Amana AVXC20 Owner's manual

  • Hello! I am an AI chatbot trained to assist you with the Amana AVXC20 Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
CONDENSING UNIT
*VXC20
IOG-4014E
06/2021















WARNING
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com•www.amana-hac.com
© 2020 Goodman Manufacturing Company, L.P.
is a registered trademark of Maytag Corporaon or its related companies and is used under license. All rights
reserved.
IMPORTANT SAFETY INSTRUCTIONS
The following symbols and labels are used throughout
this manual to indicate immediate or potential safety
hazards. It is the owner’s and installer’s responsibility to
read and comply with all safety information and instructions
accompanying these symbols. Failure to heed safety
information increases the risk of personal injury, property
damage, and/or product damage.
WARNING





CAUTION


“Proper sizing and installaon of equipment is crical to achieve opmal performance. Split system
air condioners and heat pumps must be matched with appropriate coil components to meet ENERGY
STAR criteria. Ask your contractor for details or visit www.energystar.gov.
IMPORTANT – This product has been designed and manufactured to meet ENERGY STAR criteria for
energy eciency when matched with appropriate coil components. However,
proper refrigerant charge and proper air ow are crical to achieve rated capacity and
eciency. Installaon of this product should follow the manufacturers refrigerant charging and air
ow instrucons. Failure to conrm proper charge and airow may reduce
energy eciency and shorten equipment life.
2
INDEX
1
3
3
3
3
4
4
5
7
8
10
 11
13
16
18
21
25
30
36
39
40
3
THE UNIT HAS ITS OWN PUMP-DOWN MODE. USE THE PUMP-DOWN
MODE WHILE VACUUMING THE UNIT. VACUUMING TOO LOW CAN
CAUSE INTERNAL ELECTRICAL ARCING, RESULTING IN A DAMAGED OR
FAILED COMPRESSOR.
CAUTION
SHIPPING INSPECTION
Always keep the unit upright; laying the unit on its side
or top may cause equipment damage. Shipping damage,
and subsequent investigation is the responsibility of
the carrier. Verify the model number, specications,
electrical characteristics, and accessories are correct
prior to installation. The distributor or manufacturer will not
accept claims from dealers for transportation damage or
installation of incorrectly shipped units.

This product is designed and manufactured to comply
with national codes. Installation in accordance with such
codes and/or prevailing local codes/regulations is the
responsibility of the installer. The manufacturer assumes
no responsibility for equipment installed in violation of any
codes or regulations. Rated performance is achieved after
20 hours of operation. Rated performance is delivered at
the specied airow. See outdoor unit specication sheet
for split system models or product specication sheet for
packaged and light commercial models. Specication
sheets can be found at www.goodmanmfg.com for
Goodman® brand products or www.amana-hac.com for
Amana® brand products. Within the website, please select
the residential or commercial products menu and then
select the submenu for the type of product to be installed,
such as air conditioners or heat pumps, to access a list
of product pages that each contain links to that model’s
specication sheet.
The United States Environmental Protection Agency (EPA)
has issued various regulations regarding the introduction
and disposal of refrigerants. Failure to follow these
regulations may harm the environment and can lead to
the imposition of substantial nes. Should you have any
questions please contact the local oce of the EPA.
If replacing a condensing unit, heat pump or air handler,
the system must be manufacturer approved and Air
Conditioning, Heating and Refrigeration Institute (AHRI)
matched.



NOTICE









Outdoor inverter units are approved for operation above
0°F in cooling mode and -20°F (RH10%) in heating mode
with no additional kit necessary.
Damage resulting from operation of the units in a structure
that is not complete (either as port of new construction or
renovation) is not covered by our warranties.
FEATURES
This air conditioner is part of a ComfortBridge™ control
system that uses inverter technology to more eciently
control heat gain/loss with better eciency and achieve
targeted comfort conditions.
The system utilizes digital communication between the
indoor and outdoor equipment and can be controlled by
any single-stage thermostat.
The ComfortBridge control system reduces the number
of required thermostat wires, provides additional setup
features and enhanced diagnostics through Bluetooth
connectivity with the CoolCloud™ app.
Due to components using inverter technology, the air
conditioner will not function properly if used with a non-
approved control system.
NOTICE





Special consideration must be given to location of the
condensing unit(s) in regard to structures, obstructions,
other units, and any/all other factors that may interfere with
air circulation. Where possible, the top of the unit should
be completely unobstructed; however, if vertical conditions
require placement beneath an obstruction there should
4
be a minimum of 60 inches between the top of the unit
and the obstruction(s). The specied dimensions meet
requirements for air circulation only. Consult all appropriate
regulatory codes prior to determining nal clearances.
Another important consideration in selecting a location for
the unit(s) is the angle to obstructions. Either side adjacent
the valves can be placed toward the structure provided the
side away from the structure maintains minimum service
clearance. Corner installations are strongly discouraged.


AA AAA
A
CC
CC




NOT
RECOMMENDED
AA
AA AA
AA
AA
B B B
B
Model Type A B C AA
Residential 10" 10" 18" 20"
12" 12" 18" 24"

This unit can be located at ground oor level or on at
roofs. At ground oor level, the unit must be on a solid,
level foundation that will not shift or settle. To reduce the
possibility of sound transmission, the foundation slab
should not be in contact with or be an integral part of the
building foundation. Care should be taken to ensure the
unit is installed away from noise sensitive locations such as
bedrooms, windows and outdoor living areas. Ensure the
foundation is sucient to support the unit. A concrete slab
raised above ground level provides a suitable base.

If it is necessary to install this unit on a roof structure,
ensure the roof structure can support the weight and that
proper consideration is given to the weather-tight integrity
of the roof. Since the unit can vibrate during operation,
sound vibration transmission should be considered when
installing the unit. Vibration absorbing pads or springs can
be installed between the condensing unit legs or frame and
the roof mounting assembly to reduce noise vibration.

The unit should be well grounded so that potential
eects of electrical noise from the inverter to surrounding
equipment can be minimized.
When selecting an installation location, keep sucient
distance from the air conditioner unit and wiring to radios,
personal computers, stereos, etc., as shown in the
following gure.
Circuit
Breaker
(In.)
Radio, TV
60 or more
To Indoor Unit and Thermostat
60 or more


While these items will not cover every conceivable
situation, they should serve as a useful guide.
T
O
AVOID
POSSIBLE
INJURY
,
EXPLOSION
OR
DEATH
,
PRACTICE
SAFE
HANDLING
OF
REFRIGERANTS
.
WARNING
T
O
AVOID
POSSIBLE
EXPLOSION
,
USE
ONLY
RETURNABLE
(
NOT
DISPOSABLE
)
SERVICE
CYLINDERS
WHEN
REMOVING
REFRIGERANT
FROM
A
SYSTEM
.
• E
NSURE
THE
CYLINDER
IS
FREE
OF
DAMAGE
WHICH
COULD
LEAD
TO
A
LEAK
OR
EXPLOSION
.
• E
NSURE
THE
HYDROSTATIC
TEST
DATE
DOES
NOT
EXCEED
5
YEARS
.
• E
NSURE
THE
PRESSURE
RATING
MEETS
OR
EXCEEDS
400
PSIG
.
W
HEN
IN
DOUBT
,
DO
NOT
USE
CYLINDER
.
WARNING
5
REFRIGERANTS
ARE
HEAVIER
THAN
AIR
. T
HEY
CAN
PUSH
OUT
THE
OXYGEN
IN
YOUR
LUNGS
OR
IN
ANY
ENCLOSED
SPACE
. T
O
AVOID
POSSIBLE
DIFFICULTY
IN
BREATHING
OR
DEATH
:
• N
EVER
PURGE
REFRIGERANT
INTO
AN
ENCLOSED
ROOM
OR
SPACE
. B
Y
LAW
,
ALL
REFRIGERANTS
MUST
BE
RECLAIMED
.
• I
F
AN
INDOOR
LEAK
IS
SUSPECTED
,
THOROUGHLY
VENTILATE
THE
AREA
BEFORE
BEGINNING
WORK
.
• L
IQUID
REFRIGERANT
CAN
BE
VERY
COLD
. T
O
AVOID
POSSIBLE
FROSTBITE
OR
BLINDNESS
,
AVOID
CONTACT
AND
WEAR
GLOVES
AND
GOGGLES
. I
F
LIQUID
REFRIGERANT
DOES
CONTACT
YOUR
SKIN
OR
EYES
,
SEEK
MEDICAL
HELP
IMMEDIATELY
.
• A
LWAYS
FOLLOW
EPA
REGULATIONS
. N
EVER
BURN
REFRIGERANT
,
AS
P
OISONOUS
GAS
WILL
BE
PRODUCED
.
WARNING
T
O
AVOID
POSSIBLE
EXPLOSION
:
•N
EVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLINDER. IF YOU
MUST HEAT A CYLINDER FOR FASTER CHARGING, PARTIALLY IMMERSE
IT IN WARM WATER.
•NEVER FILL A CYLINDER MORE THAN 80% FULL OF LIQUID
REFRIGERANT.
•NEVER ADD ANYTHING OTHER THAN R-410A TO A RETURNABLE
R-410A CYLINDER. THE SERVICE EQUIPMENT USED MUST BE LISTED
OR CERTIFIED FOR THE TYPE OF REFRIGERANT USE.
•STORE CYLINDERS IN A COOL, DRY PLACE. NEVER USE A CYLINDER
AS A PLATFORM OR A ROLLER.
WARNING

THE COMPRESSOR PVE OIL FOR R-410A UNITS IS EXTREMELY
SUSCEPTIBLE TO MOISTURE ABSORPTION AND COULD CAUSE
COMPRESSOR FAILURE. DO NOT LEAVE SYSTEM OPEN TO ATMOSPHERE
ANY LONGER THAN NECESSARY FOR INSTALLATION.
CAUTION
Use only refrigerant grade (dehydrated and sealed) copper
tubing to connect the condensing unit with the indoor unit.
After cutting the tubing, install plugs to keep refrigerant
tubing clean and dry prior to and during installation. Tubing
should always be cut square keeping ends round and free
from burrs. Clean the tubing to prevent contamination.
The liquid line must be insulated if more than 50 ft. of liquid
line will pass through an area that may reach temperatures
of 30 °F or higher than ambient in cooling mode and/or if
the temperature inside the conditioned space may reach a
temperature lower than ambient in heating mode. Never
attach a liquid line to any uninsulated potion of the suction
line.
Do NOT let refrigerant lines come in direct contact with
plumbing, ductwork, oor joists, wall studs, oors, and
walls. When running refrigerant lines through a foundation
or wall, openings should allow for sound and vibration
absorbing material to be placed or installed between tubing
and foundation. Any gap between foundation or wall and
refrigerant lines should be lled with a pliable silicon-
based caulk, RTV or a vibration damping material. Avoid
suspending refrigerant tubing from joists and studs with
rigid wire or straps that would come in contact with the
tubing. Use an insulated or suspension type hanger. Keep
both lines separate and always insulate the suction line.
Insulation is necessary to prevent condensation from
forming and dropping from the suction line. Armex or
satisfactory equivalent with 3/8” min. wall thickness is
recommended. In severe conditions (hot, high humidity
areas) 1/2” insulation may be required. Insulation must
be installed in a manner which protects tubing and
connections from damage and contamination.
Where possible, drain as much residual compressor
oil from existing systems, lines, and traps; pay close
attention to low areas where oil may collect. NOTE:
If changing refrigerant, the indoor coil and metering
device must be replaced. Only AVPEC** air handlers or
TXV-V** expansion valves are compatible and have been
manufacturer approved for use with these models. See unit
specications or AHRI for an approved system match.


 
23/4 3/8
37/8 3/8
41 1/8 3/8
51 1/8 3/8




If burying refrigerant lines can not be avoided, use the
following checklist:
1. Insulate liquid and suction lines separately.
2. Enclose all underground portions of the refrigerant
lines in waterproof material (conduit or pipe) sealing
the ends where tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete
slab, ensure lines are adequately protected and
sealed.
6
Air Condioner BELOW Indoor Coil
Air Condioning Unit
7

IMPORTANT
















1. The ends of the refrigerant lines must be cut square,
deburred, cleaned, and be round and free from nicks
or dents. Any other condition increases the chance of
a refrigerant leak.
2. Purge with nitrogen at 2 to 3 psig during brazing
to prevent the formation of copper-oxide inside
the refrigerant lines. The FVC oils used in R-410A
applications will clean any copper-oxide present
from the inside of the refrigerant lines and spread it
throughout the system. This may cause a blockage or
failure of the metering device.
3. After brazing, quench the joints with water or a wet
cloth to prevent overheating of the service valve.
4. A bi-ow lter drier is shipped with the unit as a
separate component and must be brazed on by the
installer on-site. Ensure the bi-ow lter drier paint
nish is intact after brazing. If the paint of the steel
lter drier has been burned or chipped, repaint or treat
with a rust preventative.
The recommended location of the lter drier is before the
expansion device at the indoor unit.



Do NOT make nal refrigerant line connection until plugs
are removed from refrigerant tubing.


WARNING



WARNING




Using dry nitrogen, pressurize the system to 450 PSIG.
Allow the pressure to stabilize and hold for 15 minutes
(minimum). If the pressure does not drop below 450 PSIG
the system is considered leak free. Proceed to system
evacuation using the Deep Vacuum Method. If after 15
minutes the pressure drops below 450 PSIG follow the
procedure outlined below to identify system leaks. Repeat
the Standing Pressure Test.

WARNING



WARNING




Leak test the system using dry nitrogen and soapy
water to identify leaks. If you prefer to use an electronic
leak detector, charge the system to 10 PSIG with the
appropriate system refrigerant (see Serial Data Plate
for refrigerant identication). Do not use an alternative
refrigerant. Using dry nitrogen nish charging the system
to 450 PSIG. Apply the leak detector to all suspect areas.
When leaks are discovered, repair the leaks, and repeat
the pressure test. If leaks have been eliminated proceed to
system evacuation.

Condensing unit liquid and suction valves are closed to
contain the charge within the unit. The unit is shipped with
the valve stems closed and caps installed. Do not open
valves until the system is evacuated.
8
WARNING






CAUTION





The Deep Vacuum Method requires a vacuum pump
rated for 500 microns or less. This method is an eective
and ecient way of assuring the system is free of non-
condensable air and moisture. As an alternative, the Triple
Evacuation Method is detailed in the Service Manual for
this product model.
It is recommended to remove the Schrader Cores from the
service valves using a core-removal tool to expedite the
evacuation procedure.
1. Connect the vacuum pump, micron gauge, and
vacuum rated hoses to both service valves.
Evacuation must use both service valves to eliminate
system mechanical seals.
2. Evacuate the system to less than 500 microns.
3. Isolate the pump from the system and hold vacuum
for 10 minutes (minimum). Typically, pressure will rise
slowly during this period. If the pressure rises to less
than 1000 microns and remains steady, the system is
considered leak-free; proceed to system charging and
startup.
4. If pressure rises above 1000 microns but holds steady
below 2000 microns, non-condensable air or moisture
may remain or a small leak is present. Return to step
2: If the same result is achieved check for leaks and
repair. Repeat the evacuation procedure.
5. If pressure rises above 2000 microns, a leak is
present. Check for leaks and repair. Repeat the
evacuation procedure.
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0 1 2 3 4 5 6 7 8 9 10

PRESENT
MINUTES
VACUUM IN MICRONS


NO 
NO 

HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRIC
SHOCK
. W
IRING
MUST
CONFORM
WITH
NEC
OR
CEC
AND
ALL
LOCAL
CODES
. U
NDERSIZED
WIRES
COULD
CAUSE
POOR
EQUIPMENT
PERFORMANCE
,
EQUIPMENT
DAMAGE
OR
FIRE
.
WARNING
T
O
AVOID
THE
RISK
OF
FIRE
OR
EQUIPMENT
DAMAGE
,
USE
COPPER
CONDUCTORS
.
WARNING
GROUNDING REQUIRED!
A
LWAYS
INSPECT
AND
USE
PROPER
SERVICE
TOOLS
. L
ACK
OF
INSPECTION
OR
IMPROPER
TOOLS
MAY
CAUSE
EQUIPMENT
DAMAGE
OR
PERSONAL
INJURY
. A
LL
DISCONNECTED
GROUNDING
DEVICES
MUST
BE
RECONNECTED
BEFORE
INSTALLING
OR
SERVICING
. M
ULTIPLE
COMPONENTS
OF
THIS
UNIT
MAY
CONDUCT
ELECTRICAL
CURRENT
;
THESE
ARE
GROUNDED
. I
F
SERVICING
THE
UNIT
,
ANY
DISCONNECTION
OF
GROUNDING
WIRES
,
SCREWS
,
STRAPS
,
CLIPS
,
NUTS
OR
WASHERS
USED
TO
COMPLETE
THE
GROUND
MUST
BE
RETURNED
TO
THEIR
ORIGINAL
POSITION
AND
PROPERLY
FASTENED
.
CAUTION
9
NOTICE












The air conditioning unit rating plate lists pertinent
electrical data necessary for proper electrical service and
overcurrent protection. Wires should be sized to limit
voltage drop to 2% (max.) from the main breaker or fuse
panel to the condensing unit. Consult the NEC, CEC, and
all local codes to determine the correct wire gauge and
length.
Local codes often require a disconnect switch located near
the unit; do not install the switch on the unit.

The inverter control system software provides sucient
time delay to protect from overcurrent conditions and
permit the compressor and fan motors to adjust their
rotational speed.

Route power supply and ground wires through the high
voltage port and terminate in accordance with the wiring
diagram provided inside the control panel cover.
Make sure to apply the rated voltage of 208/230V for
the unit.
Use conduit for power supply cables.
A power circuit (see the production specication
sheet or the unit serial plate) must be provided for
connection of the unit. This circuit must be protected
with the required safety devices.
When using residual current operated circuit breakers,
be sure to use a high-speed type (0.1 seconds or
less) 200 mA rated residual operating current.
Use copper conductors only.
Use insulated wire for the power cord.
Select the power supply cable type and size
in accordance with relevant local and national
regulations.
Outside the unit, make sure to keep the wirings 5 inch
away. Otherwise, the outdoor unit may be aected by
electrical noise (external noise), and malfunction or
fail.
Make sure the wirings will not be pinched by the front
panel, and close the panel rmly.
Route the conduit along the unit and so on to prevent
wirings from being stepped on.

The unit is designed to work as part of a fully
communicating HVAC system, utilizing either:
ComfortBridge compatible indoor unit with any 24V
single stage thermostat.
CTK04AE or newer thermostat (If paired with
ComfortNet compatible indoor unit.)
Route control wires through the low voltage port and
terminate in accordance with the wiring diagram provided
inside the control panel cover.


ComfortBridge control system low voltage wiring consists
of two wires between the indoor unit and outdoor unit. The
required wires are data lines 1 and 2.
The thermostat needs 4 wires between the indoor unit and
thermostat or 5 wires if the thermostat requires a Common
wire.
Regarding the wiring of the indoor unit to the thermostat,
also refer to ComfortBridge compatible indoor unit’s Install
manual (in case of communicating inverter system.).
If installing with a CTK04 thermostat, please see the
addendum for further instructions.
10



Adequate refrigerant charge for the matching indoor coil
and 15 feet of line set is supplied with the condensing
unit. If liquid line set exceeds 15 feet in length, refrigerant
should be added at 0.6 ounces per foot of liquid line.

Liquid and suction valves on condensing unit are closed to
contain the charge within the unit. The unit is shipped with
the valve stems closed and caps installed. Do not open
valves until the indoor coil and line set is evacuated.


The condenser unit is shipped with a predetermined factory
charge level as shown in unit serial plate. For longer line
sets greater than 15 feet, add 0.6 ounces of refrigerant per
foot. Refer to the following page for the equivalent length of
the elbow ttings.
NOTICE
TOTAL REFRIGERANT =
FACTORY CHARGE + (0.6 OZ./FT. * ADDITIONAL FEET
OF ACTUAL LINE SET).

CAUTION
OPEN THE LIQUID VALVE FIRST! IF THE SUCTION SERVICE VALVE IS OPENED
FIRST, OIL FROM THE COMPRESSOR MAY BE DRAWN INTO THE INDOOR
COIL TXV RESTRICTING
REFRIGERANT FLOW AND AFFECTING OPERATION OF THE SYSTEM.
POSSIBLE REFRIGERANT LEAK!
TO
AVOID
A
POSSIBLE
REFRIGERANT
LEAK, OPEN
THE
SERVICE
VALVES
UNTIL
THE
TOP
OF
THE
STEM
IS 1/8” FROM
THE
RETAINER.
CAUTION
ENSURE
VALVES
ARE
OPEN
AND
ADDITIONAL
CHARGE
IS
ADDED
BEFORE
APPLYING
POWER.
CAUTION
After the refrigerant charge has bled into the system, open
the liquid service valve.
When opening valves with retainers, open each valve
only until the top of the stem is 1/8” from the retainer. To
avoid loss of refrigerant, DO NOT apply pressure to the
retainer. When opening valves without a retainer, remove
service valve cap and insert a hex wrench into the valve
stem and back out the stem by turning the hex wrench
counterclockwise. Open the valve until it contacts the rolled
lip of the valve body.
The service valve cap is the secondary seal for the valves
and must be properly tightened to prevent leaks. Make
sure cap is clean and apply refrigerant oil to threads and
sealing surface on inside of cap. Tighten cap nger-tight
and then tighten additional 1/6 of a turn to properly seat the
sealing surfaces.
Do not introduce liquid refrigerant from the cylinder into the
crankcase of the compressor (suction side) as this may
damage the compressor.
Break vacuum by fully opening liquid and gas base valve.








11

NOTICE



A system verication test is now required to check the
equipment settings and functionality.
Inverter units are tested by any of the following methods:
Setting the “SUt” menu (System verication test)
to ON through the indoor unit control board push
buttons.
Setting the System verication test menu of mode
display screen-4 to ON through the outdoor unit
control board push buttons.
Through the CoolCloud HVAC phone application
Once selected, it checks the equipment for approximately 5
- 15 minutes. System test may exceed 15 minutes if there
is an error. Refer to the Troubleshooting section.
NOTICE




The CoolCloud HVAC phone application was designed
to improve the contractor’s setup /diagnostic experience.
This application can only be used with ComfortBridge
compatible indoor units and can be downloaded through
the Google Play or Apple App Store.
Users can see specic model information, review active
diagnostic error codes, observe system status during
operation, make system menu adjustments, add site visit
notes and run system testing of all operational modes (heat
/ cool / fan) directly from the phone.
If installing with a CTK04 thermostat, please see the
addendum for further instructions.

CHARGE MODE allows for charging of the system.
System operates for a duration of approximately one hour
while the equipment runs at full capacity.
After one hour, the CHARGE MODE ends and the system
resumes normal operation.
Before starting the CHARGE MODE, turn o the Cool or
Heat mode and electric heater or gas furnace.
a. Inverter units are charged by any of the following
methods:
Setting the “CR9” menu (Charge Mode) to ON
through the indoor unit control board push buttons.
Setting the Charge mode menu of mode display
screen-4 to ON through the outdoor unit control board
push buttons.
Through the CoolCloud HVAC phone application.
b. The System will remain in charge mode (high speed)
for 60 minutes before timing out.
c. When charge mode is complete, the installer must
manually shut o.
If installing with a CTK04 thermostat, please see the
addendum for further instructions.

Using service equipment, add or recover refrigerant
according to the calculation in Step 1. Allow system to
stabilize for 10 minutes after adjusting charge level.



1. Purge gauge lines.
2. Connect service gauge manifold to base valve service
ports.
3. Convert the liquid pressure to temperature using a
temperature/pressure chart.
4. Temporarily install a thermometer on the liquid line at
the liquid line service valve.
a. Ensure the thermometer makes adequate contact
and is insulated for best possible readings.
5. Subtract the liquid line temperature from the
converted liquid pressure to determine subcooling.
6. Before starting the subcooling adjustment, make sure
the outdoor ambient temperature is in a below range
and the unit is operating at 100% capacity.
7. For EEV Indoor Unit: If the system subcooling is not
within the ranges shown in the following table, adjust
subcooling according to the following procedure:
a. If subcooling is low, add charge to adjust the
subcooling as specied in the following table.
b. If subcooling is high, remove charge to lower the
subcooling to 8° ± 1°F.


12

OD AMBIENT TEMP
(degF)
Subcooling Weigh in 2T to 4T: 8°F ± 1°F Weigh in
(degF) Charge 5T: 10°F ± 1°F Charge
< 65° F 65° F to 105° F > 105° F
NOTE: Subcooling information is only valid while the unit is
operating at 100% capacity or 100% of compressor speed in
CHARGE MODE. Compressor speed is displayed under
STATUS menu in the thermostat.
8. For TXV Indoor Unit
The system subcooling should be 8°F ± 1°F. If not
in that range, adjust subcooling and superheat
according to the following procedure.
a. If subcooling and superheat are low, adjust TXV
to 8°F ± 1°F superheat, then check subcooling.



b. If subcooling is low and superheat is 8°F ± 1°F,
add charge to rise subcooling to 8°F ± 1°F, then
check superheat.
c. If subcooling is low and superheat is high, add
charge to rise subcooling to 8°F ± 1°F, then check
superheat.
d. If subcooling is 8°F ± 1°F and superheat is high,
adjust the TXV valve to 8°F ± 1°F superheat, then
check subcooling.
e. If subcooling and superheat are high, adjust the
TXV valve to 8°F ± 1°F superheat, then check
subcooling.
f. If subcooling is high and superheat is 8°F ± 1°F,
remove charge to lower the subcooling to 8°F ±
1°F, then check superheat.
g. If subcooling is high and superheat is low, adjust
the TXV valve to 8°F ± 1°F superheat and remove
charge to low the subcooling to 8°F ± 1°F.
h. If subcooling is 8°F ± 1°F and superheat is low,
adjust the TXV valve to 8°F ± 1°F superheat and
remove charge to lower the subcooling 8°F ± 1°F,
then check the superheat.




C
HECK
THE
S
CHRADER
PORTS
FOR
LEAKS
AND
TIGHTEN
VALVE
CORES
,
IF
NECESSARY
. I
NSTALL
CAPS
FINGER
-
TIGHT
.
NOTICE
D
O
NOT
ADJUST
THE
CHARGE
BASED
ON
SUCTION
PRESSURE
UNLESS
THERE
IS
A
GROSS
UNDERCHARGE
.
NOTICE
SUCTION PRESSURE
PSIG
R-410A °F LIQUID PRESSURE
PSIG
R-410A °F
50 1 200 70
52 3 210 73
54 4 220 76
56 6 225 78
58 7 235 80
60 8 245 83
62 10 255 85
64 11 265 88
66 13 275 90
68 14 285 92
70 15 295 95
72 16 305 97
74 17 325101
76 19 355108
78 20 375112
80 21 405118
85 24 415119
90 26 425121
95 29 435123
100 31 445125
110 36 475130
120 41 500134
130 45 525138
140 49 550142
150 53 575145
160 56 600149
170 60 625152
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
SATURATED LIQUID PRESSURE
TEMPERATURE CHART
















 




13
 
1ON CT Communication Terminal Resister
2ON CT Communication Terminal Resister
1ON Cooling Emergency Mode*
2ON Cooling Emergency Mode*


DS1
DS2
* DS2 sw itch 1 and 2 both must be turned on during normal operation mode

BOOST MODE can be enabled or disabled through the
control board push buttons or through the CoolCloud app.
BOOST MODE allows the system to operate at increased
compressor speed to satisfy unusually high loads. BOOST
MODE is initiated by an outdoor temperature sensor
located in the outdoor unit.
Please note that outdoor equipment operational sound
levels may increase while the equipment is running in
BOOST MODE. Disabling BOOST MODE will provide the
quietest and most ecient operation.


BOOST MODE is ON by default and is activated when the
outdoor temperature reaches 105°F. BOOST MODE can
be disabled and enabled and the activation temperature
adjusted in the Settings menu of the CoolCloud app or
through the indoor / outdoor push button menus.
If installing with a CTK04 thermostat, please see the
addendum for further instructions.






Dehumidication requires a thermostat capable of reading
the indoor humidity level and allowing the user to set a
dehumidication target.
The thermostat controls the humidity level of
the conditioned space using the cooling system.
Dehumidication is engaged whenever a cooling demand
is present and humidity levels are above the target level.
When this condition exists, the circulating fan output is
reduced, increasing system run time, over cooling the
evaporator coil and ultimately removing more humidity from
the structure than if only in cooling mode.
The thermostat may also allow for an additional
overcooling limit setting depending on the thermostat
utilized. This allows the cooling system to further reduce
humidity by lowering the temperature below the cooling
setpoint in an attempt to better achieve desired humidity
levels.

For eective dehumidication operation:
Ensure “Dehumidication selection” is NOT set to
“OFF”.
Verify the cooling airow prole is set to “Prole D”.
- See the Cool Set-up section of the Installation Manual for
complete airow prole details.
- By default, “Dehumidication selection” is standard and
the cooling airow prole is set to “Prole D”.
For additional dehumidication control, airow settings
are eld adjustable and can be ne-tuned to a value
that is comfortable for the application from a range of
Cool Airow Trim.
In addition, the system can have Enhanced
Dehumidication operation in setting “A”, “B”,
or “C” of “Dehumidication Selection” based on
dehumidication demand.
- See the DEHUMIDIFICATION SELECT section of the
Installation Manual for more detail.


The ComfortBridge based inverter heating and air
conditioning system uses an indoor unit and outdoor unit
digitally communicating with one another via a two-way
communications path. ComfortBridge is compatible with
any 24 VAC single stage thermostat which sends inputs to
the indoor unit.

The ComfortBridge system permits access to system
information, advanced set-up features, and advanced
diagnostic/troubleshooting features via the control board
push buttons or the CoolCloud HVAC app.
(If using a CTK04 thermostat, please see the addendum
for further instructions.)

The air conditioner’s diagnostics menu provides access
to the most recent faults. The six most recent faults can
be accessed through the control board seven segment
displays or the CoolCloud mobile app. Any consecutively
repeated fault is stored a maximum of three times.
Example: A leak in the system, low refrigerant charge or an
incompletely open stop valve can cause the unit to ash
error code E15. This error code suggests that the unit is
experiencing operation at low pressure. The control will
only store this fault the rst three consecutive times the
fault occurs.



14

This menu displays information about the systems current
status. This menu can be utilized to conrm correct
functionality of the equipment and for troubleshooting
purposes.
The following items will be displayed:
Heat Capacity Request Percentage
Cool Capacity Request Percentage
Heat Capacity Request During Defrost Percentage
Dehumidication Request Percentage
Reversing Valve Status
Reported Airow by Indoor Unit
Boost Mode
Previous Defrost Run Time
* Information specic to the heat pump is not
displayed.

The following sensor values will be displayed:
Outdoor Temperature
Coil Temperature
Liquid Line Temperature
Discharge Temperature
Defrost Sensor
Suction Pressure

This function can be enabled in this menu.
* Information specic to the heat pump is not displayed.

The system allows for the adjustment of several cooling
performance variables. Cool Airow Trim (*1), Cool Airow
Proles, Cool Fan ON Delay, Cool Fan OFF Delay and
Dehumidication Select (some enable option or o) can
be adjusted in this menu. You can also reset this entire
menu to factory default settings. See the following images
showing the four cooling airow proles.

 provides only an OFF delay of one (1)
minute at 100% of the cooling demand airow.
 ramps up to full cooling demand airow
by rst stepping up to 50% of the full demand for
30 seconds. The motor then ramps to 100% of the
required airow. A one (1) minute OFF delay at 100%
of the cooling airow.
50% CFM
1/2 min
100% CFM 100% CFM
1 min
OFF OFF
 ramps up to 82% of the full cooling demand
airow and operates there for approximately 7 1/2
minutes. The motor then steps up to the full demand
airow. Prole C also has a one (1) minute 100% OFF
delay.
100% CFM
OFF OFF
 (default) ramps up to 50% of the demand
for 1/2 minute, then ramps to 82% of the full cooling
demand airow and operates there for approximately
7 1/2 minutes. The motor then steps up to the full
demand airow. Prole D has a 1/2 minute at 50%
airow OFF delay.
OFF
OFF

*1
1. At Cool and Heat Hi speed trim, *VXC200601* with
**VC960804C, **VM970804C and *MVC800804C
combination trim more than 5% settings are invalid.
Trimmed up CFM makes miss matching error.
2. At Cool Hi speed trim, Other than the above,
depending on the connected indoor unit, there are
restrictions on the positive side Trim setting.
If you want to change the Cool Airow Trim to positive
side, be sure to conrm the Airow Trim restrictions
in the latest indoor unit installation manual. The
latest manual can be obtained from the website
“PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/
goodman/info-nder-plus
3. The Inverter system uses lower compressor speed
and lower indoor unit CFM to optimize system
performance. To obtain 100% CFM for home
circulation, use full Trim setting instead of Int/
Low speed. This is recommended for applications
with unusually cold return temperatures such as
basements.
15

Dehumidication requires a thermostat capable of reading
the indoor humidity level from the thermostat and allows
the user to set a dehumidication target based on these
settings.
The thermostat controls the humidity level of
the conditioned space using the cooling system.
Dehumidication is engaged whenever a cooling demand
is present and structural humidity levels are above the
target level. When this condition exists, the circulating fan
output is reduced, increasing system run time, over cooling
the evaporator coil and ultimately removing more humidity
from the structure than if only in cooling mode.
The thermostat may also allow for an additional
overcooling limit setting depending on the thermostat
utilized. This allows the cooling system to further reduce
humidity by lowering the temperature below the cooling
setpoint in an attempt to better achieve desired humidity
levels.
When Dehumidication mode exists, the circulating fan
output is reduced, increasing system run time, over cooling
the evaporator coil and ultimately removing more humidity
from the structure than if only in cooling mode.
The system can have Dehumidication operation in setting
“Standard”, “A”, “B” or “C” of “dehumidify with cooling”
menu based on dehumidication demand.
Setting “Standard” allows for the widest compressor
operation range with lower CFM than Cooling mode.
In the Enhanced Dehumidication (setting A, B and C)
the indoor airow is lower than Standard Dehumidication
(Standard).
Setting “A” allows for the same compressor operation
range as standard Dehumidication with lower CFM than
standard dehumidication (Standard).
Setting “B” limits compressor operation range and keeps
high dehumidication capacity.
In setting “C” the system runs xed at 100% compressor
and airow. See Figure 1.









Max compressor speed at which the outdoor unit will
operate can be changed through the control board seven
segment displays or the CoolCloud mobile app.
Max compressor speed can be changed to get the required
capacity or eciency.
Once the maximum speed is set, the system operates
between the set maximum speed and default low speed.
When determining the appropriate compressor speed
for cooling and heating, in the “RPS Range For Cooling/
Heating” menu select the range that contains the desired
value.
(Then, after pressing the Apply Changes button, leave the
Device setting menu and enter the this menu again.
Otherwise, the changed settings will not be reected.)
Next, in the “Selected RPS for Cooling/Heating” menu,
select the desired RPS within the displayed range.
16

A representative menu is posted. Item names and setting value are subject to change.
SUBMENU ITEM INDICATION/USER MODIFIABLE OPTIONS COMMENTS
ALL (The Active and History Fault codes are displayed.) Active fault code and up to 6 fault code histories.
ACTIVE (The Active Fault codes are displayed.) Active fault code only.
HISTORY (The History Fault codes are displayed .) Up to 6 fault code histories.
REFRESH N/A Selecting this menu will refresh the display.
SUBMENU ITEM INDICATION/USER MODIFIABLE OPTIONS COMMENTS
HVAC DEVICE AIR CONDITIONER(AC)
The type of HVAC Device.
FIRMWARE VERSION **
Specific number associated with the control
software.
MODEL NUMBER *VXC200*01*
This number match the model name found on the
serial plate.
SERIAL NUMBER *********
This number match the serial number found on the
serial plate.
SUBMENU ITEM INDICATION(Units) COMMENTS
COOL CAPACITY REQUEST %
The request for cooling.
0% means the system is off.
All other values mean the system is running.
DEHUMIDIFICATION REQ UEST %
Request for dehumidification.
0% means dehumidification is not being requested.
All other values mean dehumidification is being
requested.
OUTDOOR FAN SPEED RPM
Current speed of the outdoor fan in rotations per
minute.
REQUESTED AIRFLOW CFM
This is the airflow the indoor unit will try to deliver
while the unit is active.
REPORTED AIRFLOW CFM
Indoor airflow (in cubic feet per minute) as reported
by the indoor unit.
BOOST MODE OFF or ON
If this feature is available and enabled, an inverter
can ramp the compressor above default speeds to
increase capacity.
This shows if the feature is active or inactive.
To check if this function is enabled, find the Boost
Mode Enable item in the setting for this unit.
SUBMENU ITEM INDICATION(Units) COMMENTS
OUTDOOR TEMP FDisplays the outdoor air temperature.
LIQUID LINE TEMP FDisplays the outdoor liquid temperature.
DISCHARGE TEMP FDisplays the outdoor discharge temperature.
SUCTION PRESSURE PSI
Displays the pressure of taken slightly upstream of
the suction accumulator.




17

A representative menu is posted. Item names and setting value are subject to change.
*1 At Cool and Heat Hi speed trim, *VXC200601* with **VC960804C, **VM970804C and *MVC800804C combination trim more than 5% settings are
invalid. Trimmed up CFM makes miss matching error.
*2 Other than the above, depending on the connected indoor unit, there are restrictions on the positive side Trim setting.
If you want to change the Cool Airow Trim to positive side, be sure to conrm the Airow Trim restrictions in the latest indoor unit installation manual.
The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info-nder-plus
*3 The Inverter system uses lower compressor speed and lower indoor unit CFM to optimize system performance.
To obtain 100% CFM for home circulation, use full Trim setting instead of Int/Low speed.
This is recommended for applications with unusually cold return temperatures such as basements.
*4 Please refer to the page of “DEHUMIDIFICATION SELECT “ for details of this function.
SUBMENU ITEM INDICATION(Units) COMMENTS
BOOST MODE ENABLE OFF or ON BOOST MODE is ON by default. See BOOST MODE
section of this manual for more details.
BOOST TEMP Always Active or 70F to 105F in increments
If enabled, when the ambient outdoor temperature is
greater than this selected value, boost mode will be
operational.
Below this temperature the mode will not function.
There is also an option to keep boost mode
countinuously enabled.
INDOOR/OUTDOOR HEIGHT DIFFERENCE
Both Units at Same Level,
Outdoor Unit is Lower, or
Indoor Unit is Lower
If the outdoor & indoor units are within +/- 15 ft. vertical
distance, select SAME LEVEL. If the outdoor unit is
more than 15 ft. below the indoor unit, select OUTDOOR
LOWER. If the outdoor unit is more than 15 ft. above the
indoor unit, select INDOOR LOWER.
RESET FOR SYSTEM SETUP NO or YES Selecting yes will reset any system setting to their factor
y
defaults.
SYSTEM VERIFICATION TEST OFF or ON
System Verification Test must be run after installation.
This is approximately a 5-15 minute test. If operation
mode is set to COOL mode, the system will enter
CHARGE mode upon completion, otherwise it will stop.
PUMP DOWN OFF or ON
Enter PUMP DOWN Mode.
This procedure runs the equipment for approximately 15
minutes and allows accumulation of refrigerant at
the outdoor unit for purposes of removing & replacing th
e
indoor unit or outdoor unit.
ACTIVATE CHARGE MODE OFF or ON
Enter Charging Mode. This allows for a steady system
operation for a duration of approximately 1 hour to allow
for refrigerant charging of the system via the charge port.
COOLING TRIM FACTOR(HIGH)
*1, 2 -15% to +15% in 5% increments Select this airflow trim when inverter system is running
high compressor speeds during a cooling cycle.
COOLING TRIM FACTOR(MID) -15% to +15% in 5% increments,20 30, Full(Max)
*3
Select this airflow trim when inverter system is running
mid-range (intermediate) compressor speeds during a
cooling cycle.
COOLING TRIM FACTOR(LOW) -15% to +15% in 5% increments,20 30, Full(Max)
*3 Select this airflow trim when inverter system is running
low compressor speeds during a cooling cycle.
COOLING AIRFLOW PROFILE A, B, C, or D
If it is desirable to quickly ramp up the indoor airflow
select profile A.
If it is desirable to reach nominal airflow quickly, but a
slower ramp up time is required, select profile B.
If dehumidification is required immediately when cooling
mode begins select profile C.
If a slower airflow ramp up / ramp down time is required
in addition to dehumidification select profile D.
BLOWER ON DELAY-COOLING 5, 10, 20 or 30 Seconds Delay between compressor turning on and indoor blower
turning on during a cooling cycle.
BLOWER OFF DELAY-COOLING 30, 60, 90 or 120 Seconds Delay between compressor shutting off and the indoor
blower shutting off after a cooling cycle.
DEHUMIDIFICATION ENABLE*4 Standard, OFF, A, B or C Selecting "OFF" disables dehumidification selecting.
"Standard", "A", "B" or "C" enables dehumidification.
RESET COOLING SETTINGS NO or YES Selecting yes will reset any cooling setting to their
factory defaults.
RPS RANGE FOR COOLING **.* to **.* RPS,…(Total 5 Ranges)
When determining the appropriate compressor speed for
cooling, select the range that contains the desired value.
The Selected RPS for Cooling menu is where you will
select your desired value within this selected range.
SELECTED RPS FOR COOLING **.* RPS
This value will be a number inside the RPS Range for
Cooling.
If you'd like to select a RPS from a different range, you
must change the RPS Range for Cooling setting first,
then restart the device setting page
RESET FAULT HISTORY NO or YES Selecting yes will clear the fault histories of device.
AIR CONDITIONER(AC) / DEVICE SETTING
18





Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
*VXC200241**; *VXC200361**
1.THE POSITION OF THE SELECTOR SWITCHES (DS1/DS2) INDICATE FACRTORY SETTING.
2. MOTOR OVERLOAD PROTECTION PROVIDED BY INVERTER: SEE TABLE
3. USE COPPER CONDUCTORS ONLY.
4. CLASS 2 WIRE
NOTES:
0
X11A
AMBIENT
SEG
1
SEG
2
SEG
3
U
V
W
BK
RD
YL
BK
WH
RD
L2
L1
TERMINAL BLOCK
FIELD WIRING
H/LPT
COMPRESSOR
TERMINAL ORIENTATION
X108A
Z1C
Z2C
1
2
R
C
W1
Y1
Y2
L
TO INDOOR
UNIT
X17A +
-
HPS
E1
HR1 HR3
BR
WH
HR2
HR4
X32A
X851A
POWER CONDITIONER
X12A
LIQUID LINE
DISCHARGELINE
GR
RD
Z3C
RD
BK
PU
GROUND LUG
V
W
U
NOTE 1
1
OFF
ON
SEE NOTE 3
SEE NOTE 3
2
X52A
SHARE DATA
Z4C
BS1 BS2 BS3
COILCIRCUIT
RD YL
GR
M1C
M1F
+
-
THERMISTOR/TEMPRATURE SENSOR
MOTOR
HIGH/LOW PRESSURE TRANSDUCER(H/LPT)
HIGH PRESSURE SWITCH(HPS)
DS1/DS2 DIP SWITCH
SEG1-SEG3 7-SEGEMENT DISPLAY
Z1C-Z4C FERRITE CORE
BS1-BS3 PUSH BUTTON SWITCH
M1C COMPRESSOR MOTOR
M1F FAN MOTOR
TERMINAL
CONNECTOR
NOISLESS EARTH
ELECTRICAL GROUND
HIGH VOLTAGE
LOW VOLTAGE
HIGH VOLTAGE FIELD
COMPONENT CODE
NOTE 1
1
OFF
ON
DS1
2
INVERTER BOARD
GY
BK
RING
COLOR
0140R00352-G
DS2
208-230 V
60 HZ
SEE NOTE 4
COLOR CODE:
RD-----------------
BR-----------------
GR-----------------
BK-----------------
WH---------------
YL-----------------
BL-----------------
PU----------------
GY-----------------
RED
BROWN
GREEN
BLACK
WHITE
YELLOW
BLUE
PURPLE
GRAY
SEE NOTE 3
ON
ON OFF
19





Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
*VXC200481**
1. THE POSITION OF THE SELECTOR SWITCHES (DS1/DS2) INDICATE FACTORY SETTING.
2. MOTOR OVERLOAD PROTECTION PROVIDED BY INVERTER: SEE TABLE
3. USE COPPER CONDUCTERS ONLY.
4. CLASS 2 WIRE
NOTES:
1
2
R
C
W1
Y1
Y2
L
0
TO INDOOR
UNIT
X11A
AMBIENT
SEG
1
SEG
2
SEG
3
X17A
X851A
X99A
HPS
RD RD BL
M1C
BK
RD
YL
M1F
BK
WH
RD
RD
L2BL1B
BK
NOISE FILTER
BOARD
L2AL1A
BK
RD
L1C L2C
TERMINAL BLOCK
FIELD
WIRING
H/LPT
GND
INVERTER BOARD
COMPRESSOR
TERMINAL ORIENTATION
X32A
X108A
GR
+
-
Z1C
Z2C
Z3C
X12A
COIL INLET
LIQUID LINE
DISCHARGE LINE
U
V
W
1
OFF
ON
DS2
2
NOTE 1
BS1 BS2 BS3
X111A
FIN THERMISTOR
X52A
SHARE DATA
NOTE 1
1
OFF
ON
DS1
2
X98A
RING
COLOR
RD
YL
GY
BK
+
-
THERMISTOR/TEMPRATURE SENSOR
MOTOR
HIGH/LOW PRESSURE TRANSDUCER(H/LPT)
HIGH PRESSURE SWITCH(HPS)
DS1/DS2 DIP SWITCH
SEG1-SEG3 7-SEGEMENT DISPLAY
Z1C-Z3C FERRITE CORE
BS1-BS3 PUSH BUTTON SWITCH
M1C COMPRESSOR MOTOR
M1F FAN MOTOR
TERMINAL
CONNECTOR
NOISLESS EARTH
ELECTRICAL GROUND
HIGH VOLTAGE
LOW VOLTAGE
HIGH VOLTAGE FIELD
COMPONENT CODE
NOTE 3
SEE NOTE 3
W
U
V
0140R00353-G
GR
GR E1
208-230 V
60 HZ
SEE NOTE 4
COLOR CODE:
RD-----------------
BR-----------------
GR-----------------
BK-----------------
WH---------------
YL-----------------
BL-----------------
RED
BROWN
GREEN
BLACK
WHITE
YELLOW
BLUE
SEE NOTE 3
ON
ON OFF
20





Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
*VXC200601**
TO INDOOR
UNIT
SEG1 SEG2 SEG3
X17A
X851A
X99A
HPS
U
V
WM1C
BK
RD
YL
M1F
BK
WH
RD
WH
OR
TERMINAL
BLOCK
FIELD
WIRING
H/LPT
GND
INVERTER BOARD
COMPRESSOR
TERMINAL
ORIENTATION
X32A
GR
+
-Z1C
Z2C
L1A
L2A
L1B
L2B
X98A
NOISE FILTER
BOARD
L2C L1C
X11A
AMBIENT
X111A
FIN THERMISTOR
X202A
X301A
X108A
X302A
P
N
L1D
L1E
X201A
GY
WH
WH
WH
W
U
V
FAN CONTROL
BOARD
POWER
CONDITIONER
BR
BK
CURRENT SENSOR
X12A
COIL CIRCUIT
LIQUID LINE
DISCHARGE LINE
X101A
NOTE 1
1
OFF
ON
DS2
2
1. THE POSITION OF THE SELECTOR SWITCHES (DS1) INDICATE FACTORY SETTING.
2. MOTOR OVERLOAD PROTECTION PROVIDED BY INVERTER: SEE TABLE
3. USE COPPER CONDUCTORS ONLY.
4. CLASS 2 WIRE
NOTES:
BS1 BS2 BS3
+
-
THERMISTOR/TEMPRATURE SENSOR
MOTOR
HIGH/LOW PRESSURE TRANSDUCER(H/LPT)
HIGH PRESSURE SWITCH(HPS)
DS1/DS2 DIP SWITCH
SEG1-SEG3 7-SEGEMENT DISPLAY
Z1C-Z2C FERRITE CORE
BS1-BS3 PUSH BUTTON SWITCH
M1C COMPRESSOR MOTOR
M1F FAN MOTOR
TERMINAL
CONNECTOR
NOISLESS EARTH
ELECTRICAL GROUND
HIGH VOLTAGE
LOW VOLTAGE
HIGH VOLTAGE FIELD
CRANKCASE HEATER(CH)
COMPONENT CODE
CAPACITOR
X28A
CH
GR
RD
RD
BL
BK
RD
BK
RD
RD
YL
RING
COLOR
BK
GY
0140R00354-H
NOTE 1
1
OFF
ON
DS1
2
X52A
SHARE DATA
SEE NOTE 3
NOTE 3
208-230 V
60 HZ
THESE WIRES GO
THROUGH THE
CURRENT SENSOR HOLE
1
2
R
C
W1
Y1
Y2
L
0
COLOR CODE:
RD-----------------
BR-----------------
GR-----------------
BK-----------------
WH---------------
YL-----------------
BL-----------------
RED
BROWN
GREEN
BLACK
WHITE
YELLOW
BLUE
SEE NOTE 4
SEE NOTE 3 ON
ON OFF
/