Speakman SE-575-DP-238 User guide

Category
Sanitary ware
Type
User guide
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
05/06/16 speakman.com 92-SE575-DP-23X-01
SPEAKMAN
®
SE-575-DP-237 & SE-575-DP-238
Installation, Operation, and Maintenance Instructions
EYESAVER® EYE/FACE WASH & SAFE-T-ZONE®
EMERGENCY SURFACE MOUNTED WALL SHOWER
DESCRIPTION
Barrier-Free wall mounted emergency eye/face wash with drain pan for draining water. Unit supplied with
plastic spray heads, with individual flow restrictors. Unit activated by pulling handle down to open position,
and is supplied with a cabinet flush with wall to keep corridors free from obstruction. Unit also supplied with
wall mounted emergency shower as described below.
SE-575-DP-237:
Emergency deluge shower unit with wall activator. Shower is supplied with a 1" NPTF stay-open full flow
ball valve that is activated by pull handle that is mounted on wall. Shower head designed to mount flush
with ceiling.
SE-575-DP-238:
Emergency deluge shower unit with wall activator. Shower is supplied with a 1" NPTF stay-open full flow
ball valve that is activated by pull handle that is mounted on wall. Shower head designed to drop down
through ceiling.
SPECIFICATIONS
EYE/FACE WASH:
SPRAY HEADS: (2) ABS PLASTIC NON-AERATED.
VALVE: BRASS, CHROME-PLATED.
ACTIVATOR HANDLE: BLACK, NYLON PLASTIC.
INLET: ½" NPT FEMALE.
DRAIN: 1-1/4" BRASS TUBE.
CABINET & DRAIN PAN: 20 GAUGE (.036 THK.) 300 SERIES STAINLESS STEEL
WITH SATIN FINISH.
EMERGENCY SHOWER:
SHOWER HEAD: 8" DIAMETER STAINLESS STEEL (SE-575-DP-238).
10" DIAMETER STAINLESS STEEL FLANGED (SE-575-DP-237).
COVER PANEL: 20 GAUGE (.036 THK.) 300 SERIES STAINLESS STEEL.
VALVE: 1" NPT FEMALE BRASS, CHROME-PLATED. FULL FLOW STAY-OPEN BALL VALVE.
ACTIVATOR: STAINLESS STEEL LEVER WITH BLACK PLASTIC ROTATING HANDLE.
PIPING: 1" IPS STEEL PIPE NIPPLE & UNIONS.
INLET: 1" NPTF.
FLOW CONTROL: 20 GPM.
SHIPPING WEIGHT: 27 LB. (SE-575-DP-238).
28 LB. (SE-575-DP-237).
EMERGENCY SIGN: 7-7/8" X 12" PLASTIC WALL SIGN.
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
05/06/16 speakman.com 92-SE575-DP-23X-01
InstAllAtion
Review and understand configuration of the unit as shown in the diagrams following in this instruction before
roughing in or installing unit.
1. Once desired location & spray head height is determined cut openings in the wall for the eye/face wash &
emergency shower per the minimum dimensions shown in Fig. 1, making sure there are suitable structures
(stud, etc.) on each side of the eye/face wash opening for securing the eye/face wash cabinet to the wall.
2. Making sure unit is level, use appropriate fasteners (4) to secure unit to wall as shown in Fig. 2A & Fig. 2B.
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
05/06/16 speakman.com 92-SE575-DP-23X-01
3. Plumb the eye/face wash & emergency shower ball valve (supplied) as shown in Fig. 2A & Fig. 2B, and
the required water supply piping (supplied by others). For smooth activation, make sure that when final
union connection is made that the stainless steel activation lever handle is as close to perpendicular
to the finished wall as possible. Use thread sealant on all pipe thread connections (not union connections).
The eye/face wash is supplied with a ½" NPT inlet, and requires a minimum 30 PSI flowing water pressure,
and the emergency shower is supplied with a 1" NPT inlet. Shown in Fig. 1 as dotted lines is the
recommended piping configuration for a single water supply inlet.
NOTE: Water supply to the unit to be an uninterrupted source of potable water. Failure to use potable
water can result in emergency units producing impure or contaminated water causing possible
further injury.
4. Connect drain tailpiece or waste an adequate drain in compliance with local and/or national
plumbing codes.
5. Assemble shower head to supply piping accordingly. Drop down design for the SE-575-DP-238,
and ceiling mount for the SE-575-DP-237. Make note that ANSI specifies that showerhead must
be 82"-96" from the surface on which the user stands. Use thread sealant on all pipe thread connections.
See shower head differences in Fig. 3.
6. Once piping is complete, and all supply and drain connections are made. Assemble lever handle to valve
making sure it is oriented correctly. Place the stainless steel wall panel into position and make sure
the lever handle rotates from the on & off positions freely without dragging on wall panel. If valve operates
correctly, secure the wall panel to the wall using proper fasteners. If dragging occurs, loosen 1" union
and adjust 1" ball valve so the lever handle is centered in the wall panel slot, and any interference
is eliminated.
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
05/06/16 speakman.com 92-SE575-DP-23X-01
7. Assemble the black nylon rotating handle, and 3/8-16" hex nut to the activation lever handle.
8. Turn water supply on and test the eye/face wash & shower.
OPERATION
The eye/face wash is activated by pulling the handle on the eye/face wash drain pan down to the open
position. Once the eye/face wash is activated water will discharge from the spray heads until the unit
is manually shut off. To shut off, lift back onto the upright off position.
The shower is activated by pulling/pushing the handle in the downward direction to the full open position.
Once the valve is activated the head will continue to discharge water until the valve is manually closed.
The unit is shut off by pulling/pushing the handle in the upward direction to the complete off position.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be
activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes
a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspector’s initials
should be noted.
MAINTENANCE
Should you need to repair components behind the wall (valve, lever handle, etc.); the cover panel is removed
by following these instructions.
1. Shut off water supply before doing any repair to this unit.
2. Position lever handle in the half-open (horizontal) position, and remove black plastic rotating handle from
lever handle.
3. Remove the (4) fasteners that attach the cover panel to the wall, and slide the cover panel off.
This will give you full access to valve and lever handle inside the wall.
4. Once repair is made follow above instructions in reverse to reassemble handle and panel cover.
Be sure to turn water supply back on once repairs are final.
WARNING: Use only genuine Speakman parts when repairing or replacing components. To order parts
call 1-800-537-2107.
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
05/06/16 speakman.com 92-SE575-DP-23X-01
Rough-In MEASUREMENTS
REPAIR/REPLACEMENT PARTS
ITEM NUMBER PART NUMBER DESCRIPTION
1 RPG20-1985 1" Emergency Shower Ball Valve
2A SE-830
10" Stainless Steel Shower Head for SE-575-DP-237
(shown in Fig. 3)
2B SE-820
8" Stainless Steel Shower Head for SE-575-DP-238
(shown in Fig. 3)
3 RPG20-2010-RCP Swing Down Eye/Face Wash Valve Assembly
4 RPG38-0417 Non-Aerated Spray Head Assembly
NOT SHOWN RPG05-0673 Internal O-rings, Screws for Eye/Face Wash Valve
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
05/06/16 speakman.com 92-SE575-DP-23X-01
FLOW DATA
EYE/FACE WASH:
FLOW PRESSURE PSI (BAR) 30 (2.07)
FLOW RATE GPM (LPM) 3.9 (15)
SHOWER:
FLOW PRESSURE PSI (BAR) 20 (1.38) 60 (4.14)
FLOW RATE GPM (LPM) 20 (75) 25 (94)
NOTE: This unit should be connected to an uninterrupted source
of potable water, with a minimum flowing pressure of 30 PSI
and a maximum static pressure of 80 PSI.
Note: All units meet existing ANSI
Z358.1 Standards and OSHA Rules.
Product improvements may cause
specification and dimensional
changes without notice.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Speakman SE-575-DP-238 User guide

Category
Sanitary ware
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI