White Rodgers WHITE-RODGERS 25M01A-100 Dryer Gas Valve User manual

Type
User manual
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.
Operator: Save these instructions for future use!
DESCRIPTION
SPECIFICATIONS
CONTENTS
Description ......................................................................... 1
Specifications ..................................................................... 1
Model Description .............................................................. 2
Precautions ........................................................................ 2
Installation .......................................................................... 2
Adjustment ........................................................................... 3
Lighting Instructions ............................................................ 4
DoC ..................................................................................... 5
Notes ................................................................................6-8
The 25M series gas control is a compact, multifunctional
valve, with a direct-acting regulator ideal for use in pilot valve
applications, thru-the wall heaters, RV heaters, gas clothes
dryers, hearth products, radiant heat systems, water heaters,
cooking applications, agricultural heaters/ dryers, or other
high-efficiency equipment. The 25M valve, provided with a
straight inlet, has various outlet configurations
that, when coupled with the various pipe sizes available,
make for easy adaptation to a given application.
Optional features, such as the inlet pressure tap, increase the
flexibility in adapting this valve.
Available configurations include:
Appliance (Series valve is a combination gas pressure
regulator and dual
automatic gas valve. These valves are designed for use on
gas clothes dryers.)
Manifold (The manifold type 25M series valve is a
combination gas pressure regulator and redundant
automatic gas valve. Two-Stage version (for applications
requiring both high-fire and low-fire settings)
Quiet-Type (series manifold gas valve is typically a
combination of gas pressure regulator and dual automatic
gas valve suitable for applications requiring EN approval.)
25M Gas Controls
25M Type Appliance, Manifold, Quiet-Type and Second Stage
INSTALLATION INSTRUCTIONS
Specifications
Type of Gas Natural Gas or LP Gas
Pressure Regulator
Setting
Nat. Gas - 2.5” to 5.4” W.C.
LP Gas - 8.5"to 12" W.C.
Range of Regulations Nat. Gas - 5,000 to 65,000 BTU/hr
LP Gas - 8,000 to 104,000 BTU/hr
General Ratings
Functions incorporated
in control Two shut-off valves and a regulator
Gas families 2nd and 3rd Family (conversion kit
required)
Permissible mounting
attitude(s)
Horizontal ± 90° or vertical. Not
upside down.
Operating temperature
range 0°C to 80°C
Maximum working
pressure 50 mbar
Inlet connection type
& size Female NPT or Rp in 3/8” or 1/8” sizes
Outlet connection type
& size Female NPT or Rp 3/8” or 1/8” sizes
Governor Ratings
Class of governor Class C
Inlet pressure range 6 to 50 mbar
Outlet pressure range 6 to 11 mbar
Rated flow range 0.76 m3/h (dP = 2.5mbar)
Automatic Shut-off Valve Ratings
Class of valve Class B + Class B
Rated voltage of valve 12V DC, 24V DC, 24V AC or 240V
AC (50/60Hz)
Opening time < 1sec
Closing time < 1sec
PART NO. 37-7849001
2127
emerson.com/white-rodgers
2
PRECAUTIONS
MODEL DESCRIPTION
Family Description Voltage Current
Ambient
Temperature
Application
Inlet Connection Outlet
Connection
25M05V Two-Stage Manifold 12 DC 0.73 mA (-40°F to 175°F) 3/8” NPT female 3/8” BSP female
25M01A Appliance 120 60Hz 0.07 mA (32°F to 175°F) 3/8” NPT female 1/8” NPT female
25M11B Appliance except 50
mbar rating 120 50Hz 0.07 mA (32°F to 175°F) 3/8” NPT female 1/8” NPT female
25M51A Appliance except
converted for LP use 120 60Hz 0.07 mA (32°F to 175°F) 3/8” NPT female 1/8” NPT female
25M42S Manifold Quiet - Type 220/240
50/60 Hz 0.06/.05 mA (32°F to 175°F) 3/8” BSP female 3/8” BSP female
25M02V Manifold 12 DC 0.48 mA (32°F to 175°F) 3/8” BSP female or
3/8” NPT female 3/8” BSP female
25M12 Manifold 24 50/60 Hz 0.070/.060 mA (-40°F to 175°F) 3/8” BSP female or
3/8” NPT female 3/8” BSP female
25M42M Manifold Quiet - Type 220/240 DC 0.06/.05 mA (32°F to 175°F) 3/8” BSP female or
3/8” NPT female 3/8” BSP female
25M51B Appliance except
converted for LP use 120 50Hz 0.07 mA (32°F to 175 °F) 3/8” NPT female 1/8” NPT female
INSTALLATION
1. Before attempting to service device, unplug power
cord, turn off main gas supply and consult device
manufacturer's instructions for accessing gas valve.
2. Disconnect gas line form the device.
3. Remove the access panel if is need it as the
manufacturer’s instructions indicate it.
4. The gas valve/burner assembly should now be visible.
5. Disconnect the wiring harness from gas valve. If the gas valve is not using fitting and orifice
screw go to step 15. (see figure 1)
6. Remove screw(s) fastening the mounting bracket.
7. Remove the gas inlet pipe as Manufacturer’s instructions
indicate it.
8. The gas valve should now be free to slide out of burner
and off of mounting bracket. Take care not to disturb the
air shutter.
CAUTION
!
WARNING
!If you do not follow these instructions exactly, a fire or explosion may
result, causing property damage, personal injury or loss of life.
DO NOT BEGIN INSTALLATION UNTIL YOU READ THE
FOLLOWING PRECAUTIONS.
1. Failure to turn off electric or main gas supply to
clothes dryer could cause personal injury and/or
property damage by shock, gas suffocation, fire,
and/or explosion.
2. Do not use this control on circuits exceeding
specified voltage. Higher voltage will damage the
control and may cause shock or fire hazard.
3. NEVER USE FLAME OR ANY KIND OF SPARK TO
CHECK FOR GAS LEAKS–COULD CAUSE FIRE
AND/OR EXPLOSION.
4. Do not use a control set for natural gas with LP gas,
or a control set for LP gas with natural gas. Personal
injury and/or property damage, gas suffocation, fire,
and/or explosion may result.
1. Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring can cause
equipment damage, property damage, and/or
personal injury.
2. This control is not intended for use in locations
where it may come in direct contact with water.
Suitable protection must be provided to shield the
control from exposure to water (dripping, spraying,
rain, etc.).
3
ADJUSTMENT
Figure 1
Regulator block
Open plug
INSTALLATION
9. Remove inlet fitting from old gas valve and set it aside.
Take care not to damage the sealing surfaces. This part
could be reused (if is need it).
10. Clean the threads of the inlet fitting. Apply pipe sealant
(approved for all gases) to the threads. Install the fitting into
the inlet of the new valve and tighten to 200 lbf-in (16.6 lbf-
ft) using a 3/8 inch hex head wrench (if it is needed).
11. Remove orifice screw from old gas valve and set it aside.
Take care not to damage the sealing surfaces. This part
will be reused.
12. Inspect the threads of the orifice screw and clean if
necessary.
13. Inspect the orifice hole and remove any foreign material.
Install orifice screw into new valve and tighten to 40 lbf-in.
Do not use any pipe sealant.
14. Slide the outlet boss of the new valve into the burner. Take
care not to disturb the air shutter.
15. Fasten the gas valve to the mounting bracket using the
screw(s) removed earlier.
16. Connect the gas inlet pipe to the inlet fitting by threading
the union together and tightening to 150 lbf-in (12.5 lbf-ft).
17. Reconnect the wiring harness to the gas valve.
18. Apply pipe sealant to the threads of the inlet gas pipe and
reconnect the gas line to the device.
19. Turn on gas supply and Check for leaks.
20. Remove the outlet pressure tap from the gas valve (see
figure 2). Apply pipe sealant to the 1/8-inch NPT threads
of a hose barb. Install the hose barb into the outlet
pressure tap and tighten to 40 lbf-in (see figure 3).
Outlet Pressure
Tap (Plugged)
The orientation
could depend of the
Gas Valve model
Figure 2
Hose Barb Installed
in Outlet Pressure
Ta p
Figure 3
21. Connect a manometer to the hose barb. Manometer
should be capable of measuring pressure from 2.5" WC
up to 14.0" WC.
22. Plug dryer power cord into electrical socket.
23. Energize device and verify ignition. Also observe the
reading on the manometer. It should read the same outlet
pressure as stated on the rating plate on the old gas
valve. If it does not, see section on Pressure Regulator
Adjustment.
24. De-energize the dryer.
25. Remove the hose barb.
26. Apply pipe sealant to the 1/8 inch NPT used hex pipe
plug. Install the 1/8 inch NPT hex pipe plug into the outlet
pressure tap and tighten 40 lbf-in. (Could find BSP thread
depending of the model)
27. Check for leaks.
28. Reinstall the cover of the device if it is needed.
PRESSURE REGULATOR
ADJUSTMENT
This control was shipped from the factory with the regulator
set as specified on the control label. Consult the appliance
rating plate to ensure burner manifold pressure is as specified.
If outlet pressure adjustment is required, follow these steps.
NOTE
If a valve has been factory-adjusted for the 2.5 to 5 inches W.C.
range, it cannot be field-adjusted outside that range. This is
also true for valves adjusted to the 7.0 to 12 inches W.C. range
for LP gas.
4
Regulator
Adjustment
Tower
Hose Barb
Installed
Regulator Cover
Screw
Plastic Adjust Scre
w
Regulator Spring
Figure 5
Figure 4
1. Unplug power cord to the appliance.
2. Slide device away from wall.
3. Close manual shut-off valve for device, if none present, shut off gas supply line where it enters the building.
A. This appliance does not have a pilot. It is equipped with an
ignition device which automatically lights the burner. Do not
try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
FOR YOUR SAFETY
“WHAT TO DO IF YOU SMELL GAS”
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instruc-
tions.
• If you cannot reach your gas supplier, call the
fire department.
C. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of
the control system and any gas control which has
been under water.
WARNING
!If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
LIGHTING INSTRUCTIONS
ADJUSTMENT
If your valve has a regulator blocked open (see
figure 1) it is a non-regulable valve.
1. Unplug dryer power cord.
2. Attach a hose and manometer to the hose barb in the tap
of the valve (see figure 4).
3. Turn on system power and energize valve.
4. Remove regulator cover screw and turn regulator
adjust screw clockwise ( ) to increase pressure,
or counterclockwise ( ) to decrease pressure
(see figure 5). Always adjust regulator to provide the
correct pressure according to the original equipment
manufacturer’s specifications listed on the appliance
rating plate.
5. Replace regulator cover screw and tighten securely.
6. Turn off all electrical power to the system.
7. Remove manometer hose from outlet pressure hose barb.
8. Remove hose barb and replace plug. Use pipe sealant.
9. Plug in power cord.
10. Using a leak detection solution, check for leaks at
pressure boss screw. Bubbles forming indicate a leak.
SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.
5
Supplier Declaration of Conformity (DoC)
8100 West Florissant Ave.
PO Box 36922
St. Louis, Missouri, 63136, USA 2797
Declared under our sole responsibility for the equipment:
Multi-Functional Control (Fitting)
Certicate Numbers:
CE 686924 (type examination), valid until 2028-06-20
CE 594168 (production surveillance)
Is conformal to the following directives and standards:
BS EN126: 2012 Multifunctional controls for gas burning appliances
BS EN13611:2007 +A2: 2011 Group 1 or Group 2 device
Essential requirements of the Gas Appliances Regulation 2016/426 and is manufactured in accordance with the
harmonized European standards.
Notifying Body:
BSI Group, The Netherlands B.V., number 2797
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above
referenced standards and meets all essential requirements of the specied directives:
Signed:
Steve DeRousse, Labs and Agency Coordinator
Manufacturing Location: Termotec de Chihuahua, Calle Pelicano No. 5500, Colonia Arboledas,
Chihuahua, Chihuahua, 31110, Mexico
Model Designation
25M42S-020 25M51B-101 25M01A146 25M11B149 25M11B146 25M01A149 25M01A157
25M51A102 25M42M-006 25M42S-013 25M05V-501 25M02V-1 25M02V-2 25M02V-3
25M05V-706 25M12-712 25M12-713 25M12-714 25M12-715 25M12-751 25M42M-002
6
NOTES
7
NOTES
emerson.com/white-rodgers
Emerson and White-Rodgers are
trademarks of Emerson Electric Co.
©2021 Emerson Electric Co.
All rights reserved.
TECHNICAL SUPPORT: 1-888-725-9797