Omron Handheld EtherNet Configuration Guide

Type
Configuration Guide
Omron Automation Americas
2895 Greenspoint Parkway, Suite 200, Hoffman Estates, IL 60169
2801 Rochelle Rd., Suite 100, DFW Airport, TX 75261
100 Consilium Place, Suite 802, Toronto, Ontario, M1H 3E3
Configuration Guide for adding EtherNet/IP
Adapter to Handheld Barcode Readers
Version 1.1 August-2023
Table of Contents
Configuration Diagram ....................................................................................................................... 2
Selecting a Handheld Reader ............................................................................................................. 3
Choosing a Network Adapter ............................................................................................................. 3
Required Connection Cable ............................................................................................................... 3
Power Supply Options ........................................................................................................................ 3
Example Bill of Materials .................................................................................................................... 3
Required Firmware for EtherNet/IP ................................................................................................... 4
Omron Automation Americas
2
Configuration Diagram
Omron Automation Americas
3
Select the handheld barcode reader
Corded options from V410-H, V450 / HS360X Corded
Cordless option to connect to V450 / HS360X Base
Choose the appropriate Network Adapter
Network Adapters are available for EtherNet/IP and PROFINET
EtherNet/IP Adapter: EA3600-R1CP-11
PROFINET Adapter: EA3600-S1CP-11
Required Connection Cable
Adapter to Handheld Cable: CBA-RF2-CO9ZAR
Power Supply Options
Power the adapter from 24VDC through the supplied terminals
or
Powered by optional AC adapter
Example BOM for handheld to EtherNet/IP Adapter
Omron Automation Americas
4
Required firmware for EtherNet/IP
Please confirm that you are using “Product Software Revision” PAADRC01-001-R02 for the
EtherNet/IP adapter part number EA3600-R1CP-11
Using the Ethernet Configuration utility, the Status Log should look similar to the image below. IP
addresses may be set according to your individual application.
If the software is not the correct version:
a. Launch the industrial Ethernet Utility.exe
b. Connect to EA3600
c. Transfer the file CAADRC01-001-R02D0.HEX to the unit
A successful update will look similar to the image below