AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 © Danfoss 11/1998 13
|
Railheat Pulsin
Settin
s for railheat function
(Day/Night)
6.08
RailOnDay % During day operation: Setting of rail heat ON period in percent
0 - 100 of the "RailCycl m" time.
6:08:01
|
RailOnN
t % Durin
ni
ht operation: Settin
of rail heat ON period in percent
0 - 100 of the "RailCycl m" time
6:08:02
|
RailCycl m Period time for total ON / OFF time
6 - 60
6:08:03
|
Tc Signal Ctrl. Setting of Tc Signal control
Settings
6.09
Tc Ctrl. Tc regulation ON/OFF
OFF ON
6:09:01
|
Tc On % Openin
de
ree of the expansion valve, when Tc-outlet shall
0 100 be cut-out.
6:09:02 (higher condensing pressure is required)
|
TcOnDel.m Time delay before Tc outlet is cut-out
0 60
6:09:03
|
Tc Off % Opening degree of the expansion valve, when Tc-oulet is
0 100 cut-in.
6:09:04 (lower condensin
pressure allowed)
|
TcOffDel.m Time delay before Tc outlet is cut-in.
0 60
6:09:05
|
Output Ctrl. at Definition of controller outputs at forced control signal
Forced Closing (when the "ON" inlet is cut-out (terminal 32 - 33))
6:10
Output Ctrl. Output functions when there is forced control
1 - 3 Help 1: Fan outlet is ON
6:10:01 2: Fan outlet is OFF
3: All outlets are OFF and alarm thermostat function is stopped.
|
ON-InpMode Definition of AKC-ON input (terminals 32-33)
0 - 1 0: Connection not used, as the regulation is controlled by the
6:10:02 gateway’s override function
1: Connection must
be made (when te voltage is interrupted
the valve closes)
|
Safety Function Settings for fan stop function
Fan Stop by S5
6:11
FanStopS5 Fan stop function defines ON or OFF
OFF/ON Help
6:11:01
|
FanStop °C Temperature limit for fan stop (the fans are stopped when the
-50 - 50 S5A temperature is higher than this value. The fans will start again
6:11:02 when S5A is lower than "FanStop °C" - 2K)
|
Extended Ther. Extended settin
s for thermostat function
Ctrl. Settings
6:12
S4 Da
%S4 wei
htin
b
da
0 - 100 S3 is automatically weighted. Must only be set if "Ther.Sx" = 3
6:12:01
|
S4 Night % S4 is weighting at night
0 - 100 S3 is automaticall
wei
hted
6:12:02
|
S4MinLim °C Only AKC 114D Setting of low S4 temperature alarm limit
-50 - 50 The function is only active, if weighting between S3 and S4
6:12:03 Help is used for the thermostat function