  • Hello! I am an AI chatbot trained to assist you with the Danfoss DML / DCL Filter Drier Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Solder versions
Symbol Connection MWP
1
/4 in
5
/16 in
3
/8 in
610 psig/
1
/2 in
42 bar
5
/8 in
3
/4 in
7
/8 in
500 psig/
1
1
/8 in
35 bar
INSTRUCTIONS
DML / DCL
Filter drier
DCL: R 12, R 22, R 502 et al.
DML: R 134a, R 404A, R 407 C, R 410 A, R 507 et al.
Note!
Max. working pressure (PB/MWP) shall not be less than the pressure
outlined in sect. 8.2 of ANSI / ASHRAE 15 for the refrigerant used in the
system.
After charging, the system shall be marked with the refrigerant and the oil
used.
023R9514
023R9514
© Danfoss A/S (AC-RCMP,jp) RI.6A.G4.22 05-1999
Flare / Face Seal versions (ORS)
Symbol Connection MWP
610 psig/
All sizes
42 bar
/