Assa Abloy LCU9016III Quick Manual

Type
Quick Manual

Assa Abloy LCU9016III is a versatile and feature-rich device that offers a wide range of possibilities for access control and security management. With its Ethernet connectivity, you can easily integrate it into your existing network infrastructure, allowing for remote monitoring and control. The RS232 port provides an additional option for communication, giving you flexibility in your setup.

The LCU9016III features a tamper connection, ensuring that any unauthorized attempts to access the device are immediately detected. The WDOG relay provides an extra layer of security by automatically resetting the system in case of a malfunction.

Assa Abloy LCU9016III is a versatile and feature-rich device that offers a wide range of possibilities for access control and security management. With its Ethernet connectivity, you can easily integrate it into your existing network infrastructure, allowing for remote monitoring and control. The RS232 port provides an additional option for communication, giving you flexibility in your setup.

The LCU9016III features a tamper connection, ensuring that any unauthorized attempts to access the device are immediately detected. The WDOG relay provides an extra layer of security by automatically resetting the system in case of a malfunction.

Quick guide LCU9016III
__________________________________________________________________________________
LH5590163910A
DIP- nr.
Funktion (ON / OFF)
1
ON: I läge ON kan man via serieporten kommunicera med undercentralen med ett
terminalprogram med inställningarna 115200 bps, 8 bitar, ingen paritet, en
stoppbit och ingen flödesreglering.
OFF: Terminalkommunikationen avstängd och serieporten kan användas för att
exempelvis ansluta ett modem. (Normal drift)
2
Används ej, ska vara OFF.
3
ON: Installationstest av dörrmiljö.
Öppnarknappen fungerar och kodsymbolen på läsaren tänds. Fyra valfria
sifferknappar eller ett kort av rätt typ tänder rött och summern ljuder.
OFF: Normal drift.
4 & 5
Används ej, ska vara OFF.
6
ON: Aktiverar telnet på undercentralen.
OBS! I första hand rekommenderas att all konfiguration av undercentralen görs
med ett terminalprogram via serieporten.
OFF: Normal drift.
7
ON: Fast IP-adress för konfigurering. 192.168.1.250
OFF: Normal drift.
8
ON: Rensar databasen på LCU9016 vid uppstart och återställer LCU9016 till
fabriksinställningar.
OBS! Om detta görs kommer LCU9016 förlora alla inställningar och ny
information måste laddas ut till LCU9016.
OFF: Normal drift.
LED
Blå [WDOG]
Blinkar långsamt (0,5 Hz) under tiden som systemet håller på att startas upp.
Blinkar fort (5 Hz) när undercentralen är igång
Gul [A]
Lyser med fast sken när undercentralen har kontakt med ARX-servern
Röd [B]
Lyser när undercentralen har meddelanden att sända till ARX-servern
Grön [C]
Lyser när undercentralen tar emot meddelanden från ARX-servern
Röd [D]
Normalt släckt.
RS232
Ethernet
DIP
Power 17-24V AC/DC
Tamper connection
Ethernet LED
WDOG Relay
USB for
MIO/MIO-Slave card
Quick guide LCU9016III
__________________________________________________________________________________
LH5590163910A
Anslutning av bandkablar mellan CPU kort och Loop kort
Connecting the ribbon cables between the CPU card and Loop Card
DIP- nr.
Function (ON / OFF)
1
ON: ON position, you can via the serial port communicate with the LCU with a
terminal program with settings 115200 bps, 8 bits, no parity, one stop bit and no
flow control.
OFF: The communication terminal off and the serial port can be used for example to
connect a modem. (Normal operation)
2
Not used, must be OFF.
3
ON: Installation testing of door environment.
RTE works and PIN LED on the reader lights up. Four any number key or a card
of the correct type lights red and the buzzer sounds.
OFF: Normal operation.
4 & 5
Not used, must be OFF.
6
ON: Enable Telnet on the LCU.
NOTE: It is recommended that all configuration of the LCU is done with a
terminal program via the serial port.
OFF: Normal operation.
7
ON: Fixed IP address for configuration. 192.168.1.250
OFF: Normal operation.
8
ON: Clears the database at startup and resets LCU9016 to factory settings.
NOTE: If this is done, The LCU lose all settings and new information must be
down loaded to LCU.
OFF: Normal operation.
LED
Blue
[WDOG]
Slow flashing (0.5 Hz) while the system is booted.
Flashes fast (5 Hz) when the LCU is running
Yellow
[A]
Lit when the LCU is in contact with the ARX-server
Red
[B]
Lights when the LCU has messages to send to the ARX-server
Green
[C]
Lights when the LCU receives messages from the ARX-server
Red
[D]
Normally off.
9016C CPU
9014LC
CN1
J1
CN2
J2
CN3
J4
9014LC
4014LC
J3
CN1
9016C CPU
9019EM
CN1
J4
CN2
J2
CN7
J1
9019EM
9018ES
J5
J5
J3
J3
9014LC
9019EM
  • Page 1 1
  • Page 2 2

Assa Abloy LCU9016III Quick Manual

Type
Quick Manual

Assa Abloy LCU9016III is a versatile and feature-rich device that offers a wide range of possibilities for access control and security management. With its Ethernet connectivity, you can easily integrate it into your existing network infrastructure, allowing for remote monitoring and control. The RS232 port provides an additional option for communication, giving you flexibility in your setup.

The LCU9016III features a tamper connection, ensuring that any unauthorized attempts to access the device are immediately detected. The WDOG relay provides an extra layer of security by automatically resetting the system in case of a malfunction.