1. Remove the Cover (B) from the Stand Alone Protector (SAP) unit by removing the two Tory Head screws
(D) and separating the Cover (B) from the Mounting Frame (A).
2. Remove the IG1C coax module from the Mounting Frame by removing the
outer hex nut from each of the F-thread connectors. Do not loosen the
inner hex nut. (see Figure 3)
3. Reverse the Mounting Frame and Cover so that it appears similar to the
illustration in Figure 2.
4. Insert the IG2C coax module through the holes in the Cover (B) and
secure it using the two hex nuts that were removed in step 2. (Figures 2)
5. If a second IG2C module is being used, insert it through the holes in the
opposite end of the Cover and secure it using the outer set of hex nuts.
Individual IG1C Protection Modules are shipped with a mounting plate installed over the F-thread con-
nector. The mounting plate is used in conjunction with model IG1C3R, raintight enclosure. Remove and
discard the mounting plate for this installation.
6. Attach the Cover (B) that was removed in step 1 to the Mounting Frame (A). The Cover should be
secured to the Mounting Frame in the same manner that it was before step 1 above. The Cover now
becomes the Back Plate of the Stand Alone Protection unit. (see Figure 2)
7. Select a location to install the SAP that is convenient to coaxial and /or telephone cables. Allow enough
room to route the cables in and out of the unit.
REMEMBER:
The Ground Conductor must be bonded (COMMON) with the Service Entrance Ground.
8. If the SAP is being installed in an existing wall or surface for coaxial protection, continue with step A1
below. If the SAP is being used in a New building or Prewire installation for coaxial protection, proceed
to SECTION B.
A1. Position the Cutting Template on the wall and mark the recommended cut-out and mounting hole
positions.
A2. Cut and remove the recommended area. Drill or punch the holes required to mount the SAP to the wall.
If the 3/4” anchors are to be used, insert them into the proper holes in the wall at this time.
A3. Route the coax cables to the SAP. If the cables have connectors installed, secure them to the IG1C
unit(s). Note that at this point, the SAP has not been secured to the wall.
A4. If the cables do not have connectors attached, leave enough cable for future installation of connectors.
NOTE:
The IG1C coax protector is bidirectional. Coax cable may enter and exit from either
connector. The F-thread connectors should be hand tight only. Do not overtighten.
A5 Connect the Ground Wire making certain that it is properly connected to the building ground. Use at least
12 gauge wire if additional length is required.
A6. TEST each coax line for proper operation.
A7. When all wiring and connections are complete, place the Flush Mount Cover Plate on the Mounting
Frame and secure it with two (2) 5/8” self threading screws (J).
A8. Align the holes in Flush Mount Cover Plate with the holes or anchors in the wall and secure it to the wall
using the 3/4” x 6 Pan Head Screws.
SECTION
A:
Existing or Retro-fit Inst
allations - Coaxial Lines
COAXIAL LINE PROTECTION
Note: These modules rely on a good ground connection to function properly. Ground
availability should be a consideration when selecting an installation location.
Do not install Protection Devices during Electrical Storms.
Figure 3
OUTER HEX NUT
INNER HEX NUT