  • Hello! I am an AI chatbot trained to assist you with the Danfoss GBC Ball Valve - for CO2 90 bar Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
DKRCC.PI.FB0.D5.02 / 520H8132 © Danfoss A/S (AC-MCI / sw), 2014-04
Installation guide
Shut-o ball valve
Type GBC 6s H to GBC 42s H
009R9505
009R9505
Temperature range:
GBC 6s H - GBC 42s H: -40 °C - 100 °C / 40 °F - 212 °F
Max. working pressure:
GBC 6s H - 28s H: PS/MWP = 90 bar / 1305 psig
GBC 35s H - 42s H: PS/MWP = 75 bar / 1085 psig
Remove cap and access cap (if present)
OPEN position
CLOSED position
Bi-ow
Danfoss
9G162.13
Danfoss
9G144.12
Danfoss
9G145.12
Refrigerant:
R744 (CO
2
)
Opening valve
1
2
Valve size
Max. Torque
Nm ft-lbs
6s - 16s 10 7.4
18s - 22s 13 9.6
28s 26 19.2
35s 27 19.9
42s 48 35.4
Warning: Only authorized persons are allowed to operate this valve, as closing can
cause build-up of excessive pressure in the system.
2 DKRCC.PI.FB0.D5.02 / 520H8132 © Danfoss A/S (AC-MCI / sw), 2014-04
Tighten cap
Tighten the cap with approx. torque
Install Schraeder valve
(if present) and cap
4
5
Install Schraeder valve
with approx. torque
0.3 Nm / 0.2 ft-lbs
Brazing (Copper and
Copper alloy)
Danfoss
9G156.14
Min. 5% Ag
3
Danfoss
9G207
Danfoss
9G207
Danfoss
9G208
Max. 100 °C
(212 °F)
Welding
Welding with
stainless steel
100 °C
(212 °F)
Danfoss
9G207
Danfoss
9G209.10
Fully open
Fully closed
Valve size
Max. Torque
Nm ft-lbs
6s - 22s 15 11.0
28s - 35s 20 14.8
42s 32 23.6
/