Zenith 305652 Installation And Operating Instructions Manual

Category
Sanitary ware
Type
Installation And Operating Instructions Manual

This manual is also suitable for

804545NZ 03.17 v1.00 Page 1 of 16
Zenith Autoboil
303652 Zenith Autoboil 3 Litre White
303651 Zenith Autoboil 3 Litre Stainless Steel
305652 Zenith Autoboil 5 Litre White
305651 Zenith Autoboil 5 Litre Stainless Steel
307652 Zenith Autoboil 7.5 Litre White
307651 Zenith Autoboil 7.5 Litre Stainless Steel
Installation and Operating Instructions
Page 2 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
Contents
Read These Warnings First ........................................................................................................................3
Installation Requirements .........................................................................................................................3
Installation Procedures .............................................................................................................................4
Step 1 – Positioning ................................................................................................................4
Step 2 – Fastening .................................................................................................................. 4
Step 3 – Connecting ................................................................................................................5
3.1 Plumbing ................................................................................................................5
3.2 Venting ....................................................................................................................5
3.3 Electrical.................................................................................................................6
Step 4 – Installing Filter Guide ..............................................................................................6
Step 5 – Installing Tap ...........................................................................................................6
Step 6 – Installing Filter ........................................................................................................7
Step 7 – Commissioning - Filter Flush & Calibrate ............................................................7
Menu Operation .......................................................................................................................................... 9
Wall Mounting Template Dimensions .....................................................................................................17
Spare Parts .................................................................................................................................................18
Exploded View Diagram .............................................................................................................................19
Problem Solving .........................................................................................................................................20
Earthing Continuity Verfication ..................................................................................................................20
Operating Procedures ................................................................................................................................21
Filter Replacement ....................................................................................................................................21
Cleaning ......................................................................................................................................................22
End of Life Disposal ...................................................................................................................................22
Contact Details ...........................................................................................................................................24
Note:
All plumbing must comply with the relevant parts of AS/NZS 3500
All electrical must comply withthe relevant parts of AS/NZS 60335/3000
This appliance is not intended for use by per-
sons (including children) with reduced physical,
sensory or mental capabilities, or lack of expe-
rience and knowledge, unless they have been
given supervision or instruction concerning use
of the appliance by a person responsible for
their safety. For products sold in Europe, this
appliance can be used by children aged from
8 years and above and persons with reduced
physical, sensory or mental capabilities or lack
of experience and knowledge if they have been
given supervision or instruction concerning use
of the appliance in a safe way and understand
the hazards involved. Children should be super-
vised to ensure that they do not play with the
appliance. Cleaning and user maintenance shall
not be made by children without supervision.
This appliance is intended to be used in house-
hold and similar applications such as
- Staff kitchen areas in shops, of ces and other
working environments;
- Farm houses and by clients in hotels, motels
and other residential type environments;
- Bed and breakfast type environments;
- Catering and similar non-retail applications.
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 3 of 24
Read These Warnings First
Please read all installation requirements, installation procedures
and precautions before installing any Zenith Autoboil instant boiling
water heater.
Never attempt to install any Zenith Autoboil instant boiling water
heater without reading all of the applicable instructions.
In some hard water areas where mineral scale accumulation in
the boiling chamber of the Zenith Autoboil may become a problem,
consideration should be given to the maintenance required. A
suitable form of water treatment may be necessary.
The cold water supply to this appliance must be potable and fall
within your local authority’s guidelines.
All plumbing connections must be made in accordance with local
regulations.
The Zenith Autoboil instant boiling water heater is not intended for
use by young children or infirm people without supervision.
Young children should be prevented from having access to ensure
that they are not able to use or play with the heater.
This appliance must be earthed. If the power supply cord is damaged
it must be replaced by a Zenith authorised agent or a qualified
electrician.
Do not remove the cover of the heater under any circumstances
without first isolating the heater from the power supply.
Do not use strong, corrosive or abrasive cleaners to clean the case
of the heater.
Frost protection: If this heater is located where ambient air
temperature could fall below 5ºC when the heater is not in use, do
not turn off the appliance electrically. This safeguide does not offer
the same protection to the connecting pipework and fittings.
The ambient temperatures this unit must operate within is 5ºC -
50ºC.
This heater is intended only for indoor use and should never be
installed outdoors or be exposed to the elements of nature.
This unit must not be positioned in an area that may be cleaned by a
water jet. This unit must not be cleaned by a water jet.
Before installing, ensure that the following are available:
a) Sufficient space to position the heater so there is at least 100 mm
clearance above the heater for service access, 150 mm to its left
and
20 mm to its right – the tap outlet must be positioned at least
300 mm above a draining board or drip tray.
b) Standard 220- 240 volt power cable positioned as shown on the
paper mounting template for connection from the rear of the
heater to the terminal block within the heater, OR a standard 10
amp 220- 240 volt power outlet on the wall within 1500 mm of the
heater. This switch must provide all-pole disconnection and a
contact separation of at least 3 mm installed in accordance with
wiring rules, see Step 3 - 3.3).
Installation Requirements
Page 4 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
c) Cold water supply with a minimum working pressure of 70 kPa
and a maximum working pressure of 700 kPa connected via an
isolation valve.
d) Outlet drainage to a sink draining board or to a drip tray.
e) Access to drainage from a vent situated at the base of the
heater.
f) If the water pressure is likely to exceed 700 kPa, a 350 kPa
pressure reducing valve must be installed in the cold water supply
line.
f) In all installation instances the walls of the heater must be
vertical and the base horizontal, there can be no exceptions to
this rule.
Before You Begin
Refer to the mounting-hole template on page 17.
Read the installation and operating instructions completely.
Decide whether to install with concealed or exposed plumbing and/
or electrical connections. Concealed connections are preferred for
superior appearance.
Step 1 – Positioning
Position the heater so the tap will drain on to a draining board or
drip tray.
Position the base of the tap to be not less than 300 mm above the
draining board (height should be increased only if essential for
filling larger vessels).
Provide clearance for service access of not less than 100 mm top,
150 mm left, 20 mm right.
Mark corner positions for the heater on the wall so as to position
the paper mounting-hole template.
Step 2 – Fastening
Position mounting-hole template on wall and drill holes where
shown.
Remove cover fastening screws from heater and lift whole cover off
heater.
Installation Procedures
COLD
INLET
VENT
OUTLET
INLET
POSITION
VENT
POSITION
Approximate Weight When Filled
100 mm
minimum
clearance
20 mm
minimum
clearance
from right
edge to wall
300 mm
150 mm
3.0 Litre models 12.5 kg
5.0 Litre models 16.5 kg
7.5 Litre models 20.5 kg
Installation Requirements
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 5 of 24
Concealed
Vent
Concealed
Inlet
45 mm
Remove filter guide as shown in picture above.
Install plumbing and wiring and prepare pipe ends and wiring ends as
shown.
Screw heater chassis to the wall using screws or bolts suited to the
wall.
Screws or bolts must be capable of supporting the heater weight
when filled.
Step 3 – Connecting
THE FOLLOWING PROCEDURE IS TO BE DONE BY AN AUTHORISED
INSTALLER ONLY.
3.1 Plumbing
For exposed plumbing connection, connect the cold water inlet pipe from
the base of the heater directly to the 12.7 mm compression fittings.
For concealed plumbing connections, connect the cold water pipe
through the rear of the chassis using a 12.7 mm capillary elbow (# 63
Swivel Elbows).
Cold water pipes must be flushed before connection to the inlet. Any
clogging due to sediment or fines will adversely affect the operation of the
heater.
It is recommended that the heater be installed with a stop cock which
allows it to be isolated from the mains supply for servicing.
Water pressure requirements:
Minimum - 70 kPa maximum - 700 kPa.
3.2 Venting
A vent at the base of the heater must be plumbed to a safe visible location
as, under certain conditions, it may discharge cold or boiling water and/
or steam.
For exposed vent plumbing, connect vent outlet from the base of heater
to a 12.7 mm pipe which has a continuous fall, is no more than 3 metres
long, has no more than 3 right angle bends, and visibly discharges to a
waste water drain.
Alternatively attach a tun dish to the wall as shown and plumb away to
waste.
Note: when routing the plumbing for the vent / tundish installed and
mains inletline, ensure you do not obstruct filter access for filter
replacement.
1
2
Remove Filter Guard
Visible Tundish
Vent line
Installation Procedures
Warning: If pressure is likely
to exceed 700 kPa, a pressure
limiting valve must be installed
in the cold water supply line.
Zenith recommends a valve
rated at 350 kPa for this ap-
plication.
Page 6 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
3.3 Electrical
Warning: Do not turn on the power until instructed. Water must first
be available from the tap outlet to prevent damage.
For an exposed electrical connection, the pre-fitted flex and plug cable
is plugged into the PCB as shown. Use a standard GPO power outlet
within 1500 mm from the heater with adequate power for the unit.
For a concealed electrical connection, disconnect the pre-fitted
flex and plug cable at the PCB connector and discard. Connect the
concealed power cable through the rear access opening to the green
terminal block on the PCB.
Check that the earth is connected through the PCB to the chassis with
an ohm meter.
Warning: Do not connect both options. It is essential that the flex and
plug cable is removed from the PCB if the concealed connection is
used. Otherwise the GPO plug will become live.
Step 4 – Installing Filter Guide
Assemble the lter guide provided with the unit, make sure it is locked in position, then put the cover back on.
1. Push the lter guide upwards
2. Rotate clockwise until
locked
Thread Tape
2. Before installing the tap, ensure suf -
cient thread tape is applied to the thread.
1. After the lter guide is installed, t the
cover to the unit and x with screws top and
bottom.
Step 5 – Installing Tap
Installation Procedures
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 7 of 24
1. Insert the lter
To install a lter, insert the lter into the base of the unit as shown and turn 90° until a click or stop point is
reached, see images below. There should be approximately 20mm of the lter protuding when installed.
3. After the cover is tted, turn the tap fully
clockwise to the end stop and stopped at up-
right position.
4. Use the spanner supplied to tighten the
lock nut anti-clockwise.
2. Turn the lter through 90°
until fully engaged
20mm
Lock nut
Step 6 – Installing Filter
NOTE: For safe operation, the filter cartridge should be replaced every 6-12 months, or earlier if you
notice a persistent reduction in water pressure from the appliance or an unpleasant taste or odour in the
water. Refer to Filter Replacement section on page 21 for instructions of changing lter.
Installation Procedures
Step 7 – Commissioning - Filter Flush & Calibrate
Remove Plug
Fig.1
Warning: Do not turn on the power until
instructed. Water must first be available from
the tap outlet to prevent damage.
1) Remove the plug on the left side of the unit to access
the filter flush valve as shown in fig 1.
2) Use an 8mm allen key (or flat blade screw driver) to
rotate the valve 180 (either way) to the “FILTER FLUSH
position (fig 2).
Page 8 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
FILTER FLUSH
FILTERED
Fig.2
Depress
Inlet water
temp
15°C 10°C
3.0 Litre models 16 min 17 min
5.0 Litre models 16 min 17 min
7.5 Litre models 23 min 24 min
3) Turn on the mains water. Allow at least 5 litres of water to flush
through the filter. Make sure there is water flowing from the
vent outlet (i.e. the valve setting is correct). Water should not
flow into the tank.
4) Once the filter flush is complete, rotate the valve 180 (either
way) to the “FILTERED” position (fig 2). Replace the access
plug.
5) Open the tap (push the lever backwards) into the locked open
position (fig 2) and allow the tank to fill until water flows from
the tap outlet.
6) Once the water is available from the tap, turn off the mains
water and close the tap outlet.
7) Turn on the power to the unit (water must be in the tank).
8) Touch the white circle next to the left of the [Tick] to
“Continue”
For screen operation, see the section on “Menu Operation”.
9) Boiling Calibration will commence. It will take several minutes
for the water to boil.
Calibrating Completed
10) When it completes (as prompted), turn on the mains water
supply.
11) Select
to
Continue
12) The home screen will be shown (see section 2.1).
13) The tank will fill and heat. It will take the initial times shown in
the table to reach the final state.
Installation Procedures
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 9 of 24
The Autoboil uses a display and button menu
system for setup and operation adjustment.
The display does not have a touch screen feature.
The side buttons are used to navigate, perform
selections and modify values.
The icon changes according to the button action. A
button has no function when no icon is shown.
Menu Operation
1.Understanding Icons and Buttons
Move to the next item able to be highlighted.
Move to the previous item able to be
highlighted.
Confirm menu selection.
Move to the previous menu.
Perform one of 3 functions:
1. Move to the menu titled by the highlighted item.
2. Select the currently highlighted item to adjust it.
3. Confirm the value of a selected item.
Increment the item selected.
Decrement the item selected.
2.Home Screen Content
2.1 Normal Mode
Button 2 shows faults information.
Button 3 shows more information about the
lter life.
Fault Indication:
There are no current faults.
Shown red, there are current faults.
Page 10 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
Using to navigate to the lter life settings
menu.
Button 4 will show more information about the
sleep mode settings.
Using to navigate to the sleep mode settings
menu.
Filter Indication:
Days remaining of lter life.
Shown red, lter needs replacement.
Sleep Mode Indication:
Unit will enter sleep mode at the time shown.
Unit will enter sleep mode when it is dark.
All sleep saving modes are disabled.
2.2 Sleep Mode
Trigger Indication:
Unit will exit sleep mode at the time shown.
Unit will exit sleep mode when ambient light returns to normal (bright room).
Menu Operation
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 11 of 24
3. Settings Menu
Select on the home screen to navigate to the main menu.
Choose
Settings
and select
Choose an option and select
2.3 Sleep Override Mode
Awake time remaining:
Unit will return back to sleep mode after this time.
Main Menu Settings Menu
Menu Operation
Page 12 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
3.1 Settings - Date/Time
From the settings menu choose
Settings
and select
Navigating using and
Perform a selection or confirm an adjusted value
using
Adjust the date/time values using and
Note: Time can be in 12hr or 24hr mode.
To set up time choose a selection, then
Adjust value by using
and then to
con rm.
Follow similar steps to set up date.
From the settings menu choose
Settings
and select
, and to adjust boiling
point.
Confirm using
and return to the previous
menu.
3.2 Settings - Temperature
Note: Setting the temperature above 98°C may re-
quire boiling calibration to prevent excessive steam
release or high energy usage (see section 4.2).
3.3 Settings - Sleep Modes
From the settings menu choose
Sleep Modes
and select
Choose
Sleep Trigger
and select ,
and to select the trigger for the unit to enter
its sleep mode.
Con rm using
and return to the previous
menu.
Disabled
the unit will not enter its sleep
mode.
the unit will use the on/off
timer settings to enter and exit
its sleep mode.
the unit will enter its sleep
mode when darkness is detect-
ed and will exit its sleep mode
when the ambient light returns
to a normal level (bright room).
Timer
Ambient Light
Choose
Sleep Action
and select
and to select the heating mode action when
the unit is in its sleep mode. Con rm using
and return to the previous menu.
3.3.2 Sleep Action
3.3.1 Sleep Trigger
Menu Operation
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 13 of 24
68°C
While the unit is in its sleep
mode the set point of the water
will be reduced to 68°C.
While the unit is in its sleep
mode no heating of the water
will occur.
Off
Choose
Sleep Action
and select
and to select the trigger for the unit to enter
its sleep mode.
Con rm using
and return to the previous
menu.
Everyday
Adjust on/off timer settings for
all 7 days simultaneously.
Adjust on/off timer settings for
all 5 weekdays simultaneously.
Adjust on/off timer settings for
the 2 weekend days simultane-
ously.
Adjust on/off timer settings for
the 7 days separately.
Weekdays
Weekends
Individual Days
3.3.3 Timer Settings
Individual Days Settings
Choose item and adjust value, then
to confirm.
3.4 Settings - Filter
From the settings menu choose
Filter
and select
3.4.1 Internal / External Filters
Choose
Internal
or
External
and select
Choose one of the following options and select
Note: There is a similar set of menus for both
internal and external lters.
Menu Operation
Saving changes
to exit the timer settings menu. A
confirmation menu will be shown.
Choose
Continue
to save changes and
to confirm. Choose
Cancel
to
discard changes and
to confirm.
Page 14 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
This allows modi cation of lter life and usage
parameters.
Filter Life – Options are:
Disabled (no lter replacement reminder will be
shown on home screen)
1-14 months (Default 12 months)
Filter Usage – Automatically increments daily. This
is reset to “0 Days” when a lter reset is performed.
Can be adjusted if a partially used lter is inserted.
The days remaining of the lter shown on this
menu and on the home screen are based on these
2 parameters.
This action will reset the lter usage counter. A re-
minder is shown to ush the new lter before doing
this (see page 21 - Filter Replacement).
Select
to continue after ushing.
Choose
Continue
and select to
reset the lter usage counter.
The log shows the dates that the lter usage counter
was reset and the “days used” before the reset was
performed.
Use
and to scroll through the log history.
3.4.2 Filter Life / Usage
3.4.3 Replace Filter
3.4.2 Filter Log
Select on the home screen to navigate to the
main menu.
Choose
Install
and select
4. Install Menu
Menu Operation
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 15 of 24
4.1 Install - Light Calibration
From the install menu choose
Continue
and select
Before continuing ensure the unit is in its normal
typical light environment and the front panel is not
covered.
Select to perform the calibration. It will com-
plete after 6 seconds.
Select
to continue.
4.2 Install - Boiling Calibration
This automatically corrects for boiling point
differences at each installation site. The unit was
calibrated by the installer at installation; however
the installation environment may have changed
requiring recalibration of the boiling point.
Incorrect boiling calibration points may cause
excessive steam vent releases, or increased energy
usage.
Boiling calibration is recommended when the
temperature setting is close to 100°C (section 3.2).
From the install menu choose
Continue
and select
The unit will heat the water for boiling calibration.
This may take several minutes depending on the
initial water temperature. When it completes the
screen will automatically return to the install
screen.
4.3 Install - Power Cycle
From the install menu choose
Power Cycle
and select
This will turn the unit brie y off then on (restart).
All custom settings will be retained.
Choose
Continue
and select to
perform the power cycle.
Menu Operation
Page 16 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
5.1 Info - Product
From the install menu choose
Product
5.2 Info - Current Fault
From the info menu choose
Current Fault
6. Service Menu
Note: The service menu is used by technicians only
for diagnostic purposes.
Menu Operation
5. Info Menu
Select on the home screen to navigate to the
main menu.
Choose
Info
and select
Choose value then select
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 17 of 24
Wall Mounting Template Dimensions



/
/
/
/




//
//
/
/
/
/
/
/
/
/
/
/
/
/
&ROG
,QOHW
9HQW
([WHUQDO3OXPELQJ
(OHFWULFDO:LULQJ
,QWHUQDO3OXPELQJ
3RVLWLRQLQJSLQ
Page 18 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
Spare Parts
Item Kit Number Description
1
94443NZ EB & AB 3 Ltr Tank Assy
94444NZ EB & AB 5 Ltr Tank Assy
94445NZ EB & AB 7.5 Ltr Tank Assy
2
94479NZ AB Fascia & PCB assy
94480NZ AB Fascia & PCB assy Grey
3 94447NZ Escutcheon
4 94448NZ Tap Lock Nut
5 90501NZ Tap Top Assy
6 93730NZ Flow Insert
7 94478NZ Tap Body
8 91440NZ Hot Tank NTC
9 94449NZ Loom, PCB to Overload
10 94481NZ Ribbon Cable
11 94451NZ Plug, HB Outlet
12 94482NZ PCB, AB Powerboard
13 93704NZ
0.2 mic Zenith MicroPurity Filter
2 size
14 94454NZ Cistern Tank
15 94455NZ Ball Valve assy
16 94456NZ Cistern Gasket
17 94457NZ Cistern Lid EB & AB
18 93118NZ Elbow Stem 1/4"
19 90100NZ Grommet, Cistern to Tank
20 94458NZ Overload
21 94459NZ Side release plug
22 94460NZ Seal transfer tube
Item Kit Number Description
23
94483NZ Metering Tube 1.5 & 3 Ltr
94461NZ Metering Tube 5 & 7.5 Ltr
24
94462NZ Element assy 1500W 1.5 & 3
94463NZ Element assy 2400W 5 & 7.5
25
94484NZ Bush Vent assy 3 ltr
94485NZ Bush Vent assy 5 ltr
94486NZ Bush Vent assy 7.5 ltr
26 94487NZ Inlet assy
27
94488NZ AB Fascia Kit
94489NZ AB Fascia Kit Grey
28 94470NZ Tap assy
29
90493NZ Metering tube kit 1.5 & 3 Ltr
90494NZ Metering tube kit 5 & 7.5 Ltr
30 94471NZ Cistern Gasket kit
31 94472NZ Cistern assy
32 90506NZ Tap Outlet
33
94473NZ Hot Tank Gasket kit 1.5 & 3 Ltr
94474NZ Hot Tank Gasket kit 5 & 7.5 Ltr
34 94490NZ PCB Splash Guard
35 94491NZ Filter Flush Valve
36 94492NZ Filter Head Kit (no Bracket)
38 94493NZ PCB & Filter Bracket
39 94494NZ Filter Guide
40 94495NZ Grommet
Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00 Page 19 of 24
Exploded View Diagram


















 










Page 20 of 24 Zenith Autoboil - Installation & Operating Instructions - 804545NZ - 03.17 v1.00
Problem Solving
Warning: this appliance must be earthed.
Following remedial service the earthing continuity of the heater must
be checked by a qualified technician using an appliance tester, or
continuity tester of accuracy Class 5 or better. Class 5 denotes an
accuracy of 5% full scale deflection.
1. Isolate power supply.
2. Set meter to 0 ohm with leads connected together.
3. Connect one test lead to the earth pin on the three pin plug.
4. Connect the other test lead to a bare patch of metal (preferably on
the edge) of the top of the cover, then to the front cover of the unit,
and then to the tap.
Warning- the water may be boiling - show extra care.
5. Test that in every instance the electrical resistance does not exceed
1 ohm.
Earthing Continuity Verification
If required, an earth continuity
test can be performed by testing
between the earth pin on the
products lead and a exposed
piece of metal on the case and
the tap body.
Symptom Possible Cause Solution
Fails to dispense water.
Incorrect filter flush valve setting.
Incorrect filter insertion.
Water isolating valve turned off.
Blocked filter, blocked meter tube,
blocked strainer, jammed ball
valve assembly.
Check filter flush valve position
(see Step 7, page 8).
Check filter is inserted correctly
(see page 21).
Check water supply valve.
Contact Zenith authorised agent.
Water not boiling.
Incorrect temperature setting.
Incorrect sleep mode setting.
No power.
Faulty thermostat, faulty element,
faulty cutout.
Check temperature setting
(see section 3.2).
Check sleep mode settings (see
section 3.3) or reset settings from
service menu.
Check power supply.
Contact Zenith authorised agent.
Runs out of boiling water and
fails to refill.
Outlet tap drips.
Overflow from vent.
Excessive steam from vent.
Power “on” but no heat.
Overload repeatedly tripping
with excessive steam.
Overload repeatedly tripping
without
excessive steam.
Requires boiling calibration.
Incorrect filter flush valve setting.
Incorrect filter insertion.
Internal adjustment.
Perform boiling calibration
(see section 4.2).
Check filter flush valve position
(see Step 7, page 8).
Check filter is inserted correctly
(see page 21).
Contact Zenith authorised agent.
Sleep/Wakes incorrectly when
room is light/dark.
Requires light calibration.
Incorrect sleep modes settings.
Perform light calibration
(see section 4.1).
Check sleep mode settings (see
section 3.3) or reset settings from
service menu.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Zenith 305652 Installation And Operating Instructions Manual

Category
Sanitary ware
Type
Installation And Operating Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI