  • Hello! I am an AI chatbot trained to assist you with the Vaisala HPP27XMOUNTINGSET1 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the purpose of the HPP271MOUNTINGSET1/HPP272MOUNTINGSET1 through-wall installation kit?
    What is the difference between the HPP271 and HPP272 through-wall installation kits?
    What materials are used in the construction of the HPP271MOUNTINGSET1/HPP272MOUNTINGSET1?
    What is the recommended distance between the HPP272 main probe body and the temperature probe?
    Where should the temperature probe be placed when installing the probes horizontally?
Through-Wall Installation Kit for HPP271 and HPP272
The optional through-wall installation kits for HPP271 (HPP271MOUNTINGSET1) and HPP272
(HPP272MOUNTINGSET1) allow installing the Vaisala HPP270 series H
2
O
2
probes into the monitored
process through the process wall.
The figure below shows an example installation for HPP272. The HPP271 installation kit is otherwise the
same, but does not include the HPP272-specific temperature probe lead-through.
60 ... 100 mm
6 mm
Ø 40 mm
Ø 8 mm
1
2
40 mm
(recommended)
Ø 8 mm
Ø 40 mm
Ø 50 mm
31 mm
14
mm
12 mm
Metal parts: AISI 316L
Seals and O-rings: FPM
Figure 1 Through-Wall Installation Example for HPP272
1
Nut for tightening the probe in place (temperature probe gland for HPP272 only)
2 Nut for mounting the gland (temperature probe gland for HPP272 only)
Seal the lead-throughs on the metal body of the probes.
HPP272 only: Install the main probe body and the temperature probe 60 … 100 mm (2.36 … 3.93 in)
apart from each other. The temperature probe must be far enough to prevent heat from the main probe
body from aecting the temperature measurement, but close enough so that the two probes measure
the same environment. When installing the probes horizontally, place the temperature probe
downstream of the warmed main probe body.
M212195EN-B
Quick Guide
Mounting Accessory
HPP271MOUNTINGSET1 / HPP272MOUNTINGSET1
PUBLISHED BY
Vanha Nurmijärventie 21
FI-01670 Vantaa, Finland
© Vaisala 2019
All rights reserved. Any logos and/or product names are trademarks of Vaisala or its individual partners.
Any reproduction, transfer, distribution or storage of information contained in this document is strictly
prohibited. All specifications — technical included — are subject to change without notice.
HPP271MOUNTINGSET1/HPP272MOUNTINGSET1
Dimensions
Figure 2 (page 2) shows the dimensions of the gland through-wall installation accessory
HPP271MOUNTINGSET1/HPP272MOUNTINGSET1 in millimeters and [inches].
Ø 12 [0.47]
mm
[in]
24 [0.94]
14 [0.55]
Ø 12
[0.47]
Ø 8 [0.31]
Ø 5 [0.196]
Ø 50 [1.97]
50 [1.97]
44 [1.73]
Ø 30 [1.18]
Ø 40 [1.57]
31 [1.22]
Figure 2 HPP271MOUNTINGSET1/HPP272MOUNTINGSET1 Dimensions