Input:
• 120VAC,60Hz,3.5amp.
• Inputfuse:5A/250V.
Output:
• 12VDCor24VDCselectableoutput.
•12VDCor24VDC@2.0ampsupplycurrent.
• Power-limitedoutput.
• AuxiliaryPower-Limitedoutput
rated@1amp(unswitched).
• OverVoltageProtection.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent1.54amp.
• Automaticswitchovertostand-bybatterywhen
ACfails.Transfertostand-bybatterypoweris
instantaneouswithnointerruption.
Supervision:
• ACfailsupervision(form“C”contacts).
• Batteryfail&presencesupervision
(form“C”contacts).
• Lowpowershutdown.ShutsdownDCoutputterminals
ifbatteryvoltagedropsbelow71-73%for12Vunits
and70-75%for24Vunits(dependingonthepower
supply).Preventsdeepbatterydischarge.
Fire Alarm Disconnect:
• SupervisedFireAlarmdisconnect(latchingor
non-latching)10KEOLresistor.Operatesona
normallyopen(NO)ornormallyclosed(NC)trigger.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• BTU/Hr.:
12VDC:12.28BTU/Hr.
24VDC:24.57BTU/Hr.
• SystemACinputVArequirement:420VA.
Visual Indicators:
• GreenACPowerLEDindicates120VACpresent.
• ACinput,DCoutputandBatteryLEDindicators.
Additional Features:
• Shortcircuitandoverloadprotection.
• Unitiscompletewithpowersupply,enclosure,
batteryleadsandcamlock.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
13.5”(342.9mm)x13”(330.2mm)x3.25”(82.55mm)
- Accommodatesuptotwo(2)12VDC/7AHbatteries.
• Productweight(approx.):8.5lbs.(3.86kg).
• Shippingweight(approx.):9.4lbs.(4.26kg).
Specifications
eFlow3Nisapowersupply/chargerthatconvertsa120VAC,60Hzinputintoa
single12VDCor24VDCClass2Ratedpower-limitedoutput.
eFlow3N
Power Supply/Charger
Rev.DSeFlow3N_01042013
Overview
Agency Approvals
UL294 ULListedforAccessControl
SystemUnits.
UL603 ULListedforPowerSupplies
forUsewithBurglar-Alarms
Systems.
UL1481 ULListedforPowerSupplies
forFireProtectiveSignaling
Systems.
eFlow3N
ULC-S318-96-PowerSuppliesfor
BurglarAlarmSystems.Alsosuitablefor
AccessControl.
CSFM-CaliforniaStateFire
MarshalApproved.
Altronix Corp.
140 58th St. Brooklyn, NY