  • Hello! I am an AI chatbot trained to assist you with the Mircom LT-1000 RM-306 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
LT-1000
Mar 2004
Page
1
of
2
Model RM-306 Six Relay Adder Module
The RM-306 provides six programmable relays. It mounts below the FA-300 main fire alarm board using the 2 screws
provided. Before mounting the relay adder module, program the relays using the jumpers on the board. The jumpers
located above
each relay on the RM-306 are used to configure the relays. The jumpers located below the relays are
used to select either normally open contacts or normally closed contacts. The ribbon cable from P1 of the RM-306 is
connected to P6 on the Main Fire Alarm Board.
Figure 1: RM-306 Six Relay Adder module
P1
: Cable from RM-306 Relay Adder Module connects to P6 on Main Fire Alarm Board.
Programming the relays
A typical relay circuit is shown below in Figure 2 with the jumper locations and descriptions.
Note:
Relay programming should be done before installing the board into the fire alarm backbox.
Figure 2: RM-306 Relay programming
LT-1000
Mar 2004
Page
2
of
2
ELECTRICAL SPECIFICATIONS
Contact Rating: Normally Open NO, Normally Closed NC
28V DC per contact
1A resistive load max
Current Consumption: Standby: 0 mA
Alarm: 80 mA
/