ABB V-Contact VSC 12/F Installation And Service Instructions Manual

Type
Installation And Service Instructions Manual
Medium voltage products
V-Contact VSC
Installation and service instructions
7.2/12 kV - 400 A
For your safety! 1
I. Introduction 2
II. Programme for environmental protection 2
III. Application of the standards for X-ray emission 3
IV. Safety information 3
V. Qualified personnel 3
VI. Interventions in the field 3
1. Description 4
1.1. “MAC” magnetic drive 4
1.2. Versions available 5
1.3. Characteristics 6
1.4. Weights and overall dimensions 6
1.5. Performances 8
1.6. Contactor auxiliary contacts 8
1.7. Compliance with Standards 9
1.8. Protection against short-circuit 9
2. Checking on receipt 10
3. Handling 11
3.1. Handling and lifting using a crane 12
4. Storage 13
5. Installation 14
5.1. General 14
5.2. Installation and operating conditions 14
5.3. Normal conditions 14
5.4. Special conditions 14
5.5. Overall dimensions 15
5.6. Assembly and making the connections 21
5.7. Description of the closing and opening operations 30
5.8. Manual emergency opening operation 33
6. Putting into service 34
6.1. General procedures 34
6.2. Racking the VSC/P contactor in and out 35
7. Maintenance 36
7.1. General 36
7.2. Handling the MAC-R2 electronic card 36
7.3. Inspection 37
7.4. Servicing 38
7.5. Servicing following a short-circuit or overload 38
7.6. Repairs 38
7.7. Instructions for dismantling or replacing fuses 39
7.8. Replacement of the contactor fuses 40
7.9. Mounting and dismantling the short-circuit busbar 43
7.10. Putting the contactor back into service 43
7.11. Checking the degree of vacuum of the interrupter 43
8. Spare parts and accessories 44
8.1. List of spare parts 44
9. Product quality and environmental protection 44
This instruction booklet refers to the following models:
VSC/F-VSC/FN-VSC/P-VSC/PG-VSC/PN-VSC/PNG
VSC-S/F-VSC-S/G-VSC-S/PG-VSC-S/PNG
NEPSI.COM - Northeast Power Systems. Inc.
NEPSI.COM - Northeast Power Systems. Inc.
1
For your safety!
• Makesurethattheinstallationroom(spaces,divisionsand
ambient) is suitable for the electrical apparatus.
• Checkthatalltheinstallation,puttingintoserviceand
maintenance operations are carried out by qualified
personnel with suitable knowledge of the apparatus.
• Makesurethatthestandardandlegalprescriptions
arecompliedwithduringinstallation,operationand
maintenance,sothatinstallationsaccordingtotherules
of good working practice and safety in the work place are
constructed.
• Strictlyfollowtheinformationgiveninthisinstruction
manual.
• Checkthattheratedperformanceoftheapparatusisnot
exceeded during service.
• Checkthatthepersonneloperatingtheapparatushave
this instruction manual to hand as well as the necessary
information for correct intervention.
• Payspecialattentiontothedangernotesindicatedinthe
manual by the following symbol:
Responsible behaviour safeguards your own
and others’ safety!
For any requests, please contact the ABB
Assistance Service.
NEPSI.COM - Northeast Power Systems. Inc.
2
I. Introduction
The instructions in this manual refer to the fixed and withdrawable
versions of the VSC series of contactors. For correct use of the
product,pleasereaditcarefully.
For the electrical and construction characteristics and the overall
dimensionsoftheV-ContactVSCcontactors,pleasealsosee
technical catalogue 1VCP000165.
Likealltheapparatuswemanufacture,theV-Contactvacuum
contactors are designed for different installation configurations.
Furthermore,thisapparatusallowsfurthertechnicaland
constructionmodications(atthecustomer’srequest)toadaptto
specialinstallationrequirements.Consequently,thismanualmay
not provide information concerning special configurations of the
apparatus.
Apartfromthismanual,itisthereforealwaysnecessarytoconsult
thelatesttechnicaldocumentation(circuitandwiringdiagrams,
assemblyandinstallationdrawings,anyprotectioncoordination
studies,etc.),especiallyregardinganyvariantsrequestedin
relation to the standardised configurations.
Only use original spare parts for maintenance operations. The use
of non-original spare parts can cause hazardous malfunctions
and the apparatus warranty will no longer be valid.
Please refer to the technical sheets of the Kits for correct
assembly of the accessories and/or spare parts. For further
information,alsoseethe1VCP000165technicalcatalogueofthe
contactor and the spare parts catalogue.
This manual and all the enclosed drawings must be considered
an integral part of the apparatus. They must be easily to hand at
all times for revision and reference.
Theseinstructionsdonotintendtocoverallthedetails,
configurationsorvariantsoftheapparatus,storageor
installation.Forthisreason,theinformationgivenbelowmay
sometimes not contain the instructions regarding special
configurations. This does not relieve the user from their
responsibility for using good technical working practices
inapplication,installation,serviceandmaintenanceofthe
apparatuspurchased.Shouldfurtherinformationberequired,
please contact ABB.
WARNING
Dangerous voltages. Risk of death, serious
injury to people, damage to the apparatus or
other objects.
Before carrying out any maintenance
operations, turn the power supply off and
earth the apparatus.
Read and understand this instruction manual
before installation, service or maintenance of
the apparatus.
Maintenance must only be carried out by
skilled personnel.
The use of unauthorized spare parts for
repairs to the apparatus, modification of the
apparatus itself, or tampering by unskilled
personnel creates hazardous conditions
which may cause death or serious injury
to people, or damage to the apparatus or
other objects. Carefully follow all the safety
instructions given in this manual.
II. Environmental protection
programme
The V-Contact VSC vacuum contactors are manufactured
inaccordancewiththeISO14000Standards(Guidelines
for environmental management). The production processes
are carried out in compliance with the Standards for
environmental protection in terms of reduction in energy
consumption as well as in raw materials and production of
waste materials.
All this is thanks to the medium voltage apparatus
manufacturing facility environmental management system.
NEPSI.COM - Northeast Power Systems. Inc.
3
III. Application of the X-ray emission
Standards
One of the physical properties of vacuum insulation is the
possibility of X-ray emission when the interrupter contacts
are open. The tests carried out at the PTB laboratories
(Physikalisch-TechnischeBundesanstalt,inBrunswick-
Germany) show that local emission at a distance of 10 cm
fromtheinterrupterorpolesurface,doesnotexceed
1 µSv/h. It follows that:
– at the rated service voltage the use of vacuum interrupters
is absolutely safe;
–applicationofthewithstandvoltageatpowerfrequency,
accordingtotheIEC62271-1Standard,issafe;
application of a voltage higher than the withstand voltage
atpowerfrequencyorofadirectcurrenttestvoltage,
specifiedintheIECStandard,cannotbeused;
–limitationoftheabove-mentionedlocalphenomena,on
interrupterswithopencontacts,dependsonkeepingthe
specified distance between the contacts. This condition is
intrinsically guaranteed by correct operation of the drive and
by transmission system adjustments.
IV. Safety information
Alltheinstallation,puttingintoservice,runningand
maintenance operations must be carried out by suitably
qualified personnel with in-depth knowledge of the apparatus.
Make sure that the personnel working on the apparatus
have this manual to hand and all the information required for
correct intervention.
Strictly follow the information given in this instruction manual.
Makesurethatduringtheinstallation,serviceand
maintenance stages the standard and legal requirements
for constructing the installations in accordance with the
regulations for safety in the workplace are respected.
Check that the rated performance of the apparatus is not
exceeded during service.
V. Qualified personnel
Forthepurposesofthismanualandtheproductratingplates,
a qualified person is intended as a person who:
1) carefully reads the instruction manual all the way through.
2)hasin-depthknowledgeoftheinstallation,construction
and service of the apparatus and knows about the risks
connected with any interventions.
3)isqualifiedandauthorisedtoenergise,de-energise,earth
and identify the circuits according to the safety procedures
and the local regulations in force.
4) is qualified and authorised to put this apparatus into
service,andtocarryoutmaintenanceandrepairoperations
on it.
5)istrainedincorrectuseofprotectiveequipment,suchas
rubbergloves,hardhats,protectivegoggles,faceshields,
flameproofclothing,etc.accordingtothesafetyprocedures
and the local regulations in force.
6) is trained in first-aid procedures.
VI. Interventions in the field
ABB can provide competent and well-trained personnel for assis-
tance in the field to give technical guidance and consultancy
regardinginstallation,fullservicing,repairandmaintenanceof
apparatus.
NEPSI.COM - Northeast Power Systems. Inc.
4
1. Description
The medium voltage V-Contact VSC contactors are pieces
of apparatus suitable for operating in alternating current and
are normally used to control users requiring a high number of
hourly operations.
The basic contactors consist of:
•mouldedpolyesterresinmonobloccontainingthevacuum
interrupters
•bistableelectromagnetactuator
•multi-voltagefeeders
•auxiliarycontacts
•mechanicalstatusindicator(open/closed)
•manualemergencyopeningdevice.
Apartfromwhatisspecifiedforthefixedcontactors,the
withdrawable contactors also consist of:
•fuseholderspresetforDINorBSfuses(accordingtothe
customer’srequirements)
•automaticopeningdeviceforinterventionofevenasingle
fuse
•truck
•lockwhichpreventsclosingduringtheracking-in/out
operation.
The V-Contact VSC contactor introduces the drive with
permanentmagnets-alreadywidelyused,experimented
and appreciated in medium voltage circuit-breakers - into the
worldwide panorama of medium voltage contactors.
The experience acquired by ABB in the field of medium
voltage circuit-breakers fitted with drives with “MABS”
permanentmagnets,hasmadeitpossibletodevelopan
optimisedversionoftheactuator(BistableMACdrive)for
medium voltage contactors.
The drive is operated by means of an electronic feeder able
to cover all the power supply voltages required by the major
international Standards.
Fig. A
Magnetic circuit in the closed position.
Fig. B
Magnetic circuit with opening coil supplied.
Fig. C
Magnetic circuit in the open position.
1.1. “MAC” magnetic drive
Based on the experience gained in the field of circuit-breakers
withmagneticdrive,ABBhasimplementedthistechnologyin
the field of contactors.
The magnetic drive adapts perfectly to this type of apparatus
thanks to its precise and linear travel.
This means that a simple and direct axial transmission of the
movement to the moving contacts of the vacuum interrupter
canberealised,withbothelectricalandmechanicalbenefits.
Thedrive,whichisofbistabletype,isfittedwithanopening
and a closing coil.
The two coils - individually energised - allow the drive core to
be moved from one of the two stable positions to the other.
The drive shaft is solid with an iron core which is immersed
and held in position in a field generated by two permanent
magnets(fig.A).
Energising the coil opposite to the magnetic latching position
(fig.A)ofthecore,themagneticfield(fig.B)isgenerated,
which attracts and moves the core into the opposite position
(fig.C).
Every opening and closing operation creates a magnetic
field concordant with the one generated by the permanent
magnets,withtheadvantage,duringservice,ofkeeping
the intensity of the field itself constant as the number of
operations carried out increases.
The energy needed for operation is not supplied directly
bytheauxiliarypowersupply,butisalways“stored”inthe
capacitorwhichactsasanenergyaccumulator,andtherefore
operationalwaystakesplacewithconstantspeedsandtimes,
regardless of the divergence of the power supply voltage from
the rated value.
NEPSI.COM - Northeast Power Systems. Inc.
5
The auxiliary power supply only has the aim of keeping the
capacitor charged.
Consumption is therefore minimal.
The power required by the electronic device is indicated in the table below:
Power supply voltage
Starting(
1
) After closing After opening
Continuous power
consumption
Inrush for
2 ms
Inrush for
6 sec
Inrush for
1.2 sec
Inrush for
1.2 sec
24...60 V cc
110...250 V cc
42A(
2
) 35 W 25 W 30 W 5 W
110...250 V ac
SupplyfromvoltagetransformerorfromUPS(Uninterrupted
Power System) not available.
Use the ABB S282UC-C3 thermal-magnetic circuit-breaker or
an equivalent type to protect the secondary circuits.
Afterpowering,theelectronicboardtakes15seconds
to perform self-diagnosis and then prepares for normal
operation,dependingontheconfiguration.Donotoperatethe
contactorduringthisphase.ContactDO1willremainopen,
signal “not ready” and will only close after self-diagnosis has
terminated(“ready”state).
Careful selection of the components and a precise design
maketheelectronicmulti-voltagefeederextremelyreliable,
unaffected by electromagnetic interference generated by the
surrounding environment and free of any emissions which may
affect other apparatus placed in the vicinity.
These characteristics have made it possible for the V-Contact
VSC contactors to pass the electromagnetic compatibility
tests(EMC).
1.2. Versions available
The V-Contact VSC are available in:
fixed version without fuseholder
fixed versions with fuseholder: VSC/F e VSC/FN.
four withdrawable versions with fuseholder:
-VSC/P(IEC)andVSC/PGorVSC-S/PG(IEC/GB-DL)
withdrawableversionsforUniGear,PowerCube,CBEand
PowerBloc with manual or motorized truck
-VSC/PN(IEC)andVSC/PGorVSC-S/PNG(IEC/GB-DL)
both versions withdrawable for UniGear MCC with manual
truck.
(1)Thisvaluereferstoadischargedcapacitor.
(2)Thevaluedropsto8Aforvoltagevaluesbetween24...30V
NEPSI.COM - Northeast Power Systems. Inc.
6
1.4. Weights and overall dimensions
Contactor VSC7
VSC12
VSC-S/G
VSC7/F VSC7/FN
VSC12/F
VSC-S/F
VSC7/P
VSC12/P - VSC12/PG
VSC-S/PG
VSC7/PN VSC7/PNG VSC12/PN
VSC12/PNG
VSC-S/PNG
Weight [Kg] 23 23 35
(1)
35
(1)
35
(1)
52
(1)
52
(1)
45
(1)
45
(1)
45
(1)
45
(1)
Overall
dimensions
[mm] H 371 424 494 598 532
636 636 653 653 653 653
[mm] W 350 350 466 466 466 531 531 350 350 350 350
[mm] D
215 215 622 623 702 657 657 673 673 673 673
(1)Withoutfuses
H
D
W
1.3. Characteristics
Contactor
Reference
IEC 62271-106
VSC7
VSC7/F (
1
)
VSC7/P (
1
)
VSC7/PN (
1
)
VSC7/FN
VSC12
VSC12/F (
1
)
VSC12/P (
1
)
VSC12/PN (
1
)
Reference VSC7/PNG (
1
) VSC12/PNG (
1
) VSC-S/G
VSC-S/F (
1
)
VSC-S/PG (
1
)
VSC-S/PNG (
1
)
GB/T
14808-2001
DL/T
593-2006
Rated voltage [kV] 4.1 7.2 12 4.1 7.2 12 12
Rated insulation voltage
Withstand voltage at 50 Hz [kV]
6.2 23 28 6.2
32 42 28(
3
)
Impulse withstand voltage
[kVbil] 6.2 60 75
6.2 60 75 75
Rated frequency [Hz] 4.3 50-60 50-60 4.3 50-60 50-60 50-60
Rated service current [A] 4.101
400 400 4.101 400 400 250
Short-time withstand current
Short-time withstand current for 1 s [A] 6.6 6,000 6,000 6,000 600
Short-time withstand current for 2 s [A] 6.6 4,000 4,000
Short-time withstand current for 4 s [A]
4,000 4,000
Short-time withstand current for 30 s [A] 6.6 2,500 2,500 6.6 2,500 2,500 2,500
Rated peak current [kA] 6.6 15 15 6.6 15 15 15
Rated values
Operations/hour(SCO-DCO) [Nr.] 4.102.4 1.200 1,200 4.102.2 1,200 1,200 1,200
Rated voltage of the voltage characteristics in category of use
(CategoryAC4)100closingoperations [kA] 6.102.4 4,000 4,000 6.102.4 4,000 4,000
(CategoryAC4)25openingoperations [kA] 6.102.5 4,000 4,000 6.102.5 4,000 4,000
Switching devices and auxiliary circuits
4.8,4.9
4.8,4.9
Feeder 1 24÷60 V dc basic
Feeder 2 24÷60 V dc full option
Feeder 3 110÷250 V dc/ac basic
Feeder 4 110÷250 V dc/ac full option
Normal current [A] 6.4.6.5 400 400 6.4,6.5 400 400 400
Mechanical life [Nr.] 6.101 1,000,000(
2
) 1,000,000(
2
) 6.101 1,000,000(
2
) 1,000,000(
2
) 200,000
Short-circuitbreakingcapacity(O-3min-CO-3min-CO) [A] 6.104 5,000 5,000 6.104 5,000 5,000 -
Short-circuitmakingcapacity(O-3min-CO-3min-CO) [A] 6.104 13,000 13,000 6.104 13,000 13,000 -
Opening time [ms] 35...60 35...60 35...60 35...60 35...60
Closing time [ms] 60...90 60...90 60...90 60...90 60...90
Tropicalisation IEC 721-2-1
(1)Itispossibletocombinecurrentlimitingfuseswithbreakingcapacityupto50kA(IEC62271-106-4.107)-Damageclassification“C”(IEC62271-106-4.107.3).
(2)Withreplacementofauxiliarycontactsevery250,000closing-openingoperations.
(3)42kVforfixedversionsandindedicatedUnigearswitchgear
NEPSI.COM - Northeast Power Systems. Inc.
7
1.4. Weights and overall dimensions
Contactor VSC7
VSC12
VSC-S/G
VSC7/F VSC7/FN
VSC12/F
VSC-S/F
VSC7/P
VSC12/P - VSC12/PG
VSC-S/PG
VSC7/PN VSC7/PNG VSC12/PN
VSC12/PNG
VSC-S/PNG
Weight [Kg] 23 23 35
(1)
35
(1)
35
(1)
52
(1)
52
(1)
45
(1)
45
(1)
45
(1)
45
(1)
Overall
dimensions
[mm] H 371 424 494 598 532
636 636 653 653 653 653
[mm] W 350 350 466 466 466 531 531 350 350 350 350
[mm] D
215 215 622 623 702 657 657 673 673 673 673
(1)Withoutfuses
1.3. Characteristics
Contactor
Reference
IEC 62271-106
VSC7
VSC7/F (
1
)
VSC7/P (
1
)
VSC7/PN (
1
)
VSC7/FN
VSC12
VSC12/F (
1
)
VSC12/P (
1
)
VSC12/PN (
1
)
Reference VSC7/PNG (
1
) VSC12/PNG (
1
) VSC-S/G
VSC-S/F (
1
)
VSC-S/PG (
1
)
VSC-S/PNG (
1
)
GB/T
14808-2001
DL/T
593-2006
Rated voltage [kV] 4.1 7.2 12 4.1 7.2 12 12
Rated insulation voltage
Withstand voltage at 50 Hz [kV]
6.2 23 28 6.2
32 42 28(
3
)
Impulse withstand voltage
[kVbil] 6.2 60 75
6.2 60 75 75
Rated frequency [Hz] 4.3 50-60 50-60 4.3 50-60 50-60 50-60
Rated service current [A] 4.101
400 400 4.101 400 400 250
Short-time withstand current
Short-time withstand current for 1 s [A] 6.6 6,000 6,000 6,000 600
Short-time withstand current for 2 s [A] 6.6 4,000 4,000
Short-time withstand current for 4 s [A]
4,000 4,000
Short-time withstand current for 30 s [A] 6.6 2,500 2,500 6.6 2,500 2,500 2,500
Rated peak current [kA] 6.6 15 15 6.6 15 15 15
Rated values
Operations/hour(SCO-DCO) [Nr.] 4.102.4 1.200 1,200 4.102.2 1,200 1,200 1,200
Rated voltage of the voltage characteristics in category of use
(CategoryAC4)100closingoperations [kA] 6.102.4 4,000 4,000 6.102.4 4,000 4,000
(CategoryAC4)25openingoperations [kA] 6.102.5 4,000 4,000 6.102.5 4,000 4,000
Switching devices and auxiliary circuits
4.8,4.9
4.8,4.9
Feeder 1 24÷60 V dc basic
Feeder 2 24÷60 V dc full option
Feeder 3 110÷250 V dc/ac basic
Feeder 4 110÷250 V dc/ac full option
Normal current [A] 6.4.6.5 400 400 6.4,6.5 400 400 400
Mechanical life [Nr.] 6.101 1,000,000(
2
) 1,000,000(
2
) 6.101 1,000,000(
2
) 1,000,000(
2
) 200,000
Short-circuitbreakingcapacity(O-3min-CO-3min-CO) [A] 6.104 5,000 5,000 6.104 5,000 5,000 -
Short-circuitmakingcapacity(O-3min-CO-3min-CO) [A] 6.104 13,000 13,000 6.104 13,000 13,000 -
Opening time [ms] 35...60 35...60 35...60 35...60 35...60
Closing time [ms] 60...90 60...90 60...90 60...90 60...90
Tropicalisation IEC 721-2-1
(1)Itispossibletocombinecurrentlimitingfuseswithbreakingcapacityupto50kA(IEC62271-106-4.107)-Damageclassification“C”(IEC62271-106-4.107.3).
(2)Withreplacementofauxiliarycontactsevery250,000closing-openingoperations.
(3)42kVforfixedversionsandindedicatedUnigearswitchgear
NEPSI.COM - Northeast Power Systems. Inc.
8
1.6. Contactor auxiliary circuits
10auxiliarycontacts(5normallyopenand5normallyclosed)
areavailableonthecontactorforthecustomer’suse,withthe
following characteristics.
Auxiliary contacts characteristics
Rated voltage 24 … 660 V
Rated normal current 10 A
Ratedshorttimecurrent(30ms,20times) 100 A
Ratedfrequency(forAConly) 50 Hz
Ratedinsulationvoltage(DC) 800 V
Ratedinsulationvoltage(AC) 660 V
Insulation test voltage 2500 V
Number of contacts 5 -
Stroke 6 … 7 mm
Maximum contact resistance 10 m
Storage temperature range -20 … +120 °C
Operating temperature range -20 … +70 °C
Emperature rise of contacts 30 K
Breaking capacity
(singlecontactτ=20ms,250Vdc)
250 W
Breaking capacity
(singlecontactτ=20ms,110Vdc)
440 W
Breaking capacity
(twocontactsinseriesτ=20ms,250Vdc)
440 W
1.5. Performances
Contactor VSC7
VSC7/F
VSC7/P
VSC7/PN
VSC7/PNG
VSC7/FN
VSC12
VSC12/F
VSC12/P
VSC12/PN
VSC12/PNG
Rated voltage [kV] 2.2/2.5 3.6 3.6/7.2 6.2/7.2 12
Ultimate performances for:
Motors [kW] 1,000 1,500 1,500 3,000 5,000
Transformers [kVA] 1,100 1,000 2,000 4,000 5,000
Capacitors [kVAR] 1,000 1,500 1,500 3,000 4,800(
1
)
Contactor VSC-S/G
VSC-S/F
VSC-S/PG
VSC-S/PNG
Rated voltage [kV] 2.2/2.5 3.6 3.6/7.2 6.2/7.2 12
Ultimate performances for back-to-back capacitors banks
Rated current [A] 250 250 250 250 250
Max. transient current of the capacitor [kA] 8 8 8 8 8
Max. transient frequency of the capacitor [kHz] 2.5 2.5 2.5 2.5 2.5
(1)Overvoltagesurgearrestersarecompulsorybetweenphasesandbetweenphaseandearth.
NEPSI.COM - Northeast Power Systems. Inc.
9
1.7. Compliance with Standards
V-Contact contactors comply with the Standards of the major
industrialised countries and in particular with the following
Standards:
–IEC62271-106(2011);
–IEC62271-1(2007);
GB/T 14808-2001;
DL/T 593-2006;
IEC 60278 replaced by IEC 62271-200;
–IEC60694(2002)replacedbyIEC62271-1;
–IEC60056(4.104)replacedbyIEC62271-100;
IEC 60470 replaced by IEC 62271-106.
Characteristics of the contacts of the “Coil Continuity Control” and “Capacity Survey” devices
Technology
Relay with air-insulated contacts
Breaking characteristics:
Maximum breaking power 1200VA(onresistiveload)
Maximum breaking voltage 277VAC,30VDC
Maximum breaking current 3 A
Rated current 5 A @ 4 s
Contact characteristics:
Maximum resistance with contact open 150mohm(measureofvoltagedrop6VDC1)
Maximum capacity 1.5 pF
Trip times:
During closing 5.0 ms
During release 2.0 ms
Insulation:
Between contacts and coil 3000Vrms(50Hz/1min.)
Between open contacts 750Vrms(50Hz/1min.)
Resistance with contacts open
Min. 103 Mohm at 500 V DC
1.8. Protection against short-circuit
The value of the installation short-circuit current could exceed
the breaking capacity of the contactor. The contactor must
therefore have adequate protection against short-circuit.
Fuse replacement must only be carried out
by qualified personnel.
NEPSI.COM - Northeast Power Systems. Inc.
10
A
E
C
D
F
B
During handling, take great care not to
stress the insulating parts of the apparatus
and the terminals of the contactor.
Any operation carried out on the contactor
must be done without the presence of
voltage and with the main protection device
open: danger of electrocution and/or severe
burns.
Make sure that operations are carried out
with the main and auxiliary power off.
Onreceipt,immediatelycheckintegrityofthepackingandthe
colourofthe“SHOCKWATCH”indicator(Fig.1)placedonit.
Ifthe“SHOCKWATCH”impactindicatorisWHITE,itmeans
that the packing has not received any notable shocks during
transport.Openthepacking,removethecontactoras
indicatedbelow,andcheckthestateoftheapparatusand
itscorrespondencewiththenameplatedata(seefig.2)with
what is specified in the accompanying shipping note and in
the order confirmation sent by ABB.
Ifthe“SHOCKWATCH”impactindicatorisRED,followthe
instructions indicated on the plate.
Opening the packing does not damage its components and it
can therefore be re-instated using the original material.
Thecontactorisshippedinspecialpacking,intheopen
position.
Each piece of apparatus is protected by a plastic cover
to prevent any infiltration of water during the loading and
unloading stages and to keep the dust off during storage.
Toremovethecontactorfromthepacking,proceedas
follows:
open the plastic bag
– removethecontactor,avoidinganystresstothefunctional
insulating parts and the terminals of the apparatus.
use the special lifting plates for the withdrawable version
check the rating plate characteristics to make sure that the
performances are suitable for the destined application and
that they are those indicated in the order confirmation.
Should any damage or irregularity be noted in the supply
onunpacking,notifyABB(directlyorthroughtheagentor
supplier) as soon as possible and in any case within five days
of receipt.
The apparatus is only supplied with the accessories specified
at the time of ordering and validated in the order confirmation
sent by ABB.
The accompanying documents inserted in the shipping
packing are:
– instructionmanual(thisdocument)
test certification
identification label
fiscal copy of the shipping advice note
electric wiring diagram.
Shock indicator
Fig. 1
Ur VOLTAGE ... kV
Up LIGHTING IMPULSE WITHSTAND VOLTAGE ... kV
Ud POWER FREQUENCY WITHSTAND VOLTAGE ... kV
fr FREQUENCY ... Hz
Ie RATED OPERATING CURRENT ... A
M MASS ... kg
ALTITUDE CLASS < 1000 m
ELECTRICAL DIAGRAM 1VCD4 . . . . . . . . . . (. . . . .)
FIG. 01 . . . . . .
ALXXXXXXXXXXXXX
VACUUM CONTACTOR
V-Contact VSC/P IEC 62271-106
SN 1VC1 AL . . . . . . . . . . . . . . . . PR. YEAR ......
A Trademark
B Type of apparatus
C Serial number
D Characteristics of the apparatus
E Characteristics of the control auxiliaries
F Reference standards
Ua AUXILIARY VOLTAGE . . . . . . . . . . . .
Fig. 2
Made by ABB, Italy
2. Checking on receipt
Other documents which are sent prior to shipment of the
apparatus are:
order confirmation
original shipping advice note
any drawings or documents referring to special
configurations/conditions.
NEPSI.COM - Northeast Power Systems. Inc.
11
3. Handling
The contactor can be lifted using a lifting truck or a fork-lift
truck.
The following precautions must be taken during contactor
handling:
1. Keep the contactor in the upright position.
2. Make sure that the load is balanced on the truck or on the
transport plate/pallet.
3. Interpose protective material between the contactor and
the truck to avoid any damage or scratches.
4. Fix the contactor onto the truck or onto the transport
plate/pallet to prevent it moving or tilting over.
5. Avoidexcessivespeed,suddenstartsandstopsorsharp
changes in direction during contactor handling.
6. Only lift the contactor enough to avoid any obstacles on
the floor.
7. Takecaretoavoidanyimpactswithstructures,other
apparatus or with personnel when handling the contactor.
8. Never lift a contactor over an area where there are people.
9. Duringhandlingoftheapparatus,donotstressthe
insulating parts and the contactor terminals.
Fig. 3a - Handling using a lifting or fork-lift truck.
NEPSI.COM - Northeast Power Systems. Inc.
12
3.1. Handling and lifting using a crane
Insert the lifting plates
– Lift
– Aftertheunpackingandliftingoperations,removetheliftingaccessories.
Fig. 3c - Fixed contactor with fuses
Fig. 3d - Withdrawable contactor
Fig. 3b - Removal of the contactor from the packing and dismantling the
lifting tools.
NEPSI.COM - Northeast Power Systems. Inc.
13
4. Storage
Whenaperiodofstorageisforeseen,theoriginalpacking
must be put back. Store the contactor in a dry dust-free
area. It must not be left outside or in adverse micro-climatic
conditions:ifitisleftwithoutprotection,rustanddeterioration
of the insulation can occur.
Insertspecialhygroscopicpacketsinsidethepacking,with
at least one standard packet per piece of apparatus. Replace
the packets approximately every 6 months.
Should the original packing no longer be available and
immediateinstallationisnotpossible,storeinacovered,
well-ventilated,dry,dust-free,non-corrosiveambient,witha
dryatmosphere,awayfromanyflammablematerialsandata
temperature between – 5 °C and + 40 °C.
Inanycase,avoidanyaccidentalimpactsorpositioning
which stresses the structure of the apparatus.
NEPSI.COM - Northeast Power Systems. Inc.
14
5.3. Normal conditions
Follow the recommendations in the IEC 62271-1 and 62271-106
Standards. In more detail:
Ambient temperature
Maximum + 40 °C
Average maximum over 24 hours + 35 °C
Minimum(accordingtoclass–5),
apparatus for indoor installation
– 5 °C
Humidity
Theaveragevalueoftherelativehumidity,measuredfora
periodlongerthan24hours,mustnotexceed95%.
Theaveragevalueofthewatervapourpressure,measuredfor
aperiodlongerthan24hours,mustnotexceed2.2kPa.
Theaveragevalueoftherelativehumidity,measuredfora
periodlongerthan1month,mustnotexceed90%.
Theaveragevalueofthewatervapourpressure,measuredfor
aperiodlongerthan1month,mustnotexceed1.8kPa
Altitude
< 1000 m above sea level.
5.4. Special conditions
Installations above 1000 m a.s.l.
Possible within the limits allowed by reduction of the dielectric
resistance of air.
For altitudes over 2000 m ask ABB.
Climate - Increase in temperature
In order to avoid the risk of corrosion or other damage in
areas with high humidity and/or rapid large fluctuations
intemperature,takeappropriatemeasures(forexample,
using suitable electric heaters) to prevent any condensation
phenomena.
For special installation requirements or other operating
conditions,pleasecontactABB.
5. Installation
5.1. General
Correct installation is of primary importance. The
manufacturer’sinstructionsmustbecarefullystudiedand
followed. It is good practice to use gloves for handling the
pieces during installation.
The areas involved in the passage of power
conductors or conductors of auxiliary
circuits must be protected against access of
any animals which might cause damage or
disservices.
Thecontactorenclosuremustbeinstalledinaclean,dry
and heated place with good ventilation. It must be easily
accessibleforcleaningandinspection,andmustbelevelled,
placed on the supporting foundations and securely fixed into
position.
Whenthecontactorisconnectedtoacapacitiveload,make
sure that there is a heating element to keep the humidity
down and of suitable size for the compartment where the
contactor is installed. The contactor must always be installed
associatedwithasuitableprotectiondevice(e.g.:fuses).
The fixed version of the V-Contact VSC
contactors must be installed by the customer
so as to guarantee a minimum degree of
protection of IP2X.
5.2. Installation and operating
conditions
The following Standards must be taken into particular
consideration during installation and service:
IEC62271-1/DIN VDE 0101
VDE 0105: Operation of electrical plants
DIN VDE 0141: Earthing systems for electrical installations
with rated voltage higher than 1 kV
All the accident prevention regulations in force in the relative
countries.
NEPSI.COM - Northeast Power Systems. Inc.
15
VSC7
VSC12
5.5. Overall dimensions
5.5.1. VSC fixed contactor
Fortheoveralldimensionsanddistancesbetweenfixingholes,refertofigure4a.
Inanycase,avoidstressingthesupportingstructureofthecontactor:ifnecessary,arrangeslotsinthefixingareatofacilitate
correct positioning of the apparatus.
The assembly positions can be selected between the two shown in figure 4b.
Fig. 4a
(1) Thewidthofthecontactorvariesbasedonthepresenceoftheinterfacing
shafts.
(2) Holeforearthingthecontactor
(3) Themaximum
torquewhichcanbeappliedtotheinterfacingshafts(right
and left) is 2 Nm. The rotation angle is approximately 10°.
(1) Thewidthofthecontactorvariesbasedonthepresenceoftheinterfacing
shafts.
(2) Holeforearthingthecontactor
(3) Themaximum
torquewhichcanbeappliedtotheinterfacingshafts(right
and left) is 2 Nm. The rotation angle is approximately 10°.
NEPSI.COM - Northeast Power Systems. Inc.
16
VSC 7 - VSC 12
E
B
A
C
D
Fig. 4b
5.5.2. VSC/F contactor in fixed version with fuses
Please refer to figures 5a - 5b for the overall dimensions and the distances between the fixing holes.
Inanycase,avoidstressingthesupportingstructureofthecontactor:ifnecessary,prepareslotsinthefixingareatofacilitate
correct positioning of the apparatus.
Thecontactormustbeinstalledonthefloorwithmovingcontactsatthebottom(figure5c).
Installation of fixed contactors
The performance of the contactor remains unaltered in the installation positions indicated below:
VSC 7 - VSC 12
A) Floor-mounted with moving contacts at the bottom.
B) Wall-mounted with horizontal moving contacts and
terminals at the bottom.
C) Wall-mounted with horizontal moving contacts and
terminals at the top.
D) Wall-mounted with horizontal moving contacts with
interruptersonthefront(orrear)withverticalterminals.
E) Ceiling-mounted with moving contacts at the top.
VSC 7/F - VSC 12/F - VSC 7/FN
A) Floor-mounted with moving contacts at the bottom.
NEPSI.COM - Northeast Power Systems. Inc.
17
VSC7/F
11
195
332
15
115 115
338
350
91
374
578
598
22
/36/70
22/36/
70
450
466
132
40
28
8.5
8.5
30
4
215
291
220 216
319
615
623
10
12
12
11
28
VSC7/FN
(1) Thewidthofthecontactorvariesaccordingtothepresenceofthe
interfacing shafts
(2) Holeforgroundingthecontactor
(3) Themaximumtorquewhichcanbeappliedtotheinterfacingshafts(right
and left) is 2 Nm. The rotation angle is about 10°.
Fig. 5a
Fig. 5b
NEPSI.COM - Northeast Power Systems. Inc.
18
VSC12/F
(1) Thewidthofthecontactorvariesaccordingtothepresenceofthe
interfacing shafts
(2) Holeforgroundingthecontactor
(3) Themaximumtorquewhichcanbeappliedtotheinterfacingshafts(right
and left) is 2 Nm. The rotation angle is about 10°.
Fig. 5c
Fig. 5d
Installation of the fixed contactor with VSC/F - VSC/FN fuses
NEPSI.COM - Northeast Power Systems. Inc.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48