  • Hello! I am an AI chatbot trained to assist you with the Mircom LT-1006 OCAC Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
LT-1006
Mar 2004 Page 1 of 2
OCAC-304/302 Output Class-A Converter Adder Module
The Model OCAC-304 Output Class A Converter Adder Module is used to convert 4 Class B output circuits in
the FA-300 Fire Alarm Panel to 4 Class A output circuits. It mounts under the FA-300 main fire alarm board
near the output terminal blocks on the right hand side.
The Model OCAC-302 Output Class A Converter Adder Module is used to convert 2 Class B output circuits in
the FA-300 Fire Alarm Panel to 2 Class A output circuits. It mounts under the FA-300 main fire alarm board
near the input terminal blocks.
- +- +- +- +- +- +- +- +- +- +- +- +- +- +- +- +
DET 1DET 2DET 3DET 4DET 5DET 6DET 7DET 8DET 9DET 10DET 11DET 12SIG 1SIG 2SIG 3SIG 4
TO PR-300 MODULE
TO RM-312/RM-306 RELAY
MODULE
+
S - +NC NOCNC NOCNC NOCNC NOC
+-+-
COM(+)
COM(-)
TRLTRB R T R T R T R T
RES CO RES CO
LINE1LINE2
RS-
485
AUX. RELAY
ALARM
RELAY
SUPERVISORY
RELAY
TROUBLE
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UNFILTERED
RTI
PORT
LT-1006
Mar 2004 Page 2 of 2
OCAC-304/302 Output Class A Converter Adder Modules
Indicating circuits must be wired from the OCAC-304/302 to the main Fire Alarm board. For example indicating
circuit 1 positive (red wire) and negative (black wire) is wired from the Class A converter module to the positive
and negative terminals of Indicating circuit 1 on the Main Fire Alarm board.
The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and
then wired back to the SIGNAL RET positive and negative.
ELECTRICAL SPECIFICATIONS:
Current Consumption: Standby: 0 mA
Alarm: 0 mA
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
/