CENTAC TROUBLESHOOTING GUIDE
1
CST-TP0007
1994 Ingersoll-Rand Company
Date of issue: January, 1999 Supersedes: 16-dec-94
Surge
Cause Solution
1. Dirty inlet air filter. Replace filter.
2. Too small inlet pipe (remote-mounted
air filter).
Replace pipe.
3. High interstage air temperatures. Investigate. Check to see what is
necessary to lower air temperatures.
Check water temperature, water flow,
water pressure, etc.
4. Increase in water temperature. Investigate. Check to see if it is possible
to lower water temperature.
5. Increase in inlet air temperature. Lower setpoint.
6. Setpoint higher than design discharge
pressure of compressor.
Lower setpoint.
7. Defective system pressure controller. Adjust or replace.
8. Too low CLL or LLR (throttle surge). Increase CLL or LLR setting.
9. Too low P1, PR3, or mechanical stop
adjustment (unloaded surge).
Increase P1, PR3 or adjust mechanical
stop.
10. Improper calibration of valve I/P,
positioner, or actuator.
Calibrate as necessary.
11. Defective bypass valve. Repair or replace.
12. Restriction in customer's system. Investigate. Take necessary steps to
correct restriction. Check for closed block
valve or excessive dryer pressure drop.
13. Restricted air flow through air coolers. Clean air coolers.
14. Dirt build-up on impeller vanes. Clean impeller.
15. Blockage of diffuser air passage. Clean diffuser.
16. Improper wheel clearance. Reset clearance.
17. Worn or damaged impeller. Replace.
18. Butterfly valve pin broken. Replace pin.
19. Discharge check valve hanging up. Repair or replace.