Microprocessor Controller for Make-Up Air Products 3
®
Sequence of Operation
Set Point Control (Occupied)
The supply air temperature set point can be configured
as constant (local), or can be reset by either outside
air temperature, or room temperature. If equipped
with BMS communications, the user can also directly
command the supply temperature set point, or room
temperature set point (if equipped with an optional
room temp sensor).
• Outdoor Air Temperature Reset Function: The
controller will default to supply temperature reset
based on outdoor air temperature. The controller will
monitor the OA temperature and reset the supply
temperature set point based upon the outdoor air
reset function.
• Room Temperature Reset (optional): With a
room temperature sensor, the controller will adjust
the supply air temperature set point between the
minimum (55°F adj.) and maximum (90°F adj.), to
satisfy the desired room temperature.
Set Point Control (Unoccupied)
When equipped with an unoccupied recirculation
damper and optional room temperature sensor, the
unit will cycle on to maintain the unoccupied room set
points.
• Unoccupied Heating: If equipped with heating,
the unit is enabled when the room temperature is
less than the unoccupied heating set point minus
differential (65°F-5°F). The supply air temperature
set point will be set to the supply maximum reset
limit (90°F). The unit cycles off when the room
temperature reaches the unoccupied heating set
point.
• Unoccupied Cooling: If equipped with cooling,
the unit is enabled when the room temperature is
greater than the unoccupied cooling set point plus
differential (80°F+5°F). The supply air temperature
set point will be set to the supply minimum reset
limit (55°F). The unit cycles off when the room
temperature reaches the unoccupied cooling set
point.
Heating
The heating is controlled to maintain the supply
temperature set point. The heating will be locked out
when the outside air temperature is above the heating
lockout (65ºF adj).
• Indirect Gas Furnace: Microprocessor controller
will modulate the indirect gas furnace to maintain the
supply temperature set point.
• Hot Water Coil: Microprocessor controller will
modulate a hot water valve (provided by others) to
maintain the supply temperature set point (0-10 Vdc).
Coil freeze protection must be provided by others
in the field!
• Steam Coil: Microprocessor controller will modulate
a steam valve (provided by others) to maintain the
supply temperature set point (0-10 Vdc). Coil freeze
protection must be provided by others in the field!
• Electric Heater: Microprocessor controller will
modulate an electric heater to maintain the supply
temperature set point (0-10 Vdc).
• Morning Warm-Up: The unit uses an algorithm
involving space temperature and heating/cooling rate
of the previous day to determine the time required
to efficiently temper the space occupied set point
prior to occupancy (optional room temp sensor is
required).
Cooling
The cooling is controlled to maintain the supply
temperature set point. The mechanical cooling will be
locked out when the outside air temperature is below
the cooling lockout (80°F).
• Chilled Water: Microprocessor controller will
modulate a chilled water valve (provided by others) to
maintain supply air set point. Coil Freeze protection
must be provided by others in the field!
• Packaged DX Cooling (Standard Scroll):
Microprocessor controller will control stages of
cooling to maintain the supply air set point.
Economizer
If the application requires cooling, and the outdoor
air conditions are suitable for free cooling, the
controller may enter the economizer state. If the unit is
economizing and the discharge temperature set point is
not being met, the controller may bring on mechanical
cooling. If equipped with a modulating outdoor air and
recirculated air damper, the dampers will modulate
between the minimum OA and maximum positions to
maintain the supply temperature set point.
• Temperature: The economizer will be locked out
when:
- The outside air is less than the economizer low
lockout (40°F).
- The outside air is greater than the economizer
high lockout (65°F).
- There is a call for heating.
Supply Fan VFD Sequence
If the factory has installed a VFD, the unit can be either
constant volume, 2-speed, or variable air volume (VAV).
The maximum speed can be adjusted for any airflow
arrangement. For 2-speed operation both the high
and low fan speeds can be set on the controller, and
a field-wired switch to a digital input on the controller
will switch the fan between the 2 speeds. If the unit has
been configured for VAV operation, the minimum speed
can also be adjusted during the test and balance.
During VAV operation, the microprocessor controller
will modulate the supply fan speed per one of the