tekmar 406 Installation guide

Category
Heat pumps
Type
Installation guide

This manual is also suitable for

tekmarNet
®
2 House Control 406
406_D
05/16
Alternative
Energy
Replaces: 10/14
Installation & Operation Manual
1 of 48 © 2016 406_D - 05/16
Menu
House Control 406
Item
Benefits
Energy efficiency through Outdoor Temperature
Reset with Indoor Temperature Feedback
Indoor Temperature Feedback minimizes the water
temperature (increasing energy savings), and the
efficiency of your mechanical equipment through
integrated tekmarNet
®
Thermostats
Zone Synchronization reduces equipment cycling
Auto Differential - Reduces boiler cycling
Compact enclosure for flexible installation
Simple zone expansion using Wiring Centers
Features
One or two-stage heat pump control
Equal runtime rotation for two heat pumps
On/off or modulating boiler control
Tank, mix and boiler outdoor reset temperatures
Domestic hot water operation
Setpoint operation
Mixing with variable speed pump
For use with tekmarNet
®
2 Thermostats
Four 24 V (ac) built in powered zone valve outputs
Expand to 24 zones on two water temperatures using
tekmarNet
®
4 expansion ports
CSA C US Certified for use in USA and Canada
Introduction
The tN2 House Control 406 is designed to operate the
equipment in a 2-pipe, single tank, hydronic heating and
cooling system. It operates two heat pump stages (water-
to-water or air-to-water) with a backup heat source (boiler
or electric resistance). The heat pump provides either hot
or chilled water to a storage tank loop and optional mixed
temperature loop. For radiant heating, the water temperature
is calculated using outdoor temperature reset. For radiant
cooling, the chilled water temperature is maintained at an
adjustable setpoint, or is adjusted using dew-point reset with
a humidity sensor. A backup boiler can provide an outdoor
reset water temperature as well as domestic hot water and
setpoint water temperatures. The 406 operates 4 on-board
heating and cooling zones and is expandable up to 52 zones
total on the boiler, tank, and mix water temperatures.
© 2016 406_D - 05/16 2 of 48
Table of Contents
Getting Started
Installation .........................................................................2
Preparation ....................................................................2
Important Safety Information .........................................3
Physical Dimensions .....................................................4
Installation Location .......................................................4
Rough-In Wiring .............................................................4
Sizing the Transformer ..................................................5
Control Wiring ................................................................5
Sensor Wiring ................................................................8
Testing the Sensor Wiring ............................................. 9
Testing the Control Wiring ........................................... 10
Max Heat ..................................................................... 11
Applications .....................................................................12
User Interface ..................................................................22
Display .........................................................................22
Symbols .......................................................................22
Navigating The Display ................................................22
Access Levels and Thermostat Lock ..........................23
Programming and Settings ..........................................23
View Menu ..............................................................23-25
Adjust Menu .................................................................25
Adjust Menu ............................................................26-30
Monitor Menu ..........................................................30-31
Toolbox Menu
.................................................32
Sequence of Operation ...................................................33
tekmarNet
®
System .....................................................33
System Setup ..............................................................33
Heat Cool Operation ....................................................35
Hydronic Operation......................................................36
Heat Pump Operation ..................................................37
DHW Operation ...........................................................38
Boiler Operation ...........................................................40
Setpoint Operation ...................................................... 41
Mixing Operation ......................................................... 42
Pump Operation ..........................................................42
Troubleshooting ...............................................................43
Error Messages (1 of 3) ......................................... 43-45
Frequently Asked Questions .......................................46
Job Record .................................................................. 47
Technical Data .................................................................48
Limited Warranty and Product Return Procedure ...........48
Congratulations on the purchase of your new tekmarNet
®
House Control!
This manual covers the complete installation, programming and sequence of operation for this control. You will also find instruc-
tion on testing, commissioning, and troubleshooting the control and system that it operates.
Installation
The installer must ensure that this control and its wiring are
isolated and/or shielded from strong sources of electromagnetic
noise. Conversely, this Class B digital apparatus complies
with Part 15 of the FCC Rules and meets all requirements of
the Canadian Interference-Causing Equipment Regulations.
However, if this control does cause harmful interference to
radio or television reception, which is determined by turning
the control off and on, the user is encouraged to try to correct
the interference by re-orientating or relocating the receiving
antenna, relocating the receiver with respect to this control,
and/or connecting the control to a different circuit from that
to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exi-
gences du Règlement sur le matériel brouilleur du Canada.
Radio Frequency Interference
Preparation
Tools Required
-----------------------------------------------------------------------------------------
tekmar or jeweller screwdriver
Phillips head screwdriver
Needle-nose Pliers
Wire Stripper
Materials Required
-------------------------------------------------------------------------------------
(2) #10 x 1” Wood Screws
(5) Wire Nuts
18 AWG LVT Solid Wire (Low Voltage Connections)
14 AWG Solid Wire (Line Voltage Connections)
tekmar 009K (24 V (ac) transformer with 4” x 4junction box)
4” x 4” Extension Ring for Electrical Junction Box
Cable or Conduit Connectors
3 of 48 © 2016 406_D - 05/16
For hydronic cooling with a fancoil, use tekmarNet
®
Thermostat 557.
For floor cooling, use tekmarNet
®
Thermostat 553 or 557.
To prevent the risk of personal injury and/or death, make sure power is not applied to the thermostat until it is fully
installed and ready for final testing. All work must be done with power turned off to the circuit being worked on.
Please be aware local codes may require this thermostat to be installed or connected by an electrician.
It is your responsibility to ensure that this thermostat is safely installed according to all applicable codes and standards. tekmar
is not responsible for damages resulting from improper installation and/or maintenance.
This is a safety-alert symbol. The safety alert symbol is shown alone or used with a signal word (DANGER,
WARNING, or CAUTION), a pictorial and/or a safety message to identify hazards.
When you see this symbol alone or with a signal word on your equipment or in this Manual, be alert to the
potential for death or serious personal injury.
This pictorial alerts you to electricity, electrocution, and shock hazards.
This symbol identifies hazards which, if not avoided, could result in death or serious injury.
This symbol identifies hazards which, if not avoided, could result in minor or moderate injury.
This symbol identifies practices, actions, or failure to act which could result in property damage or damage to
the equipment.
Read Manual and all product labels BEFORE using the equipment. Do not use unless you know
the safe and proper operation of this equipment. Keep this Manual available for easy access by all
users. Replacement Manuals are available at tekmarControls.com
It is the installers responsibility to ensure that this thermostat is safely installed according to all applicable codes and
standards.
Improper installation and operation of this thermostat could result in damage to the equipment and possibly even personal
injury or death.
This thermostat is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits
must be placed into the control circuit.
Do not attempt to service the thermostat. There are no user serviceable parts inside the thermostat. Attempting to do so voids
warranty.
Important Safety Information
© 2016 406_D - 05/16 4 of 48
Power Required
----------------------------------------------------------------------------------------
115 V (ac), 1-phase, 15 A service from circuit breaker panel
(potentially up to two circuits)
Power disconnect (optional)
Installation Location
When choosing the location for the control, consider the
following:
Keep dry. Avoid potential leakage onto the control.
RH
90% to 104°F (40°C).
Non-condensing environment.
Do not expose to operating temperatures beyond 32-104°F
(0-40°C)
Provide adequate ventilation.
Keep away from equipment, appliances or other sources of
electrical interference.
Locate the control near pumps and/or zone valves if possible.
Provide easy access for wiring, viewing and adjusting the
control.
Mount approximately 5 ft. (1.5 m) off the finished floor.
Install the electrical junction box to a wall using #10 x
1” wood screws. Wall anchors are recommended when
mounting to sheet rock wallboard or masonry.
Install the extension ring onto the electrical junction box.
Total box volume must be 38 cubic inches (623 cm
3
) or
greater to comply with National Electrical Code (NEC) or
Canadian Electrical Code (CEC).
Rough-In Wiring
Line Voltage Wiring
-------------------------------------------------------------------------------------
The control operates a number of pumps through wiring on
the back of the control. The control must be mounted to a 4" x
4" electrical junction box so that these electrical connections
are safely contained.
For ease of service, the circuit breaker or power discon-
nect should be located in reasonably close proximity to the
equipment.
All line voltage wire connections are recommended to be pulled
inside a flexible or solid conduit. Always follow proper wiring
practices, building and electrical codes for your jurisdiction.
Each cable must be pulled from the equipment to the electrical
junction box. It is recommended to label each cable for easy
identification. All line voltage wires should be stripped to a
length of 1/2" (13 mm).
Physical Dimensions
Front View Side View
Menu
House Control 406
Item
+
Tank ComBoil HPRt OutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2 tN2 tN2 tN2tN2 tN2 tN2 tN2
Rc1 Y1 O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA Boil / Mix Tank
Rc2 Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
5–1/2"
(140 mm)
5–1/2"
(140 mm)
1–1/8" (30 mm)
7/8"
(22 mm)
CL
Control designed to mount on 4" x 4" electrical
box (not included). For systems that require 2
power sources of 115 V (ac), a box extension
ring is required to increase box fill capacity.
Back View
Ø 1/8"
(3 mm)
7/8" x 1/2" (23 mm x 12 mm)
Knock-out (x 4)
1/2" x 5/8"
(12 mm x 16 mm)
Knock-out (x 4)
1/2" Knock-out (x 4)
2–1/4"
(57 mm)
4–1/2" (114 mm)
Pull a three conductor 14 AWG cable for the following
equipment:
Circuit Breaker or Power Disconnect
Variable Speed Pump (if applicable)
HP Loop Pump
Boiler System Pump (if applicable)
Tank System Pump (if applicable)
Mix System Pump (if applicable)
DHW Pump (if applicable)
Transfer (Xfr) Pump (if applicable)
Low Voltage Wiring
-------------------------------------------------------------------------------------
Each cable must be pulled from the equipment to the control’s
plastic enclosure. All low voltage wiring connections enter the
enclosure through conduit knockouts on the sides, or through
the square knockouts on the rear. It is recommended to label
each cable for easy identification. All low voltage wires are
to be stripped to a length of 3/8" (9 mm) to ensure proper
connection to the control.
5 of 48 © 2016 406_D - 05/16
HP Loop
Pump
Variable
Speed Pump
Boil System
Pump
Tank System Pump
Power
Source 1
Control Wiring
Line Voltage Wiring
-------------------------------------------------------------------------------------
Ensure Junction Box Extension Ring is Installed
An extension ring must be installed on the 4” x 4” junction
box when 6 or more powered outputs for the pumps are
used on the rear of the control.
Ground the Pumps
Connect the pump grounds to the power supply ground as
shown in Figure 1. The ground wire must also be grounded
to the electrical box.
Wire the Pump Neutrals
If the combined pump power load is less than 12 A, then a
only a single 15 A circuit is required.
If the combined pump power load exceeds 12 A, then two
separate 15 A circuits are required.
Each power circuit requires its own neutral wire.
Connect the Neutral (N) wires from each pump and wire to
the 115 V (ac) Neutral (N) wire. If the transformer has been
mounted to this electrical box, connect its neutral wire with
this group. This is shown in Figure 2 and Figure 3.
Wire the Pump Power (L)
If the combined pump power load is less than 12 A, then a
only a single 15 A circuit is required.
If the combined pump power load exceeds 12 A, then two
separate 15 A circuits are required.
Connect the 115 V (ac) line voltage (L) wire to the red Pump
Power (L) wire on the back of the House Control and to the
115 V (ac) side of the transformer. Use a wire nut or approved
connector. See Figure 4.
Wire the Pumps
Wire each remaining line voltage pump wire into the push-in
wire connector of the corresponding pump lead on the back
of the House Control. This is shown in Figure 5 and 6.
HP Loop
Pump
Power
Source 1
Power
Source 2
Tank System Pump
Mix Sy
stem Pump
DHW Pump
Transf
er Pump
Variable
Speed Pum
p
Boil System
Pump
Figure 1 -
Connect
Ground
Wires
Figure 2 -
Connect
Neutral Wires
for Power
Source 1
Pull two conductor 18 AWG LVT cable, up to 500 feet
(150 m) for the following equipment:
tekmarNet
®
2 Thermostats
Heat Pump Compressor Stage 1
Heat Pump Compressor Stage 2 (if applicable)
Heat Pump Reversing Valve (O or B)
Modulating Boiler 0-10 V (dc) or 4-20 mA (if applicable)
On/Off Boiler or Backup Heat Source (if applicable)
Outdoor Temperature Sensor
HP Return Temperature Sensor
Tank Supply Temperature Sensor
Boiler Supply Temperature Sensor (if applicable)
Mix Supply Temperature Sensor (if applicable)
DHW Tank Temperature Sensor (if applicable)
DHW Tank Aquastat (if applicable)
Setpoint Device (if applicable)
The control requires an external transformer. A tekmar Transformer
009 (or 009K which includes a 4”x 4” electrical box) can
supply up to 40 VA, and includes an in-line fuse to protect the
transformer and control.
In order to correctly size the external transformer, all loads
connected to the control must be taken into account.
When adding up the loads, consider the following:
tekmarNet
®
2 Thermostats draw approximately 2 VA each.
Each zone valve must be sized for peak load. This can be
Sizing the Transformer
obtained by multiplying the peak current draw (in Amps) by
24 V (ac).
If using a Floating Action mixing valve, add the VA draw for
the actuating motor. A tekmar Actuating Motor 741 draws
1.5 VA during normal operation.
The total power capacity of the power supply should be larger
than the total load of all the devices connected to the control. This
total load must not exceed 100 VA. Multiple tekmar Transformer
009’s can be wired together to increase total VA capacity.
Zone
1 2 3 4
Thermostat Load
Control
Load (VA)
Zone Valve Load
Total Zone Load
2
Transformer
must exceed:
VA
+ + + +
This chart is provided to
simplify transformer sizing:
Turn all power off before performing any wiring. A licensed electrician is recommended.
© 2016 406_D - 05/16 6 of 48
Power
Source 2
Mix Sy
stem
Pump
DHW
Pump
Transfer
Pump
Figure 3 - Connect Neutral Wires
for Power Source 2
Figure 4 - Line Voltage
Power
Source 2
Power
Source 1
Figure 5 - System Pumps (Left)
Tank System Pump
HP Loop
Pump
Variable
Speed Pump
Boil System
Pump
Figure 6 - System Pumps (Right)
Mix Sy
stem
Pump
DHW
Pump
Transfer
Pump
Ensure that the pump wires are neatly tucked inside the
electrical box.
Using 2 of the 4 holes in the back of the enclosure, securely
fasten it to the junction box extension ring with 2 #10 screws
as shown in Figure 7.
Install The Enclosure
----------------------------
Figure 7
Boil Sys
HP Sys
Mix Sys
DHW
Transfer
Variable
Speed
115 V (ac)
N1L1 G
115 V (ac)
N2
GL
2
to pump grounds
to pump grounds
N
N
L
L
Back of House Control 406
R
C
L
N
Expansion
tN4 Boil/Mix
CtN4
Modulating
Boiler
—+
Expansion
tN4 Tank
CtN4
Tank Sys
Mix Sys PumpTank Sys Pump
DHW Pump
Transfer Pump
Boil Sys Pump
HP Loop Pump
Pump
Power (L)
Pump
Power (L)
Variable
Speed Pump
tN2tN2tN2tN2tN2tN2tN2tN2
(blue)
(red)
(black)
(black)
(black)
1
(red)
(black)
(black)
(black)
314
313
Menu
House Control 406
Item
+
Tank ComBoilHPRtOutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2tN2 tN2 tN2 tN2 tN2 tN2 tN2
Rc1Y1O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA
Boil / Mix Tank
Rc2 Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Rear Line Voltage Wiring Diagram
----------------------------------------------------------------------
Back of House Control 406
7 of 48 © 2016 406_D - 05/16
External Power Supply
It is strongly recommended that a transformer with an in-line
fuse be used in order to protect the transformer from high
currents. The tekmar Transformer 009 includes a fuse.
Connect the 24 V (ac) leads from the transformer to the C
and R terminals marked “Input Power” on the 406.
tekmarNet
®
2 Thermostats (tN2)
The 406 is designed to operate with tekmarNet
®
2 Thermostats.
They provide the heating and cooling control for each zone,
and communicate with any other tekmarNet
®
device on the
system.
Connect the tN2 terminals from each thermostat to the cor
-
responding tN2 terminals for each zone on the 406.
Two stage heating thermostats are supported. Connect the
thermostat to zone 1 to operate the first stage. When zone
2 tN2 input is left empty the zone 2 zone output operates
as the second stage. Likewise, zone 3 operates as the first
stage and zone 4 operates as the second stage.
Zone Valves
Wire the zone valves to the C and Vlv terminals on the 406.
End switches on zone valves are not required when using
the 406.
tN4 Expansion Terminals
The 406 uses the Expansion tN4 and C terminals to com-
Low Voltage Wiring
-------------------------------------------------------------------------------------
Front Low Voltage Wiring Diagram
---------------------------------------------------------------------
Boil Sys
HP Sys
Mix Sys
DHW
Transfer
Variable
Speed
115 V (ac)
N1L1 G
115 V (ac)
N2GL2
to pump grounds
to pump grounds
N
N
L
L
Back of House Control 406
R
C
L
N
Expansion
tN4 Boil/Mix
CtN4
Modulating
Boiler
—+
Expansion
tN4 Tank
CtN4
Tank Sys
Mix Sys PumpTank Sys Pump
DHW Pump
Transfer Pump
Boil Sys Pump
HP Loop Pump
Pump
Power (L)
Pump
Power (L)
Variable
Speed Pump
tN2tN2tN2tN2tN2tN2tN2tN2
(blue)
(red)
(black)
(black)
(black)
1
(red)
(black)
(black)
(black)
314
313
Menu
House Control 406
Item
+
Tank ComBoilHPRtOutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2tN2 tN2 tN2 tN2 tN2 tN2 tN2
Rc1Y1O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA Boil / Mix Tank
Rc2 Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
24 V (ac) Transformer 009
DHW Call
from DHW
Tank Aquastat
(optional)
Setpoint Call
Outdoor Sensor
Mix Supply / DHW
Universal
Sensor
Tank Supply
Universal Sensor
Boiler Supply
Universal Sensor
One Stage
Boiler T-T
tekmarNet
®
2 Thermostats
tekmarNet
®
4 Expansion to
Wiring Centers, Timers, or
User Switch
HP Return
Universal Sensor
One or Two Stage
Heat Pump
24 V (ac) Zone Valves
municate with additional thermostats, setpoint controls, and
other tekmarNet
®
devices. Connect to either the Tank or the
Boil / Mix tN4 and C terminals on the 406.
Tank
To add additional Tank water temperature zones to the system,
install a tekmarNet
®
Wiring Center.
Connect the Tank terminals, tN4 and C, on the 406 to the
corresponding tN4 and C Expansion terminals on the ex-
ternal Wiring Center.
Boil / Mix
To add additional Boil or Mix water temperature zones to the
system, install a tekmarNet
®
Wiring Center.
Connect the Boil/Mix terminals, tN4 and C, on the 406 to
the corresponding tN4 and C Expansion terminals on the
external Wiring Center.
Domestic Hot Water (DHW) or Setpoint Call
When the control receives a DHW Call or Setpoint Call for heat
it will override Outdoor Reset and Indoor Feedback and operate
the boiler to heat the DHW tank or the Setpoint equipment.
To create a DHW call, wire a dry contact switch to the DHW
call terminals.
To create a Setpoint call, wire a dry contact switch to the
Setpoint call terminals.
© 2016 406_D - 05/16 8 of 48
Sensor Wiring
Connect 18 AWG or similar wire to the two terminals provided
in the enclosure and run the wires from the outdoor sensor
to the control. Do not run the wires parallel to telephone or
power cables. If the sensor wires are located in an area
with strong sources of electromagnetic interference (EMI),
shielded cable or twisted pair should be used or the wires
can be run in a grounded metal conduit. If using shielded
cable, the shield wire should be connected to the Com or
Com Sen terminal on the control and not to earth ground.
Follow the sensor testing instructions in this brochure and
connect the wires to the control.
Replace the cover of the sensor enclosure.
Wiring the Outdoor Sensor
-----------------------------------------------------------------------------
Wiring the Heat Pump
The 406 can operate a single heat pump with a two-stage
compressor in heating or cooling mode.
Connect the Rc1 and Y1 terminals on the 406 to the R and
Y1 terminals on the heat pump.
Connect the Rc2 and Y2 terminals on the 406 to the R and
Y2 terminals on the heat pump.
Connect the Rc1 and O/B terminal on the 406 to the R and
O or B terminal on the heat pump.
Wiring the Auxiliary Backup
The 406 can operate an auxiliary backup other than a boiler.
Use the Backup terminals on the 406 to switch on the aux
-
iliary backup (ie electric element).
On/Off Boiler
Connect the Backup terminals on the 406 to the T-T (or R-
W) terminals on the boiler.
Modulating Boiler
Wire the Mod (dc/mA) positive (+) and negative (-) terminals
on the 406 to the input signal terminals on the boiler. Correct
polarity of the wires is important.
In some cases, the modulating boiler also requires contact
closure on the T-T terminals to fire the boiler. If required,
connect the Backup terminals on the 406 to the T-T (or R-
W) terminals on the boiler.
Mounting the Outdoor Sensor 070
----------------------------------------------------------------------
The 070 can be mounted directly onto a wall with the wiring
entering through the back or bottom of the enclosure. Do
not mount the 070 with the conduit knockout facing upwards
as rain could enter the enclosure and damage the sensor.
In order to prevent heat transmitted through the wall from
affecting the sensor reading, it may be necessary to install
an insulating barrier behind the enclosure.
The 070 should be mounted on a wall which best represents
the heat load on the building (a northern wall for most build-
ings and a southern facing wall for buildings with large south
facing glass areas). The 070 should not be exposed to heat
sources such as ventilation or window openings.
The 070 should be installed at an elevation above the ground
that will prevent accidental damage or tampering.
Remove
cover by
sliding
upwards
away from
the base.
To wire from
the back,
remove the
knock-out in
the sensor
base.
S1
S1
If using
conduit,
remove
the flexible
plug from
the base
bottom.
S1
S1
Attach the
base to the
wall, soffit
or electrical
box.
S1
S1
Wires from
outdoor sensor
and sensor
common
terminals on
tekmar control
Sensor is built into the
enclosure
S1
S1
Slide cover
back over
base
9 of 48 © 2016 406_D - 05/16
Mounting the Universal Sensor
-------------------------------------------------------------------------
Note: These sensors are designed to mount on a pipe or in a temperature
immersion well.
The Universal Sensor should be placed downstream of a pump or after an elbow
or similar fitting. This is especially important if large diameter pipes are used as
the thermal stratification within the pipe can result in erroneous sensor readings.
Proper sensor location requires that the fluid is thoroughly mixed within the pipe
before it reaches the sensor.
Strapped to Pipe
The Universal Sensor can be strapped directly to the pipe using the cable tie
provided. Insulation should be placed around the sensor to reduce the effect of
air currents on the sensor measurement.
Immersion Well
If a Universal Sensor is mounted onto 1” (25 mm) diameter L type copper pipe,
there is approximately an 8 second delay between a sudden change in water
temperature and the time the sensor measures the temperature change. This
delay increases considerably when mild steel (black iron) pipe is used. In general,
it is recommended that a temperature well be used for steel pipe of diameter
greater than 1-1/4” (32 mm). Temperature wells are also recommended when
large diameter pipes are used and fluid stratification is present.
Conduit Connection
The Universal Sensor and Universal Sensor Enclosure 080 (sold separately) are
specifically designed to mount onto a 3/8” (10 mm) ID temperature well that is
supplied with an end groove. To install the well, plumb a ‘T into the pipe and fix
the well into the ‘T’. The 080 enclosure has a 7/8” (22 mm) back knockout that
must be removed and fitted over the temperature well. The universal sensor is
then inserted into the well and the retaining clip supplied with the enclosure is
snapped onto the well end groove. If the well has a threaded end, the installer
must supply a standard threaded conduit retaining ring. The two wires from the
sensor are connected to the terminal block provided in the enclosure. The other
side of the terminal block is used to connect wires from the control.
A good quality test meter capable of measuring up to 5,000 k
(1 k= 1000 ) is required to measure the sensor resistance. In
addition to this, the actual temperature must be measured with
either a good quality digital thermometer, or if a thermometer
is not available, a second sensor can be placed alongside
the one to be tested and the readings compared.
First measure the temperature using the thermometer and
then measure the resistance of the sensor at the control. The
wires from the sensor must not be connected to the control
while the test is performed. Using the chart below, estimate
the temperature measured by the sensor. The sensor and
thermometer readings should be close. If the test meter reads
a very high resistance, there may be a broken wire, a poor
wiring connection or a defective sensor. If the resistance is
very low, the wiring may be shorted, there may be moisture
in the sensor or the sensor may be defective. To test for
a defective sensor, measure the resistance directly at the
sensor location.
Do not apply voltage to a sensor at any time as damage
to the sensor may result.
Testing the Sensor Wiring
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
°F °C
°F °C °F °C °F °C
-50 -46 490,813 20 -7 46,218 90 32 7, 3 3 4 160 71 1,689
-45 -43 405,710 25 -4 39,913 95 35 6,532 165 74 1,538
-40 -40 336,606 30 -1 34,558 100 38 5,828 170 77 1,403
-35 -37 280,279 35 2 29,996 105 41 5,210 175 79 1,281
-30 -34 234,196 40 4 26,099 110 43 4,665 180 82 1,172
-25 -32 196,358 45 7 22,763 115 46 4,184 185 85 1,073
-20 -29 165,180 50 10 19,900 120 49 3,760 190 88 983
-15 -26 139,403 55 13 17,4 3 6 125 52 3,383 195 91 903
-10 -23 118,018 60 16 15 ,311 130 54 3,050 200 93 829
-5 -21 100,221 65 18 13,474 135 57 2,754 205 96 763
0 -18 85,362 70 21 11,883 140 60 2,490 210 99 703
5 -15 72,918 75 24 10,501 145 63 2,255 215 102 648
10 -12 62,465 80 27 9,299 150 66 2,045 220 104 598
15 -9 53,658 85 29 8,250 155 68 1,857 225 107 553
Bottom of
Enclosure 080
Universal
Sensor
Cable Tie
Sensor Well
Retaining
Clip
Universal
Sensor
© 2016 406_D - 05/16 10 of 48
Testing the Control Wiring
Testing the Power
-------------------------------
If the control display does not turn on, check the Input Power
wiring terminals using an electrical multimeter. The voltage
should measure between 21.6 to 26.4 V (ac). If the voltage
is below this range, measure the line voltage side of the
transformer. The voltage should measure between 103.5 to
126.5 V (ac).
Testing the Thermostats
------------------------
If the thermostat display turns on, this indicates that the
thermostat is operating correctly and there are no electrical
issues. In the event that the display is off, or the display is
cycling on and off, follow this procedure.
1. Remove the tN2 wires from the thermostat.
2. Use an electrical meter to measure DC voltage between
the tN2 terminals.
If the DC voltage is 0
V (dc) for 20 seconds, then there is an
open or short circuit in the tN2 wires. If the DC voltage is 0 V
(dc) for 10 seconds and then is 23 to 24 V (dc) for 5 seconds,
this indicates the wiring i
s correct.
3. Connect the thermostat to the tN2 wires from a zone on a
House Control, Wiring Center, or Zone Manager.
4. If the thermostat display is off, or is cycling on and off, move
the thermostat to the next available zone on the House
Control, Wiring Center, or Zone Manager.
If the thermostat display remains permanently on, there may
be a fault with the previously tried zone on the House Control,
Wiring Center, or Zone Manager.
If the thermostat display continues to be off, or is cycling on
and off, there may be a fault on the thermostat.
If a fault is suspected, contact your tekmar sales representative
for assistance.
User Test
----------------------------------------
The User Test is found in the Toolbox menu of the control.
Press the Menu button to access the Toolbox Menu. Press
the Item button to locate the User Test.
Start the test sequence by going to the User Test item and
pressing the ‘Up’ arrow button.
Pause the test sequence by pressing the Item button. To
advance to the next step, press the Item button again.
If the test sequence is paused for more than five minutes,
the control exits the entire test routine and returns to normal
operation.
To advance to a particular step, repeatedly press and release
the Item button to display the appropriate device.
User Test Sequence
Step 1
Zone 1 turns on for 10 seconds.
Step 2
Zone 2 turns on for 10 seconds.
Step 3
Zone 3 turns on for 10 seconds.
Step 4
Zone 4 turns on for 10 seconds.
Step 5
The Mix 1 device ramps up to 100% over 30 seconds
or according to the motor speed setting.
Step 6
The Mix 1 device ramps down to 0% over 30 seconds
or according to the motor speed setting.
Step 7
The mix system pump turns on for 10 seconds.
Step 8
The tank system pump turns on for 10 seconds.
Step 9
The O/B contacts are closed for 10 seconds.
Step 10
The HP loop pump turns on for 10 seconds.
Step 11
The HP loop pump turns on and the Y1 contacts are
closed for 10 seconds
Step 12
The HP loop pump turns on and the Y2 contacts are
closed for 10 seconds if HP TYPE = ROT.
The HP loop pump turns on and the Y1 and Y2
contacts are closed for 10 seconds if HP TYPE =
2STG.
Step 13
The Backup contacts are closed for 10 seconds if
BACKUP = AUX.
Step 14
The transfer pump turns on for 10 seconds if
BACKUP = XFER.
Step 15
The variable speed pump turns on for 10 seconds if
BACKUP = VAR.
Step 16
The DHW pump turns on for 10 seconds if
WATERTEMP = T+B or T+MB and DHW Mode ≠
OFF.
Step 17
The boil system pump turns on for 10 seconds if
WATERTEMP = T+B or T+MB.
Step 18
If WATERTEMP = T+B or T+MB The boil system
pump turns on, and the tN2 zones, transfer pump,
variable speed pump (20%), and tank pump turn on
if necessary.
If the Boil Type is 1 Stage, the backup relay is closed for 10
seconds and then opened.
If Boiler Type is modulating 0-10 or 4-20, the backup relay is
closed for 10 seconds and the modulating output operates
at 50 % [5 V (dc) or 12 mA].
Step 19
Control returns to normal operation.
Testing the Zone Output
------------------------
Activate the User Test sequence and pause at Step 1 by pressing
the Item button once Zone 1 turns on. Using an electrical meter,
measure the voltage between the zone valve and the common
(C) terminals. The voltage should measure between 21.6 V
(ac) and 26.4 V (ac). Repeat for Zones 2, 3, and 4.
Testing the Variable Speed Pump
---------------
Activate the User Test sequence and pause at Step 5 or Step
15 by pressing the Item button once the variable speed pump is
operating at 100%. Using an electrical meter, measure the voltage
between the variable speed pump and a neutral. The voltage
should measure between 103.5 V (ac) and 126.5 V (ac).
Testing the Mix System Pump
-------------------
Activate the User Test sequence and pause at Step 7 by
pressing the Item button once the mix system pump turns on.
Using an electrical meter, measure the voltage between the
mix system pump and a neutral. The voltage should measure
between 103.5 V (ac) and 126.5 V (ac).
Only qualified personnel should perform testing procedures. A licensed electrician is recommended.
11 of 48 © 2016 406_D - 05/16
Testing the Tank System Pump
------------------
Activate the User Test sequence and pause at Step 8 by
pressing the Item button once the tank system pump turns on.
Using an electrical meter, measure the voltage between the
tank system pump and a neutral. The voltage should measure
between 103.5 V (ac) and 126.5 V (ac).
Testing the O/B Contact
-------------------------
Activate the User Test sequence and pause at Step 9 by
pressing the Item button once the O/B contact turns on. Using
an electrical meter, measure for continuity between the O/B
and Rc1 terminals.
Testing the HP Loop Pump
----------------------
Activate the User Test sequence and pause at Step 10 by
pressing the Item button once the HP Loop pump turns on.
Using an electrical meter, measure the voltage between the
HP Loop pump and a neutral. The voltage should measure
between 103.5 V (ac) and 126.5 V (ac).
Testing the Heat Pump Stage 1 Contact
---------
Activate the User Test sequence and pause at Step 11 by
pressing the Item button once the Y1 contact turns on. Using
an electrical meter, measure for continuity between the Y1
and Rc1 terminals.
Testing the Heat Pump Stage 2 Contact
---------
Activate the User Test sequence and pause at Step 12 by
pressing the Item button once the Y2 contact turns on. Using
an electrical meter, measure for continuity between the Y2
and Rc2 terminals.
Testing the Backup Contact
---------------------
Activate the User Test sequence and pause at Step 13 or Step
18 by pressing the Item button once the boiler stage 1 turns
on. Using an electrical meter, measure for continuity over the
Backup terminals.
Testing the Transfer Pump
----------------------
Activate the User Test sequence and pause at Step 14 by
pressing the Item button once the Transfer pump turns on.
Using an electrical meter, measure the voltage between the
Transfer pump and a neutral. The voltage should measure
between 103.5 V (ac) and 126.5 V (ac).
Testing the DHW Pump
--------------------------
Activate the User Test sequence and pause at Step 16 by
pressing the Item button once the DHW pump turns on. Using
an electrical meter, measure the voltage between the DHW
pump and a neutral. The voltage should measure between
103.5 V (ac) and 126.5 V (ac).
Testing the Boiler System Pump
-----------------
Activate the User Test sequence and pause at Step 17 by
pressing the Item button once the boiler system pump turns
on. Using an electrical meter, measure the voltage between
the boiler system pump and a neutral. The voltage should
measure between 103.5 V (ac) and 126.5 V (ac).
Testing the Boiler Modulating Output
------------
This test applies for modulating boilers only.
Active the User Test sequence and pause at Step 18 by
pressing the Item button once the boiler stage 1 turns on.
Using an electrical meter, measure for either a 5 V (dc) or 12
mA signal. The Boil Type setting selects whether the signal
is V (dc) or mA.
Testing the DHW Call
----------------------------
Remove all wires from the DHW Call terminals. The control
display should show no DHW Call. Reconnect wires. Then
apply either a short circuit or 24 V (ac) over the DHW Call
terminals. The control should now show a DHW Call.
Testing the Setpoint Call
------------------------
Remove all wires from the Setpoint Call terminals. The
control display should show no Setpoint Call. Reconnect
wires. Then apply either a short circuit or 24 V (ac) over
the Setpoint Call terminals. The control should now show
a Setpoint Call.
The control has a function called Max Heat. In this mode, the
control turns on and operates the system up to the maximum
set temperatures as long as there is a call for heat. Use this
mode to run the circulators during system start-up and com-
missioning, and purging air from the piping. This function is
useful when drying sheet rock and paint in the building.
To enable Max Heat, enter the Toolbox Menu and find Max
Heat. Use the up arrow to select ‘On’.
When a space heating call is present, the heat pump and
backup will run to maintain the target at the Design temperature.
(One can purge the system using this test and leave the heat
pump and backup un-powered. This will prevent heat from
entering the system during the purge.)
When a DHW Call or Setpoint Call is present, the boiler
will operate at the DHW exchange or Setpoint temperature
settings.
WWSD and DHW Priority are disabled during Max Heat
mode.
Cooling is disabled during Max Heat mode.
When Max Heat is on the display will show ‘Max Heat
Test .
Max Heat will automatically turn off after 24 hours.
To cancel Max Heat, go to Max Heat in the Toolbox menu and
use the down arrow to select ‘Off.
Max Heat
© 2016 406_D - 05/16 12 of 48
Mechanical A406-1
Applications
Description: The House Control 406 operates a two stage air source heat pump in heating or cooling mode to supply an
outdoor reset water temperature to 4 on board tank temperature zones. Additional zones can be added using the Tank tN4 and
C Expansion terminals. Domestic Hot Water pre-heat is achieved by maintaining the DHW sensor S5 in the preheat storage
tank at an adjustable temperature, 90°F (32°C) default, using the DHW pump P6. The heat pump will target a water temperature
20°F (11°C) higher than the preheat tank target at the return sensor S2, and is limited by the HP RETURN MAX setting in the
Adjust Menu. An electric element in the system storage tank is switched on through an isolation relay with the backup relay on
the 406 to provide backup heat to maintain the Tank Sensor S4 at its target temperature.
Tank zones can have fan-coils, air handling units, chilled beams, or chilled panels as their terminal units depending on the type
of tekmarNet
®
thermostat selected.
Expansion
Tank
Electric
Element
Backup
Freeze
Protection
Device
Electric
Water
Heater
S1
S4
S2
tekmarNet
®
2 Thermostats
P4
P2
Z1 Z2 Z3 Z4
Coaxial
Heat Exchanger
Cold In
Two Stage
Air to Water
Heat Pump
Preheat
Storage Tank
P6
S5
DHW Out
WATER TEMP T (tank)
BACKUP AUX (auxiliary)
HP LOOP INT (intermittent)
HP TYPE 2STG (2-stage)
DHW MODE 5 (DHW preheat)
Application Settings
P2 HP Loop Pump
P4 Tank System Pump
P6 DHW Pump
S1 Outdoor Sensor
S2 HP Return Sensor
S4 Tank Sensor
S5 DHW Sensor
Legend
406
13 of 48 © 2016 406_D - 05/16
HP Sys
115 V (ac)
NLG
to pump grounds
N
L
L
Back of House Control 406
R
C
L
N
Tank Sys
Mix Sys PumpTank Sys Pump
DHW Pump
Transfer Pump
Boil Sys Pump
HP Loop Pmp
Pump
Power (L)
Pump
Power (L)
Variable
Speed Pump
3
4
6
5
7
2
1
8
tN2tN2tN2tN2tN2tN2tN2tN2
(blue)
(red)
(black)
(black)
(black)
(red)
(black)
(black)
(black)
Y2 OY1R
Menu
House Control 406
Item
+
Tank ComBoilHPRtOutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2 tN2tN2 tN2 tN2 tN2tN2 tN2
Rc1Y1O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA Boil / Mix Tank
Rc2 Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Element
Stor. Tank
A1 A2
L1
L2
DHW
115 V (ac)
NGL
to pump grounds
N
Electrical A406-1
Outdoor
Sensor
(S1)
tekmarNet
®
2 Thermostats
24 V (ac)
Transformer 009
Tank Sensor (S4)
Heat Pump
Return Sensor (S2)
(P4)
(P2)
(Z1) (Z2) (Z3) (Z4)
240 V (ac)
Electric Element
003 Relay
Two Stage
Air to Water
Heat Pump
DHW Sensor (S5)
(P6)
© 2016 406_D - 05/16 14 of 48
WATER TEMP T+MB (tank + mix + boiler)
ZONES 1-4 MIX
BACKUP XFER (transfer pump)
BOIL TYPE 1STG (1 stage)
HP LOOP ON
HP TYPE ROT (rotate)
DHW MODE OFF
Expansion
Tank
Freeze
Protection
Device
Application Settings
Mechanical A406-2
S1
S2
S5S4
tekmarNet
®
2 ThermostatstekmarNet
®
2 Thermostats
P1
P2
Z1 Z2 Z3 Z4
P5
Z5 Z6 Z7 Z8
Backup:
Electric Boiler
2 Air to Water
Heat Pumps
P7
Description: The House Control 406 operates two air source heat pumps in heating or cooling mode to supply an outdoor reset
water temperature to 4 on board mix temperature zones and 4 tank zones connected to the Tank expansion terminals with a
Wiring Center 314. An electric boiler supplies backup heat using the Backup relay and the Transfer Pump P7.
By setting HP LOOP to ON, the HP Loop Pump P2 will operate whenever there is a call on the tank or mix bus, or when the
transfer pump is on to ensure flow through the storage tank while heating or cooling.
Mixing is useful to separate the hot and cold water temperatures required for fancoils from the warm and cool temperatures
required for radiant floor heating and cooling. The Variable Speed Pump P1 is able to mix the water temperature down for
heating or mix the water temperature up above the dewpoint for floor cooling.
2-Port
Storage tank
Coaxial
Heat Exchanger
S3
314
P1 Variable Speed Pump
P2 HP Loop Pump
P5 Mix System Pump
P7 Transfer Pump
S1 Outdoor Sensor
S2 HP Return Sensor
S3 Boiler Sensor
S4 Tank Sensor
S5 Mix Sensor
Legend
406
15 of 48 © 2016 406_D - 05/16
HP Sys
Mix Sys
Transfer
Variable
Speed
115 V (ac)
N1L1 G
115 V (ac)
N2GL2
to pump grounds
to pump grounds
N
N
L
L
Back of House Control 406
Expansion
tN4 Tank
CtN4
Mix Sys PumpTank Sys Pump
DHW Pump
Transfer Pump
Boil Sys Pump
HP Loop Pmp
Pump
Power (L)
Pump
Power (L)
Variable
Speed Pump
tN2tN2tN2tN2tN2tN2tN2tN2
T
T
(blue)
(red)
(black)
(black)
(black)
(red)
(black)
(black)
(black)
R
C
L
N
3
4
6
5
7
2
1
8
OCYR
OCYR
Transfer
314
Menu
House Control 406
Item
+
Tank ComBoilHPRtOutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2tN2 tN2 tN2 tN2 tN2 tN2 tN2
Rc1Y1O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA
Boil / Mix Tank
Rc2Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Electrical A406-2
24 V (ac)
Transformer 009
Heat Pump Return
Sensor (S2)
Tank Sensor (S4)
Mix Sensor (S5)
tekmarNet
®
2 Thermostats
Outdoor
Sensor
(S1)
Electric Boiler
Backup
(P1)
(P2)
(P5)
003 Relay
(Z1) (Z2) (Z3) (Z4)
Two
Air to Water
Heat Pumps
Boiler Sensor (S4)
(P7)
© 2016 406_D - 05/16 16 of 48
Geo Field
Expansion
Tank
Mechanical A406-3
S1
S2
S4
P3
tekmarNet
®
2 Thermostats
tekmarNet
®
2 Thermostats
P7
P2
Z1 Z2 Z3 Z4
P4
Z5 Z6 Z7 Z8
Backup:
Mod-Con
Boiler
P6
S3
DHW
Setpoint
Description: The House Control 406 operates a water source heat pump in heating or cooling mode to supply an outdoor reset
water temperature to 4 on board tank temperature zones. The 406 also operates a modulating condensing boiler to supply an
outdoor reset water temperature to 4 boiler zones connected to the Boil expansion terminals with a Wiring Center 313. The
boiler supplies backup heat to the tank loop using the transfer pump P7.
To allow the heat pump to operate for some amount of time before the transfer pump starts adding heat to the storage tank,
use the backup delay setting in the adjust menu. This ensures the heat pump is being used to its full potential before backup
is allowed. Placing the Transfer Pump P7 on the upstream side of the storage tank allows for hot water temperatures from the
boiler loop to be buffered by the storage tank to prevent sending hot water out to the tank temperature zones.
Tank zones can have fan-coils, air handling units, chilled beams, or chilled panels as their terminal units depending on the type
of tekmarNet
®
thermostat selected.
Water-to Water
Heat Pump
WATER TEMP T+B (tank + boiler)
ZONES 1-4 TANK
BACKUP XFER (transfer pump)
BOIL TYPE 0-10
HP LOOP INT
HP TYPE 1STG
DHW MODE 2
Application Settings
P2 HP Loop Pump
P3 Boiler System Pump
P4 Tank System Pump
P6 DHW Pump
P7 Transfer Pump
S1 Outdoor Sensor
S2 HP Return Sensor
S3 Boiler Sensor
S4 Tank Sensor
S5 DHW Sensor
Legend
S5
406
313
17 of 48 © 2016 406_D - 05/16
Boil Sys
HP Sys
DHW
Transfer
115 V (ac)
NLG
115 V (ac)
NGL
to pump grounds
to pump grounds
N
N
L
L
Back of House Control 406
R
C
L
N
Expansion
tN4 Boil
CtN4
Tank Sys
Mix Sys PumpTank Sys Pump
DHW Pump
Transfer Pump
Boil Sys Pump
HP Loop Pmp
Pump
Power (L)
Pump
Power (L)
Variable
Speed Pump
tN2tN2tN2tN2tN2tN2tN2tN2
RYO
+TT
-
(blue)
(red)
(black)
(black)
(black)
(red)
(black)
(black)
(black)
313
Menu
House Control 406
Item
+
Tank ComBoilHPRtOutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2 tN2tN2 tN2 tN2 tN2tN2 tN2
Rc1Y1O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA Boil / Mix Tank
Rc2Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Electrical A406-3
24 V (ac)
Transformer 009
Heat Pump
Return Sensor (S2)
Tank Sensor (S4)
tekmarNet
®
2 Thermostats
Outdoor
Sensor
(S1)
(P4)
(P6)
(Z1) (Z2) (Z3) (Z4)
Boiler Sensor (S3)
Setpoint Call
(P3)
(P2) (P7)
Mod Con
Boiler
Water-to Water
Heat Pump
DHW Sensor (S5)
© 2016 406_D - 05/16 18 of 48
Description: The House Control 406 operates a two stage water source heat pump in heating or cooling mode to supply an
outdoor reset water temperature to 4 on board tank temperature zones. The 406 also operates an on/off boiler to supply an
outdoor reset water temperature to 4 boiler zones connected to the Boil expansion terminals with a Wiring Center 314. The
boiler supplies backup heat to the tank loop using the variable speed pump P1.
To allow the heat pump to operate for some amount of time before the variable speed pump starts adding heat to the tank loop,
use the backup delay setting in the adjust menu. This ensures the heat pump is being used to its full potential before backup is
allowed. A non-condensing boiler may be used since P1 provides boiler return protection, preventing flue gas condensation.
Tank zones can have fan-coils, air handling units, chilled beams, or chilled panels as their terminal units depending on the type
of tekmarNet thermostat selected.
Expansion
Tank
Geo Field
Mechanical A406-4
S1
S2
S4
P3
tekmarNet
®
2 ThermostatstekmarNet
®
2 Thermostats
P2
Z1 Z2 Z3 Z4
P4
Z5 Z6 Z7 Z8
Backup:
On/Off
Boiler
P6
S3
DHW
P1
S5
Two Stage
Water to Water
Heat Pump
WATER TEMP T+B (tank + boiler)
ZONES 1-4 TANK
BACKUP VAR (variable speed pump)
BOIL TYPE 1STG (1 stage)
HP LOOP INT
HP TYPE 2STG
DHW MODE 2
Application Settings
P1 Variable Speed Pump
P2 HP Loop Pump
P3 Boiler System Pump
P4 Tank System Pump
P6 DHW Pump
S1 Outdoor Sensor
S2 HP Return Sensor
S3 Boiler Sensor
S4 Tank Sensor
S5 DHW Sensor
Legend
406
314
19 of 48 © 2016 406_D - 05/16
Boil Sys
HP Sys
DHW
115 V (ac)
N1L1 G
115 V (ac)
N2GL2
to pump grounds
to pump grounds
N
N
L
L
Back of House Control 406
R
C
L
N
Expansion
tN4 Boil
CtN4
Tank Sys
Mix Sys PumpTank Sys Pump
DHW Pump
Transfer Pump
Boil Sys Pump
HP Loop Pmp
Pump
Power (L)
Pump
Power (L)
Variable
Speed Pump
tN2tN2tN2tN2tN2tN2tN2tN2
Y2 OY1R
(blue)
(red)
(black)
(black)
(black)
(red)
(black)
(black)
(black)
Variable
Speed
314
T
T
Menu
House Control 406
Item
+
Tank ComBoilHPRtOutCom
Zone 1
H8009B
Zone 2 Zone 3 Zone 4
tN2tN2 tN2 tN2 tN2 tN2 tN2 tN2
Rc1Y1O/B
Sensors - No Power
No Power
Call Call
Mix/DHW
tN4 tN4CC
Mod dc/mA
Boil / Mix Tank
Rc2Y2
Setpoint DHW
RC
Input Power
Backup
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Electrical A406-4
24 V (ac)
Transformer 009
Heat Pump Return
Sensor (S2)
Tank Sensor (S4)
tekmarNet
®
2 Thermostats
Outdoor
Sensor
(S1)
(P4)
(P6)
(Z1) (Z2) (Z3) (Z4)
Boiler Sensor (S3)
(P3)
(P2)
On/Off
Boiler
Two Stage
Water to Water
Heat Pump
(P1)
DHW Sensor (S5)
© 2016 406_D - 05/16 20 of 48
Description: The House Control 406 operates two water source heat pumps in heating or cooling mode to supply an outdoor
reset water temperature to 4 on board mix temperature zones and 4 tank zones connected to the Tank expansion terminals
with a Wiring Center 313. The 406 also operates a modulating condensing boiler to supply an outdoor reset water temperature
to 4 boiler zones connected to the Boil expansion terminals with a Wiring Center 314. The boiler supplies backup heat to the
tank loop using the transfer pump P7.
Mixing is useful to separate the hot and cold water temperatures required for fancoils from the warm and cool temperatures
required for radiant floor heating and cooling. The Variable Speed Pump P1 is able to mix the water temperature down for
heating or mix the water temperature up above the dewpoint for floor cooling.
Expansion
Tank
Mechanical A406-5
S1
S2
S5
P3
tekmarNet
®
2 Thermostats
tekmarNet
®
2 Thermostats
P2
Z1 Z2 Z3 Z4
P5
Z9 Z10 Z11 Z12
Backup:
Mod Con
Boiler
P6
S3
A1
P1
Z5 Z6 Z7 Z8
P7
P4
S4
tekmarNet
®
2 Thermostats
Two
Water to Water
Heat Pumps
IMPORTANT
When a three water temperature application is selected (WATER TEMP = T+MB), either the Mix or Boiler bus is limited to
the 4 tN2 on board thermostats, and the gateway controls 482 and 483 are unable to communicate to the four on-board tN2
zones on the House Control 406.
WATER TEMP T+MB (tank + mix + boiler)
ZONES 1-4 MIX
BACKUP XFER (transfer pump)
BOIL TYPE 0-10
HP LOOP INT
HP TYPE ROT (rotate)
DHW MODE 4
Application Settings
P1 Variable Speed Pump
P2 HP Loop Pump
P3 Boiler System Pump
P4 Tank System Pump
P5 Mix System Pump
P6 DHW Pump
P7 Transfer Pump
S1 Outdoor Sensor
S2 HP Return Sensor
S3 Boiler Sensor
S4 Tank Sensor
Legend
314
406
313
S5 Mix Sensor
A1 DHW Aquastat
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

tekmar 406 Installation guide

Category
Heat pumps
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI