FläktGroup EUPZ-08 Filter monitor Installation guide

Type
Installation guide
Fläkt Woods 3189 GB 03.01 1 Specifications are subject to alteration without notice
EU Air Handling Unit INSTALLATION
EUPZ-08 Filter monitor
Delivery
The EUPZ-08 filter monitor (pressure switch) is deliv-
ered complete with hoses for mounting on the unit.
Commissioning
Remove the plastic cover for presetting the set point. Set
the required set point directly on the scale, which has
been calibrated at the factory for vertical installation of
the filter monitor.
For horizontal installation:
Cover facing upwards: preset the set point about 50 Pa
lower than the required value.
Cover facing downwards: preset the set point about 50
Pa higher than the required value.
Breaking diagram
Breaking function
on increasing pressure
P-1 open
P-2 closed
on decreasing pressure
P-2 open
P-1 closed
Max. permissible pressure drop rise, Pa
Filter EU 2 EU 3 EU 4 EU 5 EU 6 EU 7 EU 8 EU 9
(G 70) (G 85) (G 90) (F 45) (F 65) (F 85) (F 95) (F 95)
EUPA 70 70 70
EUPB – 70 70 100 –
EUPC 70 70 100 100 100 100 100
P
COM NO NC
P21
Fig. 1
Fig. 2. EUPZ-08 filter monitor diagrammatic arrangement
The tapping marked with
+ must be connected to
the hose for the higher
pressure.
Adjustment range Max. supply Ambient
Pa mbar pressure, kPa temperature
40-300 0,4-3 40 15 +60°C
Type
LGW 3A2
  • Page 1 1