RTA 515RTAENI-N34 Product User Manual

Category
Networking
Type
Product User Manual
515RTAENI-N34
Protocol Gateway
Product User Guide
Firmware Version 4.02
Real Time Automation, Inc.
2
1-800-249-1612
Trademarks
CompactLogix, ControlLogix, & PLC-5 are registered trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of the
ODVA. MicroLogix, RSLogix 500, SLC, and PanelView are trademarks of Rockwell Automation, Inc. Microsoft, Windows, and
Internet Explorer are registered trademarks of Microsoft Corporation. Kepware is a registered trademark of Kepware
Technologies, a software development business of PTC Inc. All other trademarks and registered trademarks are the property of
their holders.
Limited Warranty
Real Time Automation, Inc. warrants that this product is free from defects and functions properly.
EXCEPT AS SPECIFICALLY SET FORTH ABOVE, REAL TIME AUTOMATION, INC. DISCLAIMS ALL OTHER WARRANTIES, BOTH
EXPRESSED AND IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR AN
APPLICATION. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS, WHICH VARY
FROM STATE TO STATE.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any application, Real Time Automation, Inc. cannot assume responsibility or liability for actual use
based on the examples and diagrams. Except as specifically set forth above, Real Time Automation and its distributors and
dealers will in no event be liable for any damages whatsoever, either direct or indirect, including but not limited to loss of
business profits, income, or use of data. Some states do not allow exclusion or limitation of incidental or consequential
damages; therefore, the limitations set forth in this agreement may not apply to you.
No patent liability is assumed by Real Time Automation with respect to use of information, circuits, equipment, or software
described in this manual.
Government End-Users
If this software is acquired by or on behalf of a unit or agency of the United States Government, this provision applies: The
software (a) was developed at private expense, is existing computer software, and was not developed with government funds;
(b) is a trade secret of Real Time Automation, Inc. for all purposes of the Freedom of Information Act; (c) is “restricted
computer software” submitted with restricted rights in accordance with subparagraphs (a) through (d) of the Commercial
“Computer Software-Restricted Rights” clause at 52.227-19 and its successors; (d) in all respects is proprietary data belonging
solely to Real Time Automation, Inc.; (e) is unpublished and all rights are reserved under copyright laws of the United States.
For units of the Department of Defense (DoD), this software is licensed only with “Restricted Rights”: as that term is defined in
the DoD Supplement of the Federal Acquisition Regulation 52.227-7013 (c) (1) (ii), rights in Technical Data and Computer
Software and its successors, and: Use, duplication, or disclosures is subject to restrictions as set forth in subdivision (c) (1) (ii) of
the Rights in Technical Data and Computer Software clause at 52.227-7013. If this software was acquired under GSA schedule,
the U.S. Government has agreed to refrain from changing or removing any insignia or lettering from the Software or
documentation that is provided or from producing copies of the manual or media. Real Time Automation, Inc.
© 2017 Real Time Automation, Inc. All rights reserved.
Real Time Automation, Inc.
3
1-800-249-1612
Contents
Revision History ............................................................................................................................................ 5
Overview ....................................................................................................................................................... 7
Hardware N34 ............................................................................................................................................ 8
Mounting....................................................................................................................................................... 9
Installing ................................................................................................................................................ 9
Removing .............................................................................................................................................. 9
Powering the Gateway ................................................................................................................................ 10
Pinouts & Wiring ......................................................................................................................................... 11
Pinouts ................................................................................................................................................ 11
Wiring 11
Accessing the Main Page............................................................................................................................. 12
Error: Main Page Does Not Launch 13
Web Configuration Tabs ............................................................................................................................. 14
Committing Changes to the Gateway ......................................................................................................... 15
Network Tab ................................................................................................................................................ 16
Ethernet Settings 16
Changing from DHCP to Static IP 17
Additional Fields under Ethernet Settings .......................................................................................... 17
Serial Settings 18
Email Settings 19
Email Alarms and Messages 20
Email Message Example ...................................................................................................................... 21
Data View Tab ............................................................................................................................................. 22
Mapping Tab ............................................................................................................................................... 23
Utility Tab .................................................................................................................................................... 25
Export/Import Configuration 25
Import Configuration .......................................................................................................................... 25
Export Configuration ........................................................................................................................... 25
Restart Gateway 26
Upgrade Firmware 26
EtherNet/IP EDS File 26
Real Time Automation, Inc.
4
1-800-249-1612
Other References 26
Reference Links ................................................................................................................................... 26
NET ENI Event Log Values ................................................................................................................... 27
Security Configuration 28
Home Tab (Diagnostics) .............................................................................................................................. 30
Msg Log Tab ........................................................................................................................................ 30
DF1 Status 31
DF1 Counters ....................................................................................................................................... 31
Serial Diagnostic Tab ........................................................................................................................... 32
Ethernet Status 33
Ethernet Status: Counters ................................................................................................................... 33
Ethernet Diagnostics Tab .................................................................................................................... 34
LED Behavior 35
DF1 Node Descriptions Reference Table 36
Easily replace an existing NETENI device 39
Using RSLinx and RSLogix 40
EtherNet/IP Driver .............................................................................................................................. 40
Ethernet Driver ................................................................................................................................... 43
Troubleshooting RSLinx and RSLogix Comms ............................................................................................. 44
Application Specific Tips ............................................................................................................................. 45
PanelView Plus Comms 45
Kepware Communications 48
Real Time Automation, Inc.
5
1-800-249-1612
Revision History
Version
Date
Notes
3.29
Product Launch
3.30
Bug Fixes
1. Fixes for setting Network Config using RSLinx
2. Fixes for setting Serial and Ethernet config using old AB
1761-NET-ENI/W Serial PC Config Utility
3. EIP Stack upgrades required by new EIP conformance test
(as of 1/2/17)
3.31
Bug Fixes
1. Communication fix to work with InduSoft applications
2. PanelView Duplicate Packet Detect communications fix
3. BootP fixes
4. Data View webpage floating point writes fixed
5. Minor webpage layout fixes
6. Change to force at least 1 admin to "Full Access" when
security enabled
3.32
Bug Fixes
1. Disabled force of at least 1 Admin when security is enabled
(see change 6 in version 3.31).
4.02
Bug Fixes
1. Updated web UI diagnostics and counters.
2. Added support for RSLinx straight Ethernet driver.
3. Optimized message queue servicing.
4. Added ability to download EDS file from webpage.
5. Removed BOOTP support.
6. Improved IP configuration implementation.
Real Time Automation, Inc.
6
1-800-249-1612
7. Enabled force of at least 1 Admin when security is enabled.
8. Minor webpage layout fixes.
Real Time Automation, Inc.
7
1-800-249-1612
Overview
The 515RTAENI is a replacement for the Allen-Bradley 1761-NET-ENI and 1761-NET-ENIW modules. The
515RTAENI gateway:
Provides the same Ethernet connectivity for all DF1 serial controllers, PanelView Standard
Terminals, and other DF1 full-duplex devices
Communicates between Allen-Bradley Logix and legacy controllers
Generates email messages via Simple Mail Transport Protocol (SMTP)
Allows ability to easily upload and download programs using standard Rockwell Automation
tools
Writes to Ethernet controllers like ControlLogix
However, the interface is improved by providing web browser configuration, allowing up to 12 Ethernet
connections, adding support for string data types, and improving diagnostic functionality.
If at any time you need further assistance do not hesitate to call Real Time Automation support.
Support Hours are Monday-Friday 8am-5pm CST
Toll free: 1-800-249-1612
Email: support@rtaautomation.com
Real Time Automation, Inc.
8
1-800-249-1612
Hardware N34
Physical Specifications
POWER
8 V @ 230 mA to 28 V @ 80 mA
Power can be received over serial cable
TEMPERATURE
Industrial Temperature Range -40C to +85C
CERTIFICATIONS
UL, C/UL, CE, FCC, CLASS 1 DIV 2
MOUNTING
Din Rail, Panel
SIZE
4.2” x 3.25” x 1#
WEIGHT
5 oz.
COMMUNICATION PORTS
SERIAL
1 RS232
ETHERNET
1 10/100 Mbps BaseT Ethernet Port
Real Time Automation, Inc.
9
1-800-249-1612
Mounting
Installing
Follow these steps to install your interface converter.
1. Mount your DIN Rail.
2. Hook the top mounting flange over the DIN Rail.
3. While pressing the 515RTAENI against the rail, press down to engage the spring loaded
upper clip and rotate the unit parallel to the DIN Rail.
4. Release downward pressure.
Removing
Follow these steps to remove your interface converter.
1. Press down on unit to engage the spring loaded upper clip.
2. Swing bottom of unit away from DIN Rail.
DIN Rail
Spring Loaded Upper Clip
Real Time Automation, Inc.
10
1-800-249-1612
Powering the Gateway
The following steps will allow you to properly and safely power the gateway.
1) Connect a 24VDC power source to the gateway.
a. The unit draws 125 mA at 24VDC
b. The gateway has a voltage operating range from 8-28VDC; 24VDC is recommended.
Hazardous Environment Power & Installation Instructions
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or non-
hazardous locations only.
WARNING EXPLOSION HAZARD - Do not disconnect equipment unless power has been removed or
the area is known to be non-hazardous.
WARNING EXPLOSION HAZARD - Substitution of components may impair suitability for Class I,
Division 2.
THIS EQUIPMENT IS AN OPEN-TYPE DEVICE AND IS MEANT TO BE INSTALLED IN AN ENCLOSURE
SUITABLE FOR THE ENVIRONMENT SUCH THAT THE EQUIPMENT IS ONLY ACCESSIBLE WITH THE
USE OF A TOOL.
WARNING POWER JACK (Barrel Connector, J1) IS FOR MAINTENANCE USE ONLY AND MAY ONLY BE
USED WHILE THE AREA IS KNOWN TO BE FREE OF IGNITIBLE CONCENTRATIONS OF FLAMMABLE GASES
OR VAPORS. IT IS NOT TO BE CONNECTED UNDER NORMAL OPERATION.
In a Hazardous Environment, the unit must be powered with between 12-24 VDC; 860 mA (6 W) max.
Supervised. The unit is certified to be operated at -40C to 50°C.
Warning improper wiring will cause unit failure
Use the Barrel Connector OR the Screw
Terminals power connection, NOT both
Real Time Automation, Inc.
11
1-800-249-1612
Pinouts & Wiring
Pinouts
The gateway has two connectors for communication: T-Strip (Port 0) and DB9 port (Port 1). Either port
can be used for RS-232 communications using the pinouts in the diagram below.
DB9 pinouts are as follows:
Pin 2 RX
Pin 3 TX
Pin 5 GND
CABLE INFORMATION:
Wiring
It is recommended to use Allen-Bradley serial cables:
Allen-Bradley 1761-CBL-PM02 Ser. C
Allen-Bradley 1756-CP3
IMPORTANT: It is highly recommended to follow wiring recommendations regarding the Allen-
Bradley serial cables. Failure to do so may result in poor or inoperable intermittent communications.
NOTE: Only one physical port can be used at a time.
Real Time Automation, Inc.
12
1-800-249-1612
Accessing the Main Page
The following steps will help you access the browser based configuration of the gateway. By default,
DHCP is enabled. If the gateway fails to obtain an IP address over DHCP it will Auto IP with 169.254.X.Y.
1) Insert the provided CD-ROM into a computer also on the network.
2) Run the IPSetup.exe program from the CD-ROM.
3) Find unit under “Select a Unit”.
a. If you do not see the gateway in this tool, then your PC is most likely set up as a static IP.
i. Change your PC’s network settings to be DHCP. If DHCP fails, then it will change
to be on the 169.254.x.y network.
ii. Relaunch the IP Setup tool to see if gateway can be discovered now.
4) Click Launch Webpage. The Main page should appear.
Note: Default setting is set to DHCP. If DHCP fails, default IP Address is 169.254.x.y
Real Time Automation, Inc.
13
1-800-249-1612
Error: Main Page Does Not Launch
If the Main page does not launch, please verify the following:
1) Check that the PC is set for a valid IP Address
a. Open a MS-DOS Command Prompt
b. Type “ipconfig” and press enter
c. Note the PC’s IP Address, Subnet, and Default Gateway
2) The gateway must be on the same Network/Subnet as the PC whether it’s setup for DHCP or
Static.
Once you have both devices on the same network, you should be able to ping the gateway using a MS-
DOS Command Prompt.
The image above shows a gateway that is currently set to a static IP Address of 192.168.0.100.
If you successfully ping your gateway, open a browser and try to view the main page of the gateway by
entering the IP Address of the gateway as the URL.
Real Time Automation, Inc.
14
1-800-249-1612
Web Configuration Tabs
The 515RTAENI gateway has a built-in webserver that can be accessed by entering the IP Address of the
gateway into a web browser’s address bar.
All configurable fields inside the gateway are grouped into 5 different tabs. Below is a list of tabs and
what information can be found on each one:
1) Home used for diagnostics and status messages for both the DF1 and Ethernet sides
2) Data View used to read, write, and display data from the Controller
3) Network used to configure all Ethernet, E-mail, and Serial Port Settings
4) Mapping used to configure all the IP Address DF1 Node mappings
5) Utility used for revision information, downloading the EDS file, updating firmware, configuring
security settings, and saving/importing gateway configuration
Real Time Automation, Inc.
15
1-800-249-1612
Committing Changes to the Gateway
To make changes to the gateway, find the tab identifying which information to change. Next to the
section to modify, there is an Edit button.
Once the Edit button has been clicked, the icon will change into a Save button and any editable
fields under that section will change into text boxes or dropdown lists. See below screenshot as an
example. The only field in this section that isn’t configurable is the Serial Mode.
Changes will not take effect until the Save button is clicked. While the save is in progress, the Save
button will change into the icon to indicate that the gateway is currently saving those
settings.
If the Ethernet settings are changed, the gateway will reboot and a message will be displayed
prompting the user to enter the new IP address.
Real Time Automation, Inc.
16
1-800-249-1612
Network Tab
Ethernet Settings
By default, the gateway is configured for DHCP.
There are 2 different options for the gateway to get an IP Address:
1. DHCP Only Attempts to receive an IP Address every time that the gateway is powered up. If
DHCP fails, then an AutoIP Address is used to make the webpages accessible and DHCP will
continue to attempt to get an address.
2. Static IP An IP Address is statically set and will never change until the option is modified.
When configuring a static IP, be sure to update the appropriate values in IP Address, Subnet Mask, and
Gateway fields.
Real Time Automation, Inc.
17
1-800-249-1612
Changing from DHCP to Static IP
1) Click the Edit button next to Ethernet Settings on the Network Tab in the gateway.
2) Change the dropdown of the IP Settings field to be Static IP.
3) Change the field IP Address, Subnet Mask, and Gateway.
4) Press the Save button.
Additional Fields under Ethernet Settings
Field
Description
DNS
This is the IP of the DNS Server on the network where the gateway looks
up IP Addresses. This is mandatory for E-mail.
PLC Security Mask 1
This field limits what controllers can connect to and communicate with the
gateway based on their IP Address. This can be used to only allow a
specific IP Address or a specific IP Address range. The value 255 is the
wildcard value. A value of 0.0.0.0 or 255.255.255.255 allows any Ethernet
device to connect. Security Mask 1 takes precedence over Security Mask
2.
PLC Security Mask 2
Secondary security mask field that is only used when PLC Security Mask 1
fails.
Real Time Automation, Inc.
18
1-800-249-1612
Serial Settings
By default, the gateway is configured for the following settings:
Baud Rate: 19200
DF1 Error Detection: CRC
Serial Mode (fixed): DF1 Full-duplex, RS232, 8 data bits, parity none, 1 stop bit
These settings should match what is configured in the DF1 Serial Device, including the DLE parameters of
DLE NAK Retries, DLE ENQ Retries, and DLE Embedded Response.
See table below for more explanation:
Value
Description
Baud Rate
Set the baud rate to match the baud rate configured for the 515RTAENI.
38,400 and 19,200 are the most commonly used baud rates.
Serial Mode
Cannot be changed: DF1 RS232,8N1 (8N1 meaning 8 data bits, no parity bit, 1
stop bit)
Timeout (ms)
Elapsed time in milliseconds for sending or receiving data before an error is
reported.
DLE NAK Retries
Response that signals that a message frame was not received successfully.
DLE ENQ Retries
Requests retransmission of a response.
DLE Embedded Response
Per the DF1 protocol, this allows a response to a previous message to be
embodied in a new message.
Error Detection
DF1 error detection algorithm.
Duplicate Msg Detection
In the case of a duplicate, an error is reported in the attached PLC.
NOTE: Auto-baud is NOT supported. The 1761-NET-ENI/W serial PC Config Utility has an Auto-
baud option, but this setting is not supported by the 515RTAENI gateway.
Real Time Automation, Inc.
19
1-800-249-1612
Email Settings
This optional section can be filled out if alarms and messages need to be e-mailed out on the network.
To configure, the following fields can be modified:
Field
Description
Email server
This is the TCP/IP address or name (maximum of 64 characters) of SMTP
Server.
Username & Password
These fields are filled in if the Email Server requires SMTP Authentication.
If the Email Server does not require SMTP Authentication, then the values
here will be ignored and can be left blank. The maximum length for these
fields is 64 characters.
“From Email” Address
This is an ASCII string that cannot be left blank, so by default it is filled in
with a default value that can be modified. This is the message that is sent
with any email message initiated by the gateway.
SMTP Port
This is the TCP port of the Email Server configured. Typically, this value is
25.
Real Time Automation, Inc.
20
1-800-249-1612
Email Alarms and Messages
This optional section can be filled out if alarms and messages need to be e-mailed out on the network.
Under the “To:” section, up to 50 email addresses (up to 64 characters) can be configured and stored.
The Config column represents the Node numbers (150 to 199) that are used to store the actual email
address. The “Destn” column represents the Node ID, any messages sent to that Node ID, will be
forwarded to the associated “To” address.
The controller will send a 485CIF Write message to the DF1 destination Node that is mapped to the
destination email address. For the 515RTAENI to successfully send an email message, the Email Settings
configuration needs to be setup correctly. The 515RTAENI stores the destination email address, but
does not store the actual data that is sent.
Field
Description
Destn
Messages to the Node in this column will be sent to the associated “To”
email address.
Config
Stores the defined node for each email address.
“To”
User can manually type in one e-mail address for every individual “To”
line.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

RTA 515RTAENI-N34 Product User Manual

Category
Networking
Type
Product User Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI