Emerson PSI-XR User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

AC Power
For Business-Critical Continuity
Liebert
®
PSI-XR
High Performance Rack-Mount UPS For Network Power Protection
Liebert PSI-XR is a compact, line-interactive UPS system
designed especially for IT applications such as network
closets and small data centers. It provides reliable
power protection for servers, critical nodes, network
workstations, large network peripherals, network
routers, bridges, hubs and other electronic equipment.
Matching battery cabinets are available to extend the
on-battery operating time.
Liebert PSI-XR allows you to get more from your UPS and your protected
equipment, with features normally found only on more expensive systems:
Greater than five minutes of internal battery backup time at full load
provides ample time for an orderly shutdown of connected equipment.
Optional matching external battery cabinets offer more backup time —
add up to 6 additional cabinets to extend battery runtime to
meet equipment needs.
Liebert PSI-XR operates at a higher output power factor — meaning less
power consumption. This results in your network running at lower
power levels and lower heat levels, and ultimately provides a longer
network service life.
Remote communications and shutdown options provide remote
monitoring and power management — serial and contact closure, USB, SNMP
Ideally suited for:
PCs
Network workstations
Servers
Network closets
Large network peripherals
VoIP
Reliable UPS Protection And Extended Battery Time
To Keep Your Network Up And Running
2
The flexible design of Liebert PSI-XR allows the unit
to be configured as a self-standing tower or to be
rack-mounted within a 2U space. It is available in
four capacities, and both 120V or 230V models.
The UPS features an innovative line-interactive design incorporating
buck/boost automatic voltage regulation technology. This protects against
utility voltage fluctuation by raising and lowering utility power to the level
needed by the connected equipment. It also allows the UPS to prolong
battery life by maximizing its time on utility power before going to battery.
Battery Runtime Chart
(Runtimes are in minutes, assuming fully charged batteries at 25°C)
Optional external battery cabinets
Provide extended runtime for applications that require longer backup time.
Liebert PSI-XR Standard Features:
Flexibility:
Six to seven battery-backed outlets
Allows the Liebert PSI-XR to be more flexible in accommodating
additional equipment to be connected to the UPS via the 15, 20
or 30 Amp receptacles.
Configurable input voltage window
Allows the UPS to be properly matched to the incoming utility
power and adjusts its input window and transfer points to
supply precisely regulated power to connected loads within the
selected range. Also enables the UPS to meet the required input
voltage when transferring to battery.
Rotatable Display Panel
90 degrees rotatable LED display
panel rotates 90° to make the readout
of the LED display easy to see in rack
or tower position.
Automatic Frequency Sensing
The UPS automatically adjusts to the input frequency,
50Hz or 60Hz.
Rack Rail Kit
These telescoping rails mount to the sides of the UPS to facilitate
installation into a rackmount enclosure.
RJ-45
Data Line
Connectors
Voltage
Configuration
DIP Switch
External
Battery
Connector
Power
Cord
Liebert
Intellislot
Port
RS232
(DB-9)
Port
EPO
USB
Port
Input
Circuit
Breakers
Output
Circuit
Breakers
Receptacles
Optional External Battery Cabinet
Add up to 6 cabinets for additional runtime
UPS with internal battery
Number of batteries Load % 1000VA 1500VA 2200VA 3000VA
Internal battery 50 15 13 14 13
100 6 5 5 5
Internal Battery +1
External Battery Cabinet
50 73 55 45 31
100 31 18 15 12
Internal Battery + 2
External Battery Cabinets
50 129 95 67 56
100 65 46 29 18
Internal Battery + 3
External Battery Cabinets
50 181 131 95 73
100 96 64 48 31
Internal Battery + 4
External Battery Cabinets
50 233 167 143 95
100 124 82 72 47
Internal Battery + 5
External Battery Cabinets
50 285 203 167 113
100 151 106 84 56
Internal Battery + 6
External Battery Cabinets
50 336 239 191 131
100 179 124 102 65
3
Liebert PSI-XRW Network
Solution Package With
Built-In Communications
Liebert PSI-XRW is the standard Liebert
PSI-XR made network–ready with a
factory-installed Liebert IntelliSlot Web
Card for SNMP communications. This
totally integrated, cost-efficient solution
allows remote monitoring, start-up or
restart for connected equipment.
Optional Liebert MicroPOD
Output Distribution And
Maintenance Bypass Module
When your computer system can’t be
without power, even for scheduled UPS
maintenance, the Liebert MicroPOD
Maintenance Bypass and Output
Distribution Unit ensures continuous
uptime. It allows you to manually transfer
connected equipment to utility power via
a maintenance bypass switch, permitting
scheduled service or UPS replacement
without the need to shut down connected
equipment. Features include:
2U height minimizes rack
space requirements
Installs with plug-and-play ease
Two-year, no-hassle
replacement warranty
Higher Availability:
Data line surge protection
Network surge protection for equipment
connected to the UPS via the RJ-45.
Advance early warning of
UPS system status
The Liebert PSI-XR offers multiple audible
and visual alarms to immediately alert
you to an input voltage fluctuation
(buck/boost), output overload, low
battery or replace battery condition.
Greater than five minutes of
battery backup time at full load
when utility fails
Provides ample time for an orderly
shutdown of connected equipment.
Optional matching external battery
cabinets offer more backup time.
Full sequenced battery testing
The Liebert PSI-XR provides a manual
self-diagnostic test feature. This provides a
comprehensive analysis of the condition of
the batteries within the UPS and will notify
you when the internal batteries need to be
replaced. The battery test feature can also
be programmed for automatic operation
using Liebert shutdown software.
Lightning and surge protection
The transient voltage surge suppression
(TVSS) circuitry inside the Liebert PSI-XR
provides protection for the connected
equipment from incoming spikes, surges,
and other power anomalies present on
the incoming utility power source.
Remote emergency power off
Allows the UPS to be remotely shut
down during an emergency.
User replaceable hot
swappable batteries
Increase product life and provide
prolonged UPS reliability. Batteries
are conveniently located behind
the front bezel of the unit.
Lowest Total Cost Of Ownership:
0.9 Output Power Factor
Liebert PSI operates at a higher output power factor --
meaning less power consumption. This results in your
network running at lower power levels and lower heat
levels, and ultimately provides a longer network service life.
Wider input voltage window
Prolongs battery life by allowing the UPS to maximize the
use of utility power before transferring to battery when
input voltage exceeds specified limits.
Reduced installation time and costs
UPS is shipped with batteries connected and charged.
Warranty Protection
Standard two-year warranty ensures UPS replacement if
problems occur during the warranty period. Optional
one-year and three-year extensions also available.
Multiple Choices For Communication,
Shutdown And Reporting:
Serial and Contact Closure Communication Option
Automated shutdown software allows you to monitor
communication between the UPS and a server. It also
ensures a graceful unattended shutdown in the event
of an extended power failure.
USB Communications
Windows (98 and later) built-in power management functions
provide monitoring of UPS status and manage the automatic
orderly shutdown of the computer if a power outage ever
exceeds the battery capacity of the UPS. Liebert USB shutdown
and monitoring software is provided.
SNMP Communication Option
Liebert IntelliSlot
®
Web Card provides SNMP and
web-based management to your Liebert PSI-XR. Provides
SNMP MIB to monitor and control your UPS from your network
management station or any PC running Microsoft Internet Explorer.
Network shutdown
Sends both SNMP traps and emails for event notification,
and
automatically emails a daily UPS history.
Auto-senses 10M/100M Ethernet
Compatible with shutdown software to ensure
graceful computer shutdown
Optional Liebert
IntelliSlot Web
Card provides SNMP
and web-based
management
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2008 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-23317 (R07/08) Printed in USA
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
Liebert PSI XR Specifications
Model Number PS1000RT3-120XR PS1500RT3-120XR PS2200RT3-120XR PS3000RT3-120XR
Network Solutions Package Number
PS1000RT3-120XRW PS1500RT3-120XRW PS2200RT3-120XRW PS3000RT3-120XRW
Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W 3000VA/2700W
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228)
Weight, lb (kg)
Unit 56 (25) 62 (28) 92 (42) 105 (48)
Shipping 64 (29) 70 (32) 101 (46) 115 (52)
Input AC Parameters
Surge Protection 570J
Voltage Range Without Battery
Operation
83 to 159 VAC (configurable)
Frequency Range 45~65Hz, (0.5Hz)
Input Power Cord, 10ft (3m)
attached
NEMA 5-15P plug NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug
Output Receptacles (6) NEMA 5-15R (6) NEMA 5-15R (4) NEMA 5-15R (2) NEMA 5-20R
T-Slot, accepts 15A Plug
(4) NEMA 5-15R (2) NEMA 5-20R
T-Slot, accepts 15A Plug
(1) NEMA L5-30R
Voltage (Normal Mode) 110/120/127 VAC (configurable)
Voltage (Battery Mode) 110/120/127 VAC; 5% before low-battery warning
Transfer Time 4-6 ms typical
Battery Waveform Sinewave
Battery Parameters
Typ e Valve-regulated, non-spillable, lead acid
Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load 5 minutes
Half Load > 10 minutes. 13-14 minutes typical.
Environmental
Operating Temperature, ˚F (˚C) 32 to 104 (0 to 40)
Storage Temperature, ˚F (˚C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Operating Altitude Up to 3000m (10,000 ft) at 35˚C (95˚F) without derating
Audible Noise <40 dBA, internal fan(s) Off; <45 dBA, internal fan(s) On
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Network Surge UL 497 B
Transportation ISTA Procedure 1A Certification
Rail Kit (included)
Rail Kit RAILKITPS3G-AEC
Battery cabinet specifications
Model Number PSRT3-24VBXR PSRT3-48VBXR
Used w/UPS Model PS1000RT3-120XR, PS1500RT3-120XR PS2200RT3-120XR, PS3000RT3-120XR
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
Shipping 22 x 26.6 x 9 (560 x 675 x 228)
Weight, lb (kg)
Unit 64 (29)
Shipping 73 (33)
Batteries
Typ e Valve-regulated, nonspillable, lead acid
Manufacturer CSB, YUASA or Equivalent
Environmental
Operating Temperature, ˚F (˚C) 32 to 104 (0 to 40)
Storage Temperature, ˚F (˚C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Maximum Operating Altitude 10,000 ft. (3000m) at 95˚F (35˚C) without derating
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Transportation ISTA Procedure 1A Certification
NEC limits the input current rating of the 2200VA model to 80% of the input plug’s rating. If 1920 or more is required, contact a certified electrician to change the input plug to
30A plug. Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug.