A-POOL TOP EVO PH-CL
ENGLISH
4/12
1. DESCRIPTION
The A-LEGIO SENSE panel has been designed to control the proliferation of legionella and other hydrodiffused
pathogens through an ON / OFF or proportional dosage of sodium hypochlorite or chlorine dioxide at the same
time as a dosage of an anticorrosive conditioner.
In general, it is composed of:
• 1 AE-START + CL instrument for the measurement of free chlorine;
• 1 pump HC151 + (PImA model) to dose an inhibitor (anticorrosive) product controlled by a pulse-
emitting counter;
• 1 pump HC151 + (PimA model) with automatic air purge to dose a disinfectant product (sodium
hypochlorite, etc.) controlled by the AE-START + CL instrument;
• 1 membrane amperometric probe for the determination of free chlorine;
• 1 modular HT probe holder, proximity sensor and flow regulator;
• 1 HT prefilter.
For the pump managed by the chlorine measuring instrument, the dosage mode set in the factory is the
proportional one: the dosage is proportional to two mA values (4mA and 20mA).
1.1 PANEL COMPOSITION
▪ Panel
▪ Membrane chlorine probe 0-5ppm
▪ n. 1 temperature probe (optional)
▪ HT water filter 9”3/4 complete of AC-HT cartridge 80 micron, 10x14 tube fittings
▪ Roll of PVC tube 10X14 (4m)
▪ Controller, pump and panel programming manuals
▪ n.2 PVDF injection valve
▪ n.2 PVDF foot filter
▪ Roll of PE tube for delivery (4 m)
▪ Roll of PVC tube for suction (4 m)
▪ Roll of PVC tube for air bleed (4 m)
1.2 TECHNICAL SPECIFICATIONS
Supply: 110-240VAC – 50/ 60Hz
Panel dimensions: L 650 x H 600 x D 250 mm
Max power: 60 W (with pumps in “C” curve)