It also highlights the adjustable wattage and color temperature settings. I'm ready to answer any questions you have about this product based on the document.
  • How can I adjust the color temperature of the light?
    How can I adjust the output power (Wattage) of the light?
    What type of locations is this luminaire suitable for?
    What should I do before wiring the fixture to the power supply?
LED SPEC-SELECT™ WRAP WITH 8W EM BATTERY
INSTALL INSTRUCTIONS
PREMIUM QUALITY LIGHTING® • www.PQLighting.com
© P.Q.L., Inc. • 2285 Ward Avenue • Simi Valley, CA 93065 • 800-323-8107
Specifications subject to change without notice. Photos and line
drawings may not be to scale and are for general reference only.
!WARNING DISCONNECT POWER BEFORE INSTALLING OR SERVICING.
PLEASE FIND A QUALIFIED ELECTRICIAN FOR INSTALLATION. Please read
the instructions before you install and use the luminaire.
WARNING, CAUTIONS AND OPERATING INSTRUCTIONS
To reduce the risk of death, personal injury or property damage from fire,
electric shock, falling parts, cuts/abrasions, and other hazards read all
warnings and instructions included with and on the fixture box and all
fixture labels.
Before installing, servicing, or performing routine maintenance upon this
equipment, follow these general precautions.
Commercial installation, service and maintenance of luminaires should be
performed by a qualified licensed electrician.
For the installation: If you are unsure about the installation or maintenance
of the luminaires, consult a qualified licensed electrician and check your
local electrical code.
To prevent wiring damage or abrasion, do not expose wiring to edges of
sheet metal or other sharp objects.
Do not make or alter any open holes in an enclosure of wiring or electrical
components during kit installation.
WARNING: RISK OF FIRE OR ELECTRICAL SHOCK
Turn o electrical power at fuse or circuit breaker box before wiring fixture
to the power supply.
Turn o the power when you perform any maintenance.
Verify that supply voltage is correct by comparing it with the luminaire
label information.
All wiring connections should be capped with UL approved wire
connectors.
CAUTION: RISK OF INJURY
Avoid direct eye exposure to the un-louvered light source while it is on.
Account for small parts and destroy packing material, as these may be
hazardous to children.
Risk of burn. Disconnect power and allow fixture to cool before handling
fixture.
Green ground screw provided in proper location. DO NOT RELOCATE.
Minimum 90° supply conductors.
Suitable for Dry or Damp locations.
SURFACE MOUNTING
1. Remove lens and loosen fasteners at both ends of the top enclosure.
2. Make electrical connections according to the general wiring diagram
and local electrical codes through the Concealed Outlet Box. (Fig. 1)
3. Mount luminaire to surface with self tapping screws, use the mounting
holes on each end of the fixture housing. (Fig. 2)
4. Replace top enclosure and lens. Check to make sure the lens is
completely secure along the entire length of the fixture.
FIELD ADJUSTABLE WATTAGE & CCT
The end users may adjust the color temperature and lumen output,
respectively, by the two slide switches integrated into the side of the
fixture. Each switch has 3 options (left, middle and right ), each position
corresponds to 1 of 3 color temperatures (Warm White, Cool White, and
Sky-Brite®) and 1 of 3 wattages, which can be adjusted to the desired
combination.
Default Settings: 40W, 5000K
Switches are located on the side of the fixture. (Fig. 3)
Select a wattage and color temperature
by sliding switch left or right
respectively to the desired value. (Fig. 3)
Fixture Housing
Self-Tapping Screws
Safety Cable
Top Enclosure
Lens
Fig. 2
Concealed
Outlet Box
Fig. 1
Mounting Holes
GENERAL WIRING DIAGRAM
LED DRIVER
Black (Line)
White (Neutral)
Green (Ground)
TO SOURCE
120-277V
Purple (Dim+)
Grey (Dim-)
Blue (-)
Red (+)
Lead wires
to LED Load
** Dimming wires to
0-10V IEC Compliant
Control
Fig. 3
CCT Switch
Wattage Switch
3500K - 5000K 40W 35W 30W
Concealed Outlet Box
Fastener
LED SPEC-SELECT™ WRAP WITH 8W EM BATTERY
INSTALL INSTRUCTIONS
PREMIUM QUALITY LIGHTING® • www.PQLighting.com
© P.Q.L., Inc. • 2285 Ward Avenue • Simi Valley, CA 93065 • 800-323-8107
Specifications subject to change without notice. Photos and line
drawings may not be to scale and are for general reference only.
Hasp
CHAIN MOUNTING WITH V-HOOK (Sold Separately):
1. Mount V-Hooks to the luminaire. (Fig. 4)
2. Make electrical connections according to the General Wiring
Diagram and local electrical codes.
3. Hang luminaire up with chain.
!WARNING DISCONNECT POWER BEFORE INSTALLING OR SERVICING.
Fig. 4 Fig. 5
Flexible Metallic
Conduit Flexible Metallic
Conduit
CABLE MOUNTING (Sold Separately):
1. Mount cable to the luminaire. Wrap one end of cable to the beam,
then insert into the hasp, adjust the cable to the desired height.
(Fig. 5)
2. Make electrical connections according to the General Wiring
Diagram and local electrical codes.
V-Hook
/