MTA NGSi 15 Technical Manual

Category
Heat pumps
Type
Technical Manual
Chillers and inverter air/water heat pumps
with axial fans
TECHNICAL MANUAL
NGSi 05÷15
38178800879
Original instructions in Italian language
TECHNICAL MANUAL
Chillers and inverter air/water heat pumps with axial fans
38178800879
Ed.A
Any waste electrical and electronic equipment must not be disposed of with ordinary household waste; it must be dealt with in accordance with the
legal requirements for WEEE under European Directive 2002/96/EC and the subsequent amendments 2003/108/EC, requesting instructions from
the relevant Local Authority, or from the dealer if the product is replaced with another of the same type.
TECHNICAL MANUAL
- Contents
NGSi 05÷15
1
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
CONTENTS
CONTENTS........................................................................................................................................................... 1
Chapter 1
PURPOSE AND CONTENTS OF THIS MANUAL ..................................................................................................... 4
1.1 Conserving the manual.................................................................................................................... 4
1.2 Symbols used in the manual............................................................................................................ 4
Chapter 2
STANDARDS OF REFERENCE............................................................................................................................... 4
Chapter 3
PERMITTED USE.................................................................................................................................................. 4
Chapter 4
GENERAL SAFETY REGULATIONS ...................................................................................................................... 5
4.1 Occupational health and safety........................................................................................................ 5
4.2 Personal protective equipment ........................................................................................................ 5
4.3 Safety signs...................................................................................................................................... 6
4.4 Refrigerants safety datasheet........................................................................................................... 6
Chapter 5
TECHNICAL FEATURES....................................................................................................................................... 7
5.1 Frame............................................................................................................................................... 7
5.2 Refrigerant circuit............................................................................................................................ 7
5.3 Compressors .................................................................................................................................... 7
5.4 Air side exchanger........................................................................................................................... 7
5.5 Fans ................................................................................................................................................. 7
5.6 User heat exchangers....................................................................................................................... 7
5.7 Control panel ................................................................................................................................... 8
5.8 Control system................................................................................................................................. 8
5.9 Monitoring and protection devices.................................................................................................. 8
5.10 Water circuit .................................................................................................................................... 8
5.11 Fan speed regulation........................................................................................................................ 8
Chapter 6
VERSIONS AVAILABLE ........................................................................................................................................ 8
6.1 Optional accessories ........................................................................................................................ 8
Chapter 7
INSTALLATION .................................................................................................................................................... 8
7.1 General ............................................................................................................................................ 8
7.2 Lifting and handling ........................................................................................................................ 9
7.3 Positioning and spaces required for technical purposes ................................................................ 9
7.4 Water connections ........................................................................................................................... 9
7.4.1 Connecting to the condensate drain ............................................................... 10
7.4.2 Service tap ...................................................................................................... 10
7.4.3 System drainage ............................................................................................. 10
7.4.4 Water system diagram .................................................................................... 10
7.5 5-9 kW chiller diagram.................................................................................................................. 11
7.6 12-15 kW chiller diagram ............................................................................................................ 11
7.7 Electrical connections.................................................................................................................... 12
7.7.1 Connection terminal board ............................................................................ 12
Chapter 8
START-UP .......................................................................................................................................................... 14
Chapter 9
USER - CONTROL INTERFACE ......................................................................................................................... 14
9.1 Menu structure............................................................................................................................... 15
9.1.1 Analogue inputs menu .................................................................................... 15
9.2 Parameters category ...................................................................................................................... 16
9.3 Setpoints settable by the user ........................................................................................................ 16
9.4 Display........................................................................................................................................... 16
9.5 LEDs.............................................................................................................................................. 16
9.6 Modifying the dynamic setpoint.................................................................................................... 17
9.7 Modifying the setpoint from 0-10V input ..................................................................................... 17
TECHNICAL MANUAL
- Contents
NGSi 05÷15
2
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
9.8 Hydraulic pump operation .............................................................................................................18
9.8.1 Operation on call from temperature controller (Default) ..............................18
9.8.2 Operation on call from temperature controller with periodic activation .......19
9.8.3 Continuous operation .....................................................................................19
9.8.4 Pump proportional adjustment .......................................................................19
9.9 Heaters for antifreeze protection (if AK accessory is installed) ....................................................20
9.10 Remote on-off and remote summer-winter switching ...................................................................20
9.11 Remote water temperature probe...................................................................................................20
9.12 Domestic hot water production enable ..........................................................................................20
9.12.1 Probe storage in heating mode .......................................................................21
9.12.2 Domestic hot water production call from digital input ..................................21
9.13 Domestic hot water accumulation in hot mode .............................................................................22
9.14 System backup heaters...................................................................................................................23
9.15 Systems backup heater in defrost mode.........................................................................................23
9.16 Domestic hot water backup heater.................................................................................................23
9.17 Backup heaters selection mode......................................................................................................23
9.18 Activation of backup and hot water tank heaters in joint operation mode/compressor replacement mode23
9.19 System season indication ...............................................................................................................30
9.20 Fan and dissipation control ............................................................................................................30
9.20.1 Ventilation control in chiller mode .................................................................30
9.20.2 Ventilation control in heating mode ...............................................................30
9.21 Defrost cycle ..................................................................................................................................31
9.22 Compressor crankcase heater.........................................................................................................31
9.23 Functions which can be enabled with Hi-T accessory...................................................................31
9.23.1 Screed function ...............................................................................................31
9.23.2 Disinfection (Legionella prevention) ..............................................................31
9.24 Handbook for installation configurations ......................................................................................31
9.25 Tables of settings which can be made by the user and installer ....................................................31
9.26 Alarms............................................................................................................................................38
9.26.1 Flow switch E06 ..............................................................................................38
9.26.2 High temperature E18 ....................................................................................38
9.26.3 Antifreeze E05 .................................................................................................38
9.26.4 Probe alarms ...................................................................................................38
9.26.5 Inverter timeout E80 .......................................................................................38
9.26.6 Remote ON/OFF E00 ......................................................................................38
9.26.7 High pressure E01 ..........................................................................................38
9.26.8 High pressure switch HP (in series with compressor delivery line probe) E64 38
9.26.9 Low pressure E02 ...........................................................................................38
9.27 No voltage......................................................................................................................................38
9.28 User cutout alarm table ..................................................................................................................38
Chapter 10
LENGTH SHUT-DOWNS......................................................................................................................................39
Chapter 11
ROUTINE CHECKS AND MAINTENANCE............................................................................................................39
11.1 Environmental protection ..............................................................................................................40
Chapter 12
TAKING THE UNIT OUT OF SERVICE ................................................................................................................40
Chapter 13
TECHNICAL DATA .............................................................................................................................................40
Chapter 14
ELECTRICAL DATA OF UNIT AND CONTROL DEVICES.....................................................................................42
Chapter 15
HEAT PUMP WORKING HEADS..........................................................................................................................42
15.1 Mod. NGSi 05................................................................................................................................42
15.2 Mod. NGSi 07................................................................................................................................43
15.3 Mod. NGSi 10................................................................................................................................43
15.4 Mod. NGSi 15................................................................................................................................43
Chapter 16
OPERATING LIMITS...........................................................................................................................................44
16.1 Evaporator water flow rate ............................................................................................................44
16.2 Chilled water production (summer operation)...............................................................................44
TECHNICAL MANUAL
- Contents
NGSi 05÷15
3
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
16.3 Hot water production (winter operation)....................................................................................... 44
16.4 Room air temperature and summary table .................................................................................... 44
Chapter 17
CORRECTION FACTORS FOR THE USE OF GLYCOL......................................................................................... 45
Chapter 18
DIMENSIONS...................................................................................................................................................... 45
18.1 Mod. NGSi 05 ............................................................................................................................... 45
18.2 Mod. NGSi 07 ............................................................................................................................... 46
18.3 Mod. NGSi 10-15 .......................................................................................................................... 46
Chapter 19
ELECTRIC WIRING DIAGRAMS ......................................................................................................................... 47
19.1 Mod. NGSi 05-07 .......................................................................................................................... 47
19.2 Mod. NGSi 10 ............................................................................................................................... 48
19.3 Mod. NGSi 15 ............................................................................................................................... 49
Chapter 20
CRH REMOTE KEYPAD (OPTIONAL ACCESSORY)........................................................................................... 50
20.1 Connecting the CRH keypad to the minichiller ............................................................................ 50
Chapter 21
DOUBLE SETPOINT KIT (OPTIONAL ACCESSORY) ........................................................................................... 50
21.1 Scope and field of application ....................................................................................................... 50
21.2 Kit components and technical data................................................................................................ 51
21.3 Humidity switch mode operation .................................................................................................. 51
21.4 Minichiller settings........................................................................................................................ 52
21.5 Installation notes............................................................................................................................ 52
21.6 Settable setpoints ........................................................................................................................... 52
21.7 Switching functions....................................................................................................................... 53
21.8 Electrical wiring diagram .............................................................................................................. 53
21.8.1 Wiring diagram, configuration without external relay .................................. 53
21.8.2 Wiring diagram, configuration with external relay ....................................... 54
21.9 Humidity switch connections ........................................................................................................ 54
21.10 Standard water system diagram..................................................................................................... 55
TECHNICAL MANUAL
Chapter 1 - Purpose and contents of this manual
NGSi 05÷15
4
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
CHAPTER 1
PURPOSE AND CONTENTS OF THIS MANUAL
The manual of NGSi units contains all the necessary information for optimal use of the equipment in conditions of safety for the
operator, as required by the Machinery Directive 2006/42/EC and subsequent amendments.
This manual is intended to provide the information required for the selection, installation, use and maintenance of NGSi units. The
instructions it contains are intended for the operator who uses the unit; even if he is not specifically skilled, the information he will find here
will enable him to use it effectively.
The manual describes the equipment at the time of sale and is therefore to be considered appropriate to it, notwithstanding any subsequent
technological improvements made by MTA to the capabilities, ergonomics, safety and functionality of its products.
MTA therefore does not accept any obligation to update the manuals of previous versions of its equipment.
Users are urged to comply strictly with the information in this manual, especially that relating to safety and routine maintenance.
1.1 Conserving the manual
The manual must always accompany the unit to which it refers. It must be kept in a safe place, protected from dust and damp and easily
accessible to the operator, who must consult it whenever he is in any doubt regarding the use of the equipment.
MTA reserves the right to modify the manual together with its products, without any obligation to update materials already delivered.
Disclaims any liability for any inaccuracies in the manual, if due to printing errors or copying errors.
Any updates sent to the customer must be kept attached to this manual.
MTA is at customers’ service for the provision of more detailed information the topics covered by this manual, or information concerning
the use and maintenance of its equipment, on request.
1.2 Symbols used in the manual
CHAPTER 2
STANDARDS OF REFERENCE
The equipment covered by MTA and its individual component units have been designed in accordance with the relevant harmonised EC
standards and the other European and domestic standards, applicable in accordance with the Machinery Directive issued by the Council of
the European Communities (2006/42/EC and subsequent amendments).
The following have also been complied with:
EN ISO 12100 standard
EN ISO 13857 standard
UNI EN 378-1, 378-2, 378-3 and 378-4 standards
UNI EN 12735-1 standard
CEI EN 60204-1 standard
EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3, EN 62233 standards
Community Directives 97/23/EC, 2006/95/EC, 2004/108/EC, 2002/95/EC and 2002/96/EC
CHAPTER 3
PERMITTED USE
The company excludes all contractual and extra-contractual liability for damage caused to persons, animals or things, by
incorrect installation, adjustment and maintenance, improper use or partial or superficial reading of the information
contained in this manual.
These units have been designed for heating and/or cooling water. A different application, unless expressly authorized by the
manufacturer, is to be considered improper and therefore not permitted.
The location, the water and electrical systems must be determined by the system designer and must take into account both
the purely technical needs as well as any applicable local legislation and specific authorizations.
The execution of all work must be performed by qualified and experienced personnel, who knows the rules in force in
different countries.
Indicates operations dangerous for people and/or for the correct operation of the equipment.
Indicates operations which must not be carried out.
Indicates information with which the operator must comply to ensure that the equipment performs well in conditions of
safety.
TECHNICAL MANUAL
Chapter 4 - General safety regulations
NGSi 05÷15
5
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
CHAPTER 4
GENERAL SAFETY REGULATIONS
Before starting any type of procedure on the NGSi units, every operator must be perfectly familiar with operation of the equipment and its
controls and have read and understood all the information in this manual.
4.1 Occupational health and safety
It is reminded that the European Union has issued directives concerning the safety and health of workers, among which: 89/391/EEC,
89/686/EEC, 89/655/EEC, 86/188/EEC and 77/576/EEC that each employer has obligation to respect and enforce. Users are therefore
reminded that:
4.2 Personal protective equipment
During use and maintenance of NGSi units, personal protective equipment must be used, including:
The removal of and/or tampering with any safety device is strictly forbidden.
Children or unassisted disabled persons are not allowed to use the equipment.
Do not touch the equipment when barefoot or parts of the body are wet or damp.
Do not pull, detach or twist the electrical cables coming from the equipment, even if it is disconnected from the mains power
supply.
Do not stand with feet, sit and/or lean on any type of object on the equipment.
Do not spray or pour water directly on the equipment.
It is prohibited to dispose of, abandon or leave within reach of children packaging materials (cardboard, staples, plastic bags,
etc.) because it can be a potential source of danger.
All routine or unplanned maintenance operations must be carried out with the equipment at a standstill and disconnected
from the electricity supply.
Do not place hands or fit screwdrivers, spanners or other tools on moving parts.
The person in charge of the equipment and the maintenance operative must receive appropriate training and instruction to
enable them to perform their tasks in conditions of safety.
Operators must be familiar with personal protection equipment and the safety rules contained in national and international
laws and standards.
Tampering with or replacement of parts of the equipment not specifically authorised by the manufacturer is forbidden.
Procedures of this kind relieve the manufacturer of all liability under civil or criminal law.
The use of components, consumables or parts other than those recommended by the manufacture and/or specified in this
manual may be dangerous for operators and/or cause damage to the equipment.
The operator’s workstation must be kept clean and tidy and free of any objects which may restrict his freedom of movement.
The workplace must be suitably lit for the planned procedures. Insufficient or excessive lighting may be a source of risks.
Ensure that workplaces are well ventilated at all times and that extraction system are always in operation, in good condition
and compliant with the relevant legal requirements.
Clothing: Anyone performing maintenance on or using the system must wear clothing compliant with the relevant essential
safety requirements. He must also wear safety footwear with non-slip soles, especially in areas with slippery floors.
Gloves: Suitable protective gloves must be worn during cleaning and maintenance procedures.
TECHNICAL MANUAL
Chapter 4 - General safety regulations
NGSi 05÷15
6
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
4.3 Safety signs
The unit carries the following safety signs, with which personnel must comply:
4.4 Refrigerants safety datasheet
Mask and goggles: A mask to protect the airways and protective goggles must be worn during cleaning operations.
General hazard.
Dangerous voltage.
Moving parts.
Surfaces which may cause injuries.
Denomination: R410A (50% Difluoromethane (R32); 50% Pentafluoroethane (R125).
INDICATION OF HAZARDS
Major hazards: Suffocation.
Specific hazards: Rapid evaporation can cause cold burns.
FIRST AID MEASURES
General information: Do not attempt to administer liquids or solids to persons who have lost consciousness.
Inhalation: Move victims to the open air.
Use oxygen or artificial respiration if necessary.
Do not administer adrenaline or similar substances.
Contact with the eyes: Wash thoroughly with plenty of clean water for at least 15 minutes and seek medical assistance.
Contact with the skin: Wash immediately in plenty of clean water.
Remove contaminated clothing immediately.
FIRE-FIGHTING MEASURES
Means of extinction: Any.
Specific hazards: Pressure rise.
Specific methods: Cool containers with water spray.
MEASURES IN THE EVENT OF ACCIDENTAL LEAKAGE
Individual precautions: Evacuate personnel to safe muster points.
Provide adequate ventilation.
Use personal protective equipment.
Environmental precautions: Evaporates.
Cleaning methods: Evaporates.
HANDLING AND STORAGE
Handling technical
measures/precautions:
Ensure the presence of sufficient ventilation and/or air extraction means in the workplace.
Recommendations for safe use: Do not breath fumes or aerosol.
Storage: Close hermetically and store in a cool, dry and well-ventilated place.
Store in its original containers. Incompatible products: explosive materials, inflammable materials,
organic peroxide.
CONTROL OF EXPOSURE/INDIVIDUAL PROTECTION
Control parameters: AEL (8-h and 12-h TWA) = 1000 ml/m3 for each of the two components.
Respiratory protection: For rescue and maintenance work in tanks, use autonomous breathing apparatus.
The vapours are heavier than air and can cause suffocation, reducing the oxygen available for breathing.
Protection of the eyes: Safety spectacles.
Protection of the hands: Rubber gloves.
Hygiene measures: Do not smoke.
TECHNICAL MANUAL
Chapter 5 - Technical features
NGSi 05÷15
7
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
CHAPTER 5
TECHNICAL FEATURES
NGSi series water chillers and heat pumps are designed for residential and commercial applications. They are extremely versatile and when
operating in heat pump mode they are able to produce hot water at a temperature of 55°C for environmental heating and domestic use. The
brushless INVERTER compressor, combined with an electronic expansion valve, pump and variable speed fan, optimises the power
consumption and operating efficiency of the refrigerating components.
5.1 Frame
All NGSi units are in hot-galvanised sheet metal, painted with polyurethane powder enamels baked at 180°C to ensure the best resistance to
atmospheric agents. The frame is free-standing with removable panels for easier inspection and maintenance of the internal components. All
screws and rivets for outdoor installations are in galvanised steel.
5.2 Refrigerant circuit
The refrigerant circuit has been manufactured with components supplied by top international producers and in accordance with the UNI EN
13134 standard on braze-welding procedures. The refrigerant gas used is R410A. The refrigerant circuit includes: 4-way reverse cycle valve,
electronic expansion valve, liquid separator (07, 10 and 15 models), liquid receiver, inspection valves for maintenance and checks, PED
standard safety device (high pressure pressure switch), pressure transducers for accurate control of evaporating and condensing pressures and
filters to prevent fouling of the thermal expansion valve.
5.3 Compressors
The DC inverter compressors are of rotary hermetic (05 and 07 models), twin rotary (10 model) and scroll (15 model) types, specifically
designed for use with R410A refrigerant; they are all equipped with thermal overload protection and mounted on rubber dampers.
The compressors are installed in a separate chamber, out of the air stream, to reduce noise.
The crankcase heater is powered up when the compressor is off by at least 30 minutes and if the discharge temperature is below 20°C (with
hysteresis of 2.0°C). The crankcase heater is disabled when the compressor restarts. It is recommend to plug the unit in and put it on stand-
by at least 6 hours before it starts operation.
Compressors can be inspected through the front panel, which allows maintenance to be performed even with the unit in operation.
5.4 Air side exchanger
The air side heat exchangers are constructed with copper tubes and aluminium fins. The copper tubes have a diameter of 7 mm in the 05 and
07 models and 5/16” in the 10 and 15 models; the aluminium fins are 0.1 mm thick. The tubes are mechanically expanded into the aluminium
fins to improve the heat exchange factor. The geometry of these exchangers guarantees low air side pressure drop, meaning that fans
operating at low rpm can be used (reducing the unit’s noise level).
5.5 Fans
The unit is fitted with plastic axial fans with aerofoil blades. They are all statically and dynamically balanced and supplied complete with
safety grille as required by the EN 60335 standard (safety of household and similar electrical appliances). The fans are installed on the unit
on rubber dampers to reduce the noise level. All electric motors used are of 8 pole modulating brushless type (200/1000 rpm). The motors are
directly coupled and equipped with integral thermal overload protection. Motors all have IP X4 protection rating.
5.6 User heat exchangers
The user heat exchangers are of braze-welded plate type and are in AISI 316 stainless steel, insulated with closed-cell material in the factory;
they can be equipped with antifreeze heaters (AK optional accessory). Each evaporator is protected by an antifreeze protection temperature
probe, which starts up the water circulator, even with the unit switched off, if the conditions set on the control unit occur.
PHYSICAL AND CHEMICAL PROPERTIES
Colour: Colourless.
Odour: Slight.
Boiling point: -52.8°C at atmospheric pressure.
Flash point: Non-flammable.
Relative density: 1.08 kg/l at 25°C.
Solubility in water: Negligible.
STABILITY AND REACTIVITY
Stability: No reactivity if used in compliance with the relative instructions.
Materials to avoid: Strong oxidants. Incompatible with magnesium, zinc, sodium, potassium and aluminium.
The incompatibility becomes more serious if the metal is in powder form or if the surfaces have recently
not been protected.
Hazardous decomposition
products:
These products are halogen compounds, hydrofluoric acid, carbon oxides (CO, CO2) and carbonyl
halides.
TOXICOLOGICAL INFORMATION
Acute toxicity: (R32) LC50/inhalation/4 hours/lab.rats >760 mg/l
(R125) LC50/inhalation/4 hours/lab.rats >3480 mg/l
Local effects: Concentrations significantly above the TLV can cause narcotic effects.
Inhalation of products in decomposition can lead to respiratory difficulty (pulmonary oedema).
Long-term toxicity: No carcinogenic, teratogenic, or mutagenic effects observed in laboratory animals.
ECOLOGICAL INFORMATION
Global warming potential GWP
(R11=1):
1.730
Ozone depletion potential ODP
(R11=1):
0
Considerations on disposal: usable with reconditioning.
TECHNICAL MANUAL
Chapter 6 - Versions available
NGSi 05÷15
8
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
5.7 Control panel
The control panel is constructed in compliance with the relevant European standards. The panel is accessed by removing the front and side
panels and top of the unit with the aid of a suitable tool. The panel control protection rating is IP24. The panel also comprises a terminal
board with clean contacts for remote ON-OFF switching, summer/winter switching, the auxiliary heater, the domestic hot water sensor,
control of a remote 3-way valve and contacts for the remote control panel and double set point operation.
5.8 Control system
All NGSi units are equipped with a microprocessor with overheating control by means of the electronic thermostatic valve operated in
response to the signals sent by the pressure transducers. The CPU also controls the water temperature setting, antifreeze protection,
compressor timing, alarm reset, alarm control and operating LEDs. On request, the microprocessors can be connected to BMS remote control
systems and the simpler HNS system with our terminals. The control system, combined with the use of INVERTERS and the on-board
sensors, monitors performance of the inverter compressor, circulator and fan (2 fans in 10 and 15 models) and adapts its constantly and
swiftly as required.
The INVERTER system reduces the system’s minimum water content from the conventional 12-15 litres/kW of chilling power to the
ABSOLUTE figures of 18 litres for the 05, 25 litres for the 07, 35 litres for the 10 and 45 litres for the 15 model in the NGSi series.
Thanks to these exceptionally low water contents, NGSI series units are suitable for systems without water tanks, with obvious
benefits in terms of reduction in unit size, installation space requirements, heat loss and system installation and maintenance costs.
5.9 Monitoring and protection devices
All units are supplied as standard with the following monitoring and protection devices: return water temperature probe on the system water
return line, operating and antifreeze probe on the pipe delivering water to the system, high pressure transducer, low pressure
transducer, compressor inlet and outlet temperature probes, compressor thermal protection devices, fan thermal protection devices, water
side flow switch to protect the evaporator and high pressure switch.
5.10 Water circuit
NGSi chiller units have an integral water circuit including the circulator pump, suitable for the use of chilled water and directly controlled by
the unit’s own control unit. The circulator, always of modulating type, has an induction motor. The water circuit also includes the expansion
vessel, the safety valve (6 bar) and the automatic air bleeder valve.
5.11 Fan speed regulation
The fan speed is controlled by the microprocessor in order to optimise the evaporation/condensation pressure for summer/winter operation,
to enable the unit to operate correctly.
CHAPTER 6
VERSIONS AVAILABLE
NGSi - reversible heat pump with integrated hydronic system (expansion vessel, safety valve, pressure gauge, modulating circulator pump,
flow switch, automatic air bleeder valve. intake/discharge valve).
Models available: 05, 07, 10 and 15.
6.1 Optional accessories
Hi-T - Multi-function touch screen remote control that integrates the centralized management of the minichiller and of the HNS system, the
functions of USB port, humidity and temperature sensors. It is also equipped with an extremely intuitive interface that simplifies the use of
the control.
CRH - Remote control panel for installation in the room for remote control of the unit, with extra functions in addition to those provided on
the unit, also able to control our hydronic terminals.
AG - Rubber dampers for installation underneath the unit to cushion any vibrations.
AK - Antifreeze kit (this accessory must be installed in the factory and must be specified when ordering). It comprises a heating cable wound
around the base of the unit near to the condensation coil and a Mylar heating element on the faces of the plate heat exchanger.
KDS - Double setpoint kit (already integrated in the Hi-T) for the management of a second working setpoint on the system side.
CHAPTER 7
INSTALLATION
7.1 General
When installing or servicing the unit, staff must comply strictly with the instructions provided in this manual and those on the unit itself, and
always take all necessary precautions. Failure to follow instructions may be dangerous.
MTA must be notified of the damage within 8 days. The Customer must draw up a written report in the event of significant damage.
WARNING:
The INVERTER control system is able to manage minimum system water contents of 18 litres for the 05 model, 25 litres for
the 07 model, 35 litres for the 10 model and 45 litres for the 15 model. These figures in litres are absolute values, and not values
per kW of rated power.
WARNING:
All the operations described below must only be performed by QUALIFIED STAFF. Before doing any work on the unit,
make sure that the electricity supply is disconnected.
On receipt of the unit, inspect it for damage: it left the factory in perfect condition. Any damage must be reported to the
forwarder at once and noted on the Delivery Sheet before it is signed.
TECHNICAL MANUAL
Chapter 7 - Installation
NGSi 05÷15
9
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
7.2 Lifting and handling
7.3 Positioning and spaces required for technical purposes
* Recommended installation and maintenance space
** Recommended servicing and maintenance space
7.4 Water connections
The water connections must be made in accordance with national or local regulations; the pipelines may be in steel, galvanised steel or PVC.
The size of the pipelines must be carefully calculated for the unit’s rated flow rate and the pressure drops in the water circuit. All water
connections must be insulated with closed cell material of suitable thickness. The chiller must be connected to the pipeline by means of
flexible couplings. The following components should be installed in the water circuit:
Well thermometer for measuring the temperature in the circuit.
Manual gate valves for shutting off the chiller from the water circuit.
Y-shaped metal filter (on the system return line) with metal mesh of no more than 1 mm.
Loading assembly and discharge valve where necessary.
When unloading and positioning the unit, the greatest care must be taken to
avoid sharp or violent movements, to protect the internal components. Units can
be lifted with the aid of a forklift truck, or with slings, taking care not to damage
the side and top panels. The unit must always be kept horizontal during these
operations.
All NGSi series models are designed and built for outdoor installation; they
should therefore never be covered with canopy roofs or placed close to trees or
walls to ensure that air is not recycled through them. A plinth of suitable size for
the unit should be provided. Units transmit only a low level of vibration to the
ground, but vibration damping supports should be placed between the base frame
and the supporting surface. It is also important to avoid problems of recirculation
of air between the intake and delivery sides to avoid impairment of the unit’s
performance or even a shut-down of normal operation. To ensure this, the
minimum operating spaces detailed below must be left.
MOD. A B* C D E**
NGSi 05 1,500 500 400 400 500
NGSi 07 1,500 500 400 400 500
NGSi 10 1,500 500 400 400 500
NGSi 15 1,500 500 400 400 500
WARNING:
when deciding pipeline sizes, take care not to exceed the maximum system side pressure drop shown in the technical data
table in Section “Technical data” (see working head values).
WARNING:
Connect the pipes to the connections using always the double key system.
WARNING:
The system return pipeline must be connected to the point marked “WATER INTAKE”; otherwise, the evaporator might
freeze.
WARNING:
A metal filter with (mesh of no more than 1 mm) must be installed on the system return pipeline labelled “WATER
INTAKE”. If the flow switch is tampered with or modified, or if the metal mesh filter is not installed on the system, all
warranty cover is forfeited at once. The filter must be kept clean, so the user must check after installation that it is still clean,
and then inspect it regularly.
All units leave the factory complete with flow switch (mounted in the factory). If the flow switch is modified or removed, or if
the water filter is not fitted in the unit, the warranty will lose all validity. Refer to the wiring diagram provided with the unit
for connection of the flow switch.
TECHNICAL MANUAL
Chapter 7 - Installation
NGSi 05÷15
10
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
7.4.1 Connecting to the condensate drain
All NGSi units are built so that the base of the unit acts as a condensate collection basin. A plastic union is supplied as standard for
connection to the fitting provided underneath the base, to allow connection of a pipe to drain off the condensate.
The base of the hydronic kit of each unit (on the right-hand side panels) of each unit also has a hole to allow drainage of any condensate
which may percolate from the water system pipes. Since these pipes are well insulated, the amount of condensate produced is minimal, and
therefore the connection of a drain pipe to this hole is not essential.
7.4.2 Service tap
If it becomes necessary to top up the system or adapt the glycol concentration, it is possible to use the service valve. Unscrew the cap of the
service tap and connect a hose connection to the 14 mm (inner diameter) hose connected to the water network, and then load the system by
unscrewing the ring nut. After the operation, re-tighten the nut and screw on the cap. It is in any case recommendable for loading the system,
to use an external tap whose prearrangement is made by the installer.
7.4.3 System drainage
If it is necessary to fully discharge the unit, first close the inlet and outlet manual gate valves (not supplied) and then remove the tubes
arranged externally on the water inlet and outlet so as to drain the liquid contained in the unit (to make this operation easy, it is
recommended to externally install on the water input and output two drain valves interposed between the unit and the manual gate valves).
7.4.4 Water system diagram
Condensate drain union Union connected to the unit Condensate drain union fitting
KEY
A Plate heat exchanger
B Flow switch
CService tap
D Circulator pump
E Expansion vessel
F Air bleed valve
G Safety valve
H Pressure gauge
Ring nut
Cap with gasket
A
B
H
GF
E
D
C
TECHNICAL MANUAL
Chapter 7 - Installation
NGSi 05÷15
11
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
7.5 5-9 kW chiller diagram
7.6 12-15 kW chiller diagram
C Compressor
CLS Compressor liquid separator
ST Compressor intake temperature
DT Compressor outlet temperature
HP High pressure transducer
Pr High pressure switch
LP Low pressure transducer
LS Liquid separator (on 07, 10 and 15 models only)
4WV Cycle reverser valve
LR Liquid receiver
EEV Electronic expansion valve
FL Filter
M Axial fan
SE External air temperature
P Circulator installed on unit
IN Water intake temperature
OUT Water outlet temperature
C Compressor
CLS Compressor liquid separator
OS Oil separator (on 10 and 15 models only)
ST Compressor intake temperature
DT Compressor outlet temperature
HP High pressure transducer
Pr High pressure switch
LP Low pressure transducer
LS Liquid separator (on 07, 10 and 15 models only)
4WV Cycle reverser valve
LR Liquid receiver
EEV Electronic expansion valve
NRV Check valve (may be fitted on some models)
FL Filter
M Axial fan
SE External air temperature
P Circulator installed on unit
IN Water intake temperature
OUT Water outlet temperature
CP Capillary
WARNING:
The unit must be installed in a manner which allows maintenance and repairs. The warranty does not cover costs of the
platforms or handling equipment required for any work on the unit.
All maintenance and inspection procedures must only be performed by QUALIFIED STAFF.
Before doing any work on the unit, make sure that the electricity supply is disconnected.
WARNING:
The unit contains several moving components. Take great care when working in their vicinity, even if the electricity supply is
disconnected.
The compressor heads and delivery pipeline are often at quite high temperatures. Take special care when working in the
vicinity of the heat exchanger coils.
The aluminium fans are particularly sharp and may cause serious injuries.
SE
EEV
LR
IN OUT
4WV
DT
LP HP
ST
M
P
C
LS
OS
FL FL
NRV
CP
CLS
Pr
TECHNICAL MANUAL
Chapter 7 - Installation
NGSi 05÷15
12
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
7.7 Electrical connections
Check that the electricity supply corresponds to the unit’s rated data (voltage, phases and frequency) marked on the nameplate on its right-
hand panel. The electrical connection must be made in accordance with the wiring diagram supplied with the unit and with the local and
international regulations (provide a magneto-thermal master switch, differential security breakers for each line, suitable ground connection
for the system, etc.). The power supply cables, electrical protection devices and line fuses must be of the size stated in the unit’s wiring
diagram and in the electrical data in the technical specification table (see Section “Technical data”).
7.7.1 Connection terminal board
The electrical connections must be made by qualified staff. The connection terminal board underneath the plastic cover on the same side
as the water connections (for the 10 and 15 models, the protective casing must be removed). When connecting the terminal board, comply
with the instructions provided below (the drawing is guideline).
The connections described below are standard. Other connections are described in the table in Point 9.25.
After maintenance procedures, put the panels back in place, securing them with the fixing screws.
WARNING:
There must be no variations in the power supply voltage in excess of ±10% of the nominal value. If this tolerance is not
complied with, please contact our technical department.
WARNING:
The electricity supply must comply with the stated limits: otherwise, the warranty becomes null and void immediately. Before
starting any work on the unit, make sure that the electricity supply is disconnected.
WARNING:
The flow switch (B in the water system diagram above and installed in the factory) must ALWAYS be connected as stated in
the wiring diagram. Never bridge the flow switch connections on the terminal board. No warranty cover will be provided if
the flow switch connections have been modified or incorrectly connected.
WARNING:
The remote control panel is connected to the chiller by 4 cables with gauge 1.5 mm2. The power supply cables must be
separate from the remote control cables. Maximum distance 50 metres.
WARNING:
The remote control panel cannot be installed in an area with strong vibrations, corrosive gases, excess dirt or high humidity
levels. Leave the area close to the cooling system unobstructed.
The connections to the terminal board must only be made by qualified staff.
Terminal Type Connection
GND power supply
1-Ph/N/PE
230V, 50Hz
(3-Ph/N/PE
400 Vac, 50Hz in the 15kW size)
connect the ground cable
N1 power supply
1-Ph/N/PE
230V, 50Hz
(3-Ph/N/PE
400 Vac, 50Hz in the 15kW size)
connect the mains neutral cable
L1 power supply
1-Ph/N/PE
230V, 50Hz
(3-Ph/N/PE
400 Vac, 50Hz in the 15kW size)
connect the mains live cable (in three-phase versions, there
are two additional terminals, L2 and L3).
TECHNICAL MANUAL
Chapter 7 - Installation
NGSi 05÷15
13
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
NC1 digital output
230 Vac with exchange contact
NC terminal for supply of power (230V AC) to 3-way valve
for domestic hot water heater (only used for 3-way valves
with 3-point power supply, for switching to system side)
(for other configurations see Point 9.25)
Ndigital output
230 Vac with exchange contact
neutral terminal for supply of power (230V AC) to 3-way
valve for domestic hot water heater (for other
configurations see Point 9.25)
NO1 digital output
230 Vac with exchange contact
NO terminal for supply of power (230V AC) to 3-way valve
for domestic hot water heater (for switching the valve to the
heater side) (for other configurations see Paragraph 9.25)
NC2 digital output
230 Vac with exchange contact
NC terminal for supply of power (230V, 50Hz, 5A resistive
load, 1 A inductive load) to 3-way valve for double setpoint
for radiators (optional to be used only on series V2, see
Point “Double setpoint kit (optional accessory)) (for
other configurations see Point 9.25)
N2 digital output
230 Vac with exchange contact
neutral terminal for supply of power (230V AC) to 3-way
valve for double setpoint for radiators (optional to be used
only on series V2, see Point “Double setpoint kit (optional
accessory)”) (for other configurations see Point 9.25)
NO2 digital output
230 Vac with exchange contact
NO terminal for supply of power (230V, 50Hz, 5A resistive
load, 1 A inductive load) to 3-way valve for double setpoint
for radiators (optional to be used only on series V2, see
Point “Double setpoint kit (optional accessory)) (for
other configurations see Point 9.25)
R+ serial communication connection of modbus + signal for remote keypad
R- serial communication connection of modbus - signal for remote keypad
GNDR serial communication modbus for remote keypad ground reference connection
12V+ power supply output 12Vac, 50Hz remote keypad power supply output (12V, 50Hz, 500mA)
12V- power supply output 12Vac, 50Hz remote keypad power supply output (12V, 50Hz, 500mA)
SE analogue (ST8) / digital (DI7) input input for humidity switch for double setpoint control
(optional) (for other configurations see Point 9.25)
SE analogue (ST8) / digital (DI7) input input for humidity switch for double setpoint control
(optional) (for other configurations see Point 9.25)
AEHN digital output (DO3) 230Vac neutral output for backup heater for domestic hot water
(230V, 50Hz, 5A) (for other configurations see Point 9.25)
AEH digital output (DO3) 230 Vac phase output for backup heater for domestic hot water
(230V, 50Hz, 5A) (per for other configurations see Point
9.25)
SAN analogue input (ST9) / digital (DI8) input for domestic hot water heater probe (for other
configurations see Point 9.25)
SAN analogue input (ST9) / digital (DI8) input for domestic hot water heater probe (for other
configurations see Point 9.25)
DO5N digital output (DO5) 230 Vac neutral output (optional to be used only if the machine has
not the antifreeze kit “AK” included) (for other possible
configurations see Point 9.25)
DO5 digital output (DO5) 230 Vac phase output (optional to be used only if the machine has
not the antifreeze kit “AK” included) (for other possible
configurations see Point 9.25)
DO4N digital output (DO4) 230 Vac neutral output (230V, 50Hz, 5A resistive load,
1 A inductive load) (optional to be used only if the machine
has not the antifreeze kit “AK” included) (for other possible
configurations see Point 9.25)
DO4 digital output (DO4) 230 Vac phase output (230V, 50Hz, 5A resistive load, 1 A inductive
load) (optional to be used only if the machine has not the
antifreeze kit “AK” included) (for other possible
configurations see Point 9.25)
SW digital input input for remote summer/winter mode switching (closed=
summer mode / open= winter mode)
SW digital input input for remote summer/winter mode switching (closed=
summer mode / open= winter mode)
onoff digital input remote on/off input (closed=unit on / open=unit off)
Terminal Type Connection
TECHNICAL MANUAL
Chapter 8 - Start-up
NGSi 05÷15
14
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
CHAPTER 8
START-UP
Before start-up:
Check that system diagrams and manuals for the unit installed are available.
Check that electrical and water system diagrams of the system to which the unit is connected are available.
Check that the water circuit stop taps are turned on.
Check that the water system has been filled and pressurised and the air has been vented.
Check that all the water system connections have been made correctly and all the instructions on the decals have been
followed.
Check that arrangements have been made for the drainage of condensate.
Check the electrical connection and that all the terminals are secure.
Check that the electrical connections have been made in accordance with the relevant standards, including the ground
connection.
The voltage must be as stated on the unit nameplate.
Check that the power supply voltage is within the tolerance limits (±10%).
Check that the compressor heaters are receiving power correctly.
Check that there are no gas leaks.
Before switching on the system, check that all the enclosing panels are in place and secured with the screws provided.
CHAPTER 9
USER - CONTROL INTERFACE
onoff digital input remote on/off input (closed=unit on / open=unit off)
0-10V+ analogue input (ST10) 0-10V (+) signal input for setpoint modification
0-10V- analogue input (ST10) 0-10V (-) signal input for setpoint modification
WARNING:
The unit must be connected to the electrical mains and set in STANDBY mode (powered up) by turning on the master switch
at least 12 hours before start-up, to allow the heater to warm up the compressor crankcase as required (the heaters are
automatically powered up when the master switch is on). The heaters are operating correctly if the compressor crankcase
temperature has risen to 10÷15°C above room temperature within a few minutes.
WARNING:
Never stop the unit temporarily by turning off the master switch; this must only be done to disconnect the unit from the power
supply for lengthy stoppages (e.g. seasonal lay-offs, etc.). When the power supply is disconnected the crankcase heaters no
longer receive power, leading to the risk of a compressor breakdown when the unit is started up.
WARNING:
Do not modify the electrical connections to the unit; otherwise, warranty cover is forfeited at once.
WARNING:
Summer/winter operating mode must be selected at the start of the relative season. Frequent switching back and forth
between these modes is not recommended, as it may damage the compressors.
WARNING:
When the unit is installed and commissioned, check that it operates correct in both heating and cooling modes.
Selects the operating mode and resets alarms which can be rearmed manually. The sequence at consecutive
pressures on the key is:
off Æ cool ÆheatÆ off
If domestic hot water is enabled, the sequence is:
offÆ cool Æ cool+san Æheat Æheat+sanÆ off
During parameter setting, it moves BACK one level.
Accesses the parameter setting menu, allowing setting of the summer, winter and domestic hot water setpoints.
Terminal Type Connection
TECHNICAL MANUAL
Chapter 9 - User - Control Interface
NGSi 05÷15
15
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
9.1 Menu structure
Level 0 (U) = always visible
Level 1 (M) = visible if the maintenance password (H80) or the manufacturer password is entered
Level 2 (C) = visible only if the manufacturer password is entered
Level 3 (A)= visible only through Modbus
9.1.1 Analogue inputs menu
Entering the maintenance password in the analogue inputs menu “tP” at level 1 of the menu structure of the control installed on the unit, it is
possible to read the values of the probes:
t01: water intake temperature (°C);
t02: water outlet temperature (°C);
t03: compressor intake temperature (°C);
t04: compressor outlet temperature (°C);
t05: high pressure (bar);
t06: low pressure (bar);
t07: outdoor air temperature (°C);
t09: domestic hot water temperature (°C) (if domestic hot water production is enabled).
UP key. In parameter setting mode, used to move to a higher level menu or to increase the value of a parameter
when in “modify” mode.
DOWN key. In parameter setting mode, used to move to a lower level menu or to decrease the value of a
parameter when in “modify” mode.
Level 0 Level 1 Level 2 Level 3 Level 4
Adjustment probe
Acve alarm
U Setpoint: SEt
Label Set cooling:
Coo Cooling setpoint value
Label Set heang:
HEA Heang setpoint value
M
Analogue Input:
tP
Input code:
t01-t04 Analogue Input value
UAlarms: Err
Acve alarms code:
E00
M
Digital Inputs:
Id
Input code:
i01-i05 Digital input status
M Parameters:
PAr
Parameters category
Parameter index Parameter value
U Password: PSS
Password value
M
Operaon Hours:
Ohr
Compressor hours 1:
OH1 Number of hours
Compressor hours 2:
OH2 Number of hours
Pump hours:
OHP Number of hours
U = user
M = maintainer
C = manufacturer
TECHNICAL MANUAL
Chapter 9 - User - Control Interface
NGSi 05÷15
16
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
9.2 Parameters category
9.3 Setpoints settable by the user
The second setpoint is only operational if the relative optional kit has been purchased.
9.4 Display
Normally, the display shows the water output temperature in tenths of a degree Celsius or the alarm code if at least one alarm has been
tripped. With several alarms present, the first one is shown and the second one appears after the first has been reset. In menu mode, the
contents of the screen depend on the function being used.
9.5 LEDs
Description Group identification
code Parameter index
Configuration CnF H01-
Compressor CP C01-
Fan FAn F01-
Alarms ALL A01-
Adjustment Re b01-
Pump PUP P01-
Electric heaters Fro r01-
Defrosting dFr d01-
Electronic valve EEu U01-
Offset OFF o01-
Setpoint type Setpoint
(summer/winter)
Summer
default (range)
Winter
default (range)
First setpoint [°C] Coo/Hea 7 (5÷18) 45 (35÷55)
Second setpoint [°C] Co2/He2 18 (7÷23) 35 (25÷45)
Hot water setpoint [°C] San 48 (25÷55)
Compressor LED ON with compressor in operation.
OFF with compressor not running.
FLASHING if compressor start delay timer is running.
Domestic hot
water LED
ON with domestic hot water valve active.
OFF with domestic hot water valve not active.
Defrost LED ON with defrosting active.
OFF with defrosting disabled or completed.
FLASHING if defrosting interval timer is running.
Antifreeze heater
LED
LED ON with antifreeze heater (optional) in operation.
Pump LED LED ON with pump in operation.
Alarm LED LED ON with an alarm tripped.
Heating mode
LED
LED ON with unit in heating mode.
Cooling mode
LED
LED ON with unit in cooling mode.
TECHNICAL MANUAL
Chapter 9 - User - Control Interface
NGSi 05÷15
17
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
9.6 Modifying the dynamic setpoint
The regulator allows the setpoint to be modified by adding an offset to the external air temperature probe reading. To use this function, the
user has to set the values of parameters b08 to b14 following the instructions provided below (modifications to be made by the installer).
Parameters of regulator PAr->rE->
b08 = dynamic setpoint enabled=1 / disabled=0 (must be disabled if weather compensation from the optional CRH remote
keypad is used).
b09 = cooling maximum offset.
b10 = heating maximum offset.
b11 = External temperature setting in cooling mode.
b12 = External temperature setting in heating mode.
b13 = Temperature delta in cooling mode.
b14 = Temperature delta. in heating mode.
Modifying the setpoint in relation to the external temperature:
9.7 Modifying the setpoint from 0-10V input
Another type of adjustment allows to change the set-point by adding (or subtracting) a value according to the 0-10V input (if enabled). To
enable the function, set H21=40, and if necessary change the value of the parameter b15 (0-10 range), taking into consideration that:
with 0 Volt input the current setpoint will be: (Coo/Hea) setpoint set – b15/2
with 5 Volt input the setpoint will be the one set (Coo/Hea)
with 10 Volt input the current setpoint will be: (Coo/Hea) setpoint set – b15/2
Cooling
Heating
Ext. temp. set.
Ext. temp. set.
TECHNICAL MANUAL
Chapter 9 - User - Control Interface
NGSi 05÷15
18
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
The 0-10V signal must be applied to 0-10V+ and 0-10V terminals (see wiring diagrams).
NOTE
In “cool” mode, considering that the chiller setpoint by default is set to 7°C, the parameter b15 must not have a value greater than or equal
to 6 to ensure that the new setpoint set from the 0-10V input can achieve values below the antifreeze activation threshold (4°C).
9.8 Hydraulic pump operation
The hydraulic pump can be set according to one of the three following types of operation:
operation on call of the temperature controller (default)
operation on call from the temperature controller with periodic activation
continuous operation
The pump is switched off immediately if the flow switch alarm is activated in manual reset.
The pump instead is always on if the antifreeze heaters are operating or if the hydraulic pump in antifreeze mode operation is activated.
The operation in antifreeze mode is activated if the adjustment temperature drops below P04 °C (default 5°C), it is disabled if the adjustment
temperature rises above P04+P05 °C (Default value of P05=2.0°C).
The pump adjustment is proportional (see Point 9.8.4).
9.8.1 Operation on call from temperature controller (Default)
In this user mode (P03=1, default), the pump is activated upon request of the temperature controller; and after a time delay of 20 seconds
from the pump start up, also the compressor activates. In power off, instead, the pump is switched off with a delay time of 120 seconds from
the call with the temperature controller in off status (off status coinciding with the compressor power off).
With flow switch alarm active in automatic reset the pump is however turned on even if the compressor is off.
If the machine operation is enabled from the remote “on-off” digital input (see Point 9.10), the circulator is immediately activated for a time
of 2 minutes, regardless of the temperature control inside the unit (the activated water recirculation allows the correct activation of the
temperature control).
0 - 10 V Input [V]
New setpoint [°C]
Setpoint set
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58

MTA NGSi 15 Technical Manual

Category
Heat pumps
Type
Technical Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI