  • Hello! I am an AI chatbot trained to assist you with the Danfoss Manifold Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Manifold
With 10 x EVUB 3 NC (Normally Closed)
Max. opening differential pressure MOPD: Coil dependent
Max. working pressure: 45,2 bar g / 655 psi g
Max. temperature of medium: −40°C to +105°C / −40°F to +220°F
Ambient temperature : −40°C to +60°C / −40°F to +140°F
©Danfoss A/S (AC-AKC / frz), 01-2010 DKRCC.PI.BDO.B1.02-520H4074
032R9550
032R9550
Instructions
Be sure that the
O-ring is in place
Use 2 screws M4x25 TX 20
from plastic bag
Tightening torque: 4 Nm
Be sure there are 2 O-rings
placed in the valve before
mounting on manifold
Remove red sealing paper
before mounting the valve
Tightening torque:
Fittings G : 20 Nm
Flare ¼” : 20 Nm
/