Danfoss ECL Comfort 300 - C14 Operating instructions

Type
Operating instructions
How to use this guide
This guide is divided into two parts:
• Daily Use (Turn the guide over)
Yellow sections 01 - 09
• Installation and maintenance:
Grey sections 10 and onwards
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating and cooling systems.
The ECL Comfort ensures you of the following;
The room temperature will be adjusted to your personal
settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
Sketch an outline of your application
The ECL Comfort controller is designed for a wide range
of heating and cooling systems with different configurations
and capacities.
If your system differs from the diagrams shown in section
10, you may want to sketch an outline of the system about
to be installed. This makes it easier to use the Installer’s
Guide, which will guide you step-by-step from installation to
final adjustments before the end-user takes over.
Note! The controller is pre-programmed with factory
settings which are shown in the relevant sections of this
guide.
Before you start
VI.7C.P1.02
Click here to see the cover
Installation
Connections
Identifying your system type
10
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance to your system and make
your own combinations.
Installation
10.1 Unit heater system with constant room
temperature control
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to10
Jumper from 10 to 12
Jumper from 2 to common N-terminal
Control principle:
PI control of the flow temperature (S3) and P control of the
room temperature (S2). The flow temperature is held at a
constant level by the motorised valve M1. The P1 fans are
controlled by relay R1, and the circulation pump P2 by
relay R2.
System settings:
Line Description Recommended
setting
C Balance temperature 60°C
2 Flow/fan temperature limit min/max 30°C/90°C
85 Application selection 0
89 Relay output status R2 0
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
9 P1 Fan 4(2)A 230 V a.c.
10 230 V a.c. supply for fan relay
11 P2 Circulation pump 4(2)A 230 V a.c.
12 230 V a.c. supply for
circulation pump
Installation
Connections
Identifying your system type
10
Installation
10.2 Ventilation system with constant supply air
temperature control
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal
Control principle:
PI control of supply air temperature (S3). The temperature is
held at a constant level by the motorised valve M1 in the
primary circuit of the heat exchanger. Fan P1 is controlled
by relay R1, damper P2 by relay 2.
System settings:
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
9 P1 Fan 4(2) A 230 V a.c.
10 230 V a.c. supply for fan relay
11 P2 Damper 4(2) A 230 V a.c.
12 230 V a.c. supply for damper
relay
Line Description Recommended
setting
85 Application selection 0
87 R2 relay cut-in delay 180 sec.
Installation
Connections
Identifying your system type
10
Installation
10.3 Ventilation system with constant room
temperature control
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal
Control principle:
PI control of supply air temperature (S3) and P control of
the room temperature (S2). The temperature is held at a
constant level by the motorised valve M1 in the primary
circuit of the heat exchanger. Fan P1 is controlled by relay
R1, damper P2 by relay 2.
System settings:
Line Description Recommended
setting
C Balance temperature 23 °C
85 Application selection 0
87 R2 relay cut-in delay 180 sec.
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
9 P1 Fan 4(2)A 230 V a.c.
10 230 V a.c. supply for fan relay
11 P2 Damper 4(2)A 230 V a.c.
12 230 V a.c. supply for damper
relay
Installation
Connections
Identifying your system type
10
Installation
10.4 Ventilation system heating and mixed air
dampers
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper from 2 to common N-terminal
Control principle:
PI control of supply air temperature (S3) and P control of
the room temperature (S2) with a neutral zone between
heating and mixing. When heating, the temperature is held
at a constant level by the motorised valve M1 in the primary
circuit of the heat exchanger. When mixing, the temperature
is held at a constant level by the actuator M2 which controls
the dampers. Fan P1 is controlled by relay R1. (Note: It is
not possible to set any minimum damper position from the
controller).
System settings:
Line Description Recommended
setting
C Balance temperature 23 °C
1 Dead zone - Dz OFF
85 Application selection 2
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
6 M2 Damper motor - open 0.2 A 230 V a.c.
7 M2 Damper motor - close 0.2 A 230 V a.c.
8 230 V a.c. supply for M2
9 P1 Fan 4(2) A 230 V a.c.
10 230 V a.c. supply for fan relay
Installation
Connections
Identifying your system type
10
Installation
10.5 Ventilation system heating and cooling
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper 10 to 12
Jumper from 2 to common N-terminal
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
6 M2 Gear motor - open 0.2 A 230 V a.c.
7 M2 Gear motor - close 0.2 A 230 V a.c.
8 230 V a.c. supply for M2
9 P1 Fan 4(2)A 230 V a.c.
10 230 V a.c. supply for fan relay
11 P2 Damper 4(2)A 230 V a.c.
12 230 V a.c. supply for damper
relay
Control principle:
PI control of supply air temperature (S3) and P control of
the room temperature (S2) with a neutral zone between
heating and cooling. When heating, the temperature is held
at a constant level by the motorised valve M1 in the primary
circuit of the heat exchanger. When cooling, the
temperature is held at a constant level by the motorised
valve M2 in the primary circuit of the heat exchanger. Fan
P1 is controlled by relay R1, damper P2 by relay 2.
System settings:
Line Description Recommended
setting
1 Dead zone - Dz 2 K
2 Flow/fan temperature limit min/max 10 °C/50 °C
85 Application selection 2
Installation
Connections
Identifying your system type
10
Installation
10.6 Ventilation system heating and heat
recovery
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper from 2 to common N-terminal
Control principle:
PI control of supply air temperature (S3) and P control of
room temperature (S2) with a neutral zone between
heating and recovery. When heating, the temperature is
held at a constant level by the motorised valve M1 in the
primary circuit of the heat exchangers. At heat recovery, the
temperature is held at a constant level by the actuator M2
which controls the dampers. Fan P1 is controlled by
relay R1.
System settings:
Line Description Recommended
setting
1 Dead zone - Dz OFF
85 Application selection 2
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2 A 230 V a.c.
4 M1 Gear motor - close 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
6 M2 Gear motor - open damper 0.2 A 230 V a.c.
7 M2 Gear motor - close damper 0.2 A 230 V a.c.
8 230 V a.c. supply for M2
9 P1 Fan 4(2)A 230 V a.c.
10 230 V a.c. supply for fan relay
11 P2 Damper 4(2)A 230 V a.c.
12 230 V a.c. supply for damper
Installation
Connections
Identifying your system type
10
Installation
10.7 Refigeration system with constant brine
temperature
Establish these jumpers:
Jumper from 1 to 8
Jumper from 8 to 10
Jumper from 2 to common N-terminal
Control principle:
PI control of brine temperature (S3). The brine temperature
is held at a constant level by the motorised valve M1. The
circulation pump P1 is controlled by relay R1.
System settings:
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
6 M2 Gear motor - open 0.2 A 230 V a.c.
7 M2 Gear motor - close 0.2 A 230 V a.c.
8 230 V a.c. supply for M2
9 P1 Circulation pump 4(2)A 230 V a.c.
10 230 V a.c. supply for pump
relay
Line Description Recommended
setting
C Balance temperature 0 °C
2 Flow/fan temperature limit min/max -20/50 °C
85 Application selection 1
86 R1 relay cut-in delay 0 sec.
Installation
Connections
Identifying your system type
10
Installation
10.8 Refrigeration with constant room temperature
Establish these jumpers:
Jumper from 1 to 8
Jumper from 8 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
6 M2 Gear motor - open 0.2 A 230 V a.c.
7 M2 Gear motor - close 0.2 A 230 V a.c.
8 230 V a.c. supply for M2
9 P1 Fan 4(2)A 230 V a.c.
10 230 V a.c. supply for fan relay
11 P2 Circulation pump 4(2)A 230 V a.c.
12 230 V a.c. supply for pump
relay
Control principle:
PI control of the brine temperature (S3) and P control of the
room temperature (S2). The room temperature is held at a
constant level by the motorised valve M2. The circulation
pump is controlled by relay R2 and fan P1 by relay R1.
System settings:
Line Description Recommended
setting
C Balance temp. +17 °C
2 Flow/fan temperature limit min/max -20/50 °C
85 Application selection 1
Mounting the controller
11
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for wall mounting: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Installation
Installation
Connecting temperature sensors
Establish the jumper from 16 to common terminal
Connecting the 230 V a.c. units (general description)
12
Electrical connections -
230 V a.c.
Installation
Installation
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted into each screw
terminal.
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Note! Cable lengths above 100 m may cause noise sensibility
(EMC).
15 and 16 System device bus
17 and 16 Compensation
temp. sensor (S1) ESM-10/ESM-11
18 and 16 Room temperature
sensor (S2) ESM-10
19 and 16 Flow/air duct ESM-11/ESMB/
temp. sensor (S3) ESMC/ESMU
20 and 16 Return temperature ESMU/ESM-11/
sensor (S4) ESMC
21 and 16 External override (S5) ECA 9010
22 and 16 Frost sensor (S6) Kp 61/ESM-
Terminal Description Type (recommended)
1 L Voltage supply 230 V a.c.
2 N Voltage supply 230 V a.c.
3 M1 Gear motor - open max. 0.2 A 230 V a.c.
4 M1 Gear motor - close max. 0.2 A 230 V a.c.
5 230 V a.c. supply for M1
6 M2 Gear motor - open max. 0.2 A 230 V a.c.
7 M2 Gear motor - close max. 0.2 A 230 V a.c.
8 230 V a.c. supply for M2
9 P1 Pump/fan/damper max. 4(2)A 230 V a.c.
10 230 V a.c. supply for R1
11 P2 Pump/fan/damper max. 4(2)A 230 V a.c.
12 230 V a.c. supply for R2
13 P3 Optional max. 4(2)A 230 V a.c.
14 230 V a.c. supply for R3
Terminal Description Max. load
Connecting temperature sensorsConnecting the 24 V a.c. and 230 V a.c. units (general
description)
13
Electrical connections -
24 V a.c.
Installation
Installation
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted into each screw
terminal.
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Note! Cable lengths above 100 m may cause noise sensibility
(EMC).
1 L Voltage supply 24 V a.c.
2 N Voltage supply 24 V a.c.
3 M1 Gear motor - open max. 1.0 A 24 V a.c.
4 M1 Gear motor - close max. 1.0 A 24 V a.c.
5 24 V a.c. supply for M1
6 M2 Gear motor - open max. 1.0 A 24 V a.c.
7 M2 Gear motor - close max. 1.0 A 24 V a.c.
8 24 V a.c. supply for M2
9 K1 Relay for
pump/fan/damper max. 4(2)A 230 V a.c.
10 24 V a.c. supply for R1
11 K2 Relay pump/fan/damper max. 4(2)A 230 V a.c.
12 24 V a.c. supply for R2
13 K3 Optional relay max. 4(2)A 230 V a.c.
14 24 V a.c. supply for R3
Terminal Description Max. load
15 and 16 System device bus
17 and 16 Compensation
temp. sensor (S1) ESM-10/ESM-11
18 and 16 Room temperature
sensor (S2) ESM-10
19 and 16 Flow/air duct ESM-11/ESMB/
temp. sensor (S3) ESMC/ESMU
20 and 16 Return temperature ESMU/ESM-11/
sensor (S4) ESMC
21 and 16 External override (S5) ECA 9010
22 and 16 Frost sensor (S6) Kp 61/ESM-
Terminal Description Type (recommended)
14
Placing the temperature
sensors
It is important that the sensors are mounted in the
correct position in your heating system.
Special attention should be paid to the following sensors:
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed max. 15 cm
from the mixing point. It should always be placed on a
pipe in which the water flow never stops.
Flow/air duct temperature sensor
Place the sensor close to the exchanger.
Do not move the sensor after it has been fastened in order
to avoid damage to the sensor element.
Room temperature sensor
(ESM-10, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls or close
to radiators, windows or doors.
Outdoor temperature sensor
(ESM-10 type)
The outdoor sensor should be mounted on the north side of
the building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors or
windows.
Installation
Installation
Understanding the ECL Card
The ECL Card contains factory settings for a standard
application. If the actual application differs from the
standard system, the ECL controller must be adjusted
accordingly. After the adjustment, the new settings
should be stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the
ECL Card - the installers side - must be facing you.
As a main rule, the ECL Card should always remain in
the controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings are locked after approx. 10
min.
The card must not be exposed to direct heat or
sunshine
If several controllers are installed in the system you can
write a title on the ECL Card with a permanent ink pen.
Line
Circuit
Time
Outdoor
temperature
(S1)
Desired room/
duct temperature
CYp
0
O9C
C41
01 101
8
0 3 6 9 12 15 18 21 24
1
023
5
C
3
15
Inserting the ECL Card
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the card data.
The controller immediately starts to copy the factory
settings and heating system type from the card. After
copying, the display will show the heating system type the
controller is set to control. After approx. 10 sec. the display
will change to display C.
The controller is now ready to be set to control your
heating system.
Installation
Installation
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12 hours,
the time and the date have to be set again.
All other settings are stored as programmed.
The grey side of the ECL Card.
Go to line A.
09
01
56019
5
A
3
Actual time
Month, day
Year
Use the shift button to switch between hours,
minutes, year, month and day
Set the correct time and date
Use the yellow side of the card to enter the day plan
settings.
See User’s Guide, section 4.
16
Adjusting the ECL Card
settings
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For details
about copying, see section 34. Insert the ECL Card with the
yellow side facing you.
CYp
0
O9C
When the copying is finished display C will appear
8
0 3 6 9 12 15 18 21 24
1
023
5
C
3
You can make other changes in the day plan, set time and
date or change settings (see User’s Guide).
Line
indicator
Settings to
be adjusted
Value in range
indicator
Circuit
1
1
ON
2
ON
09
2
04
2
3
ON
Use the minus/plus buttons to adjust the
settings.
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the possibilities.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually in both circuits, ie.
circuit II.
Go to line 9
Accept to copy as indicated. No other keys are
active.
Basic set-up
Basic set-up
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the
grey side of the ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
19
Manual control - Line B
Basic set-up
Check the turning direction of the motorized valve either by
looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
Note! In manual control the pump motion programme is
switched off.
The grey side of the ECL Card.
Go to line B.
Select the unit you want to control.
The selected unit symbol will flash.
Valves close or open while
the relevant button is pressed.
Pumps/fans/dampers are switched off
or on when the relevant button is pressed.
1
1
ON
Monitoring temperatures and
system units - Line B
18
Go to line B.
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump or fan
is operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as
- -.
If the sensor is short-circuited, the display will indicate it as
- - - .
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
The grey side of the ECL Card.
Controlled units
State indicator
Frost temperature
(S6)
Compensation
temperature (S1)
Push the shift button to see the calculated flow
and return temperature set points.
Controlled
units
Controller mode
Basic set-up
Shift to manual mode
Relationship between temperature and ohmic value
-10°C 961 ohm
0°C 1000 ohm
10°C 1039 ohm
20°C 1078 ohm
30°C 1117 ohm
40°C 1156 ohm
50°C 1195 ohm
60°C 1234 ohm
70°C 1273 ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
8
B
3
0
3
ON
1
1
ON
2
ON
2
Alarm
8
B
3
0
3
ON
1
1
ON
2
ON
2
Alarm indications:
0 : No alarm
1 : Alarm sensor S1 - frost, fire
2 : Alarm sensor S2 - frost
3 : Alarm sensor S3 - frost
4 : Alarm sensor S4 - frost
5 : Not used
6 : Alarm sensor S6 - frost
1
20
The grey side of the ECL Card.
The balance temperature is the basis of the air/
water flow temperature reference, and when the
room sensor is connected, the flow/air
temperature reference varies around the
balance temperature set-point.
The flow/air temperature reference equals the
sum of the balance temperature + the influence
of different inputs (room, return, compensation).
Basic set-up
Basic set-up
Setting range Factory setting
-20 to 110°C 20 °C
Balance temperature
Set the temperature that fits your system.
Dead zone - Dz
21
The grey side of the ECL Card.
Go to line 1.
Balance temperature
Go to line C
0
C
2
3
ON
1
1
ON
2
ON
2
Dead zone - Dz
Setting range Factory setting
OFF, 0.5 - 25.0 OFF
OFF: No dead zone between cooling and
heating.
0.5 - 25.0: This setting is only used in
connection with 2-stage heating or
heating/cooling applications. The
room temperature influence is
cancelled in the dead zone - Dz.
Inheating/cooling applications this
setting protects against unwanted
changes to/from heating and cooling.
1
2
ON
0
1
2
1
ON
3
ON
2
1
2
ON
3
1
ON
3
ON
2
50
Flow/fan temperature limits -
Line 2
22
The grey side of the ECL Card.
Go to line 2.
1
1
ON
2
ON
05
2
02
3
ON
2
Max. flow
temperature
Min. flow
tempera-
ture
Temperature
range for the
flow temperature
Adjust the min. limit of your heating system. The
left end of the range indicator flashes.
Select the max. limit. The right end of the range
indicator flashes.
Adjust the max. limit of your heating system.
Basic set-up
Basic set-up
Setting range Factory setting
-20 ... 110° C min. 20 °C max. 50 °C
2 Flow temperature min., max. limits
Room temperature influence -
Kp
23
The grey side of the ECL Card.
Go to line 3.
Room
temperature
influence
Set the influence that fits your system.
This setting is only relevant if you have installed a room
sensor. The room sensor registers the difference between
desired and actual room temperature. The flow/air
temperature reference is displaced (the influence is added
to the balance temperature) to eliminate the difference.
Room temperature influence
Setting range Factory setting
0.0 - 25.0 5.0
Setting the PI-regulation -
Line 4-7
(circuit I - Heating)
(circuit II - Cooling)
26
The grey side of the ECL Card.
Go to line 4.
1
2
ON
4
80
1
ON
3
ON
2
Setting to be adjusted
The bar shows the
setting
Line
indicator
Set the proportional band.
A higher value will result in a stable, but slow
regulation of the flow temperature.
Go to line 5.
Set a high integration constant to obtain a slow
but stable reaction to deviations.
A small integration constant will make the
controller react fast but with less stability.
Go to line 6.
Set the running time of the motorised valve
according to the example on the opposite page.
This is the time it takes the valve to move from
closed to fully open position.
Go to line 7.
Set the neutral zone to a high value if you can
accept a high variation in flow temperature.
When the actual flow temperature is within the
neutral zone, the controller does not activate the
motorised valve.
Circuit Setting range Factory setting
I/II 1 ... 250 K 80 K/80 K
4 Proportional band
Circuit Setting range Factory setting
I/II 5 ... 999 sec. 30 sec./30 sec.
5 Integration constant
6 Running time of the motorized valve
Circuit Setting range Factory setting
I/II 5 ... 250 sec. 35 sec./35 sec.
Basic set-up
Basic set-up
7 Neutral zone
Circuit Setting range Factory setting
I/II 0 ... 9 K 3 K/3 K
If you want to tune the PI-regulation precisely, you can
use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (Line 4) until
the system starts hunting with a constant amplitude (it might
be necessary to force the system by setting an extreme
value).
Find the critical time period on the temperature recording or
use a stop watch.
This time period will be characteristic for the system, and you
can evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value in the
critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10 %.
Note! Make sure there is a consumption when you set the
parameters.
Time
Temp
Critical time period
29
Check list
Control & overviews
29
Check list
Control & overviews
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12 Electrical connections
Check that valves, pumps, fan and dampers are
connected to the correct terminals.
See section 12 Electrical connections
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you.
See section 15 Inserting the ECL Card
Select manual operation in the controller mode.
See section 3 in the User’s Guide.
Check that valves open and close, and that
pumps, fans and dampers start and stop when
operated manually.
See section 19 Manual control.
Check that the temperatures shown in display A
and B match the actual sensors in circuit I as
well as in circuit II.
See section 1 in the User’s Guide.
Adapting the ECL Comfort controller to the heating
system
To ensure that you have the correct settings, see section 10
Identifying your heating system for examples of different
heating systems
Turn the ECL Card so that the grey side faces
you.
Set the time and the date (Line A)
See section 17.
Check all settings on the grey side of the
ECL Card
See sections 20 to 26.
Check the settings mentioned in section 10.1
and 10.8 has been set correctly.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39

Danfoss ECL Comfort 300 - C14 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI